STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER SPD REQUIREMENTS<br />

• Each device shall have an indicator lamp visible from the front of the device showing that the<br />

module has power applied <strong>and</strong> that the protection integrity has not been compromised. Alarm relay<br />

contacts to remotely report device failure may be offered but are not required.<br />

• The minimum pulse life or durability requirements <strong>and</strong> the voltage protection level shall be as<br />

specified in Table 7-4 <strong>for</strong> the respective Maximum Continuous Operating Voltage (MCOV) listed.<br />

• Installation of Type 3 SPDs on each critical load is recommended in locations highly vulnerable to<br />

transient surges or lightning activity when the critical load is located greater than 3 m (10 ft.) of<br />

conductor length from the Type 1 SPD. Where the load is located between 3 to 15.2 m (10 to 50 ft.)<br />

of conductor length from Type 1 devices a Type 3 device is optional. Where the load is located<br />

greater than 15.2 m (50 ft.) of conductor length (7.6 m (25 ft.) of circuit length) from the Type 1<br />

device, a Type 3 device is highly recommended. (See Table 7-3.)<br />

TABLE 7-3 SPD REQUIREMENTS BASED ON CONDUCTOR LENGTH<br />

0 - 3 m<br />

(0 - 10 ft.)<br />

Conductor Length *<br />

3 - 15.2 m<br />

(10 - 50 ft.)<br />

Type 1 Required Type 1 Required<br />

Type 3 Optional<br />

> 15.2 m<br />

(>50 ft.)<br />

Type 1 Required<br />

Type 3 Highly recommended**<br />

* Lengths shown denote CONDUCTOR length. The CIRCUIT distance is ½ of conductor<br />

length shown.<br />

**In applications <strong>for</strong> st<strong>and</strong>alone pole- or pad-mounted cabinets, where an SPD or a Type 2 SPD is not<br />

installed on the Utility Panelboard, Type 3 devices shall be installed on all loads.<br />

• The device shall be UL 1449, 2nd Edition listed. Devices may also con<strong>for</strong>m to the international CE<br />

certification mark, <strong>and</strong> tested to clause 7.10. A test report from a Nationally Recognized Testing<br />

Laboratory (NRTL), NAVLAP or A2LA, or a Certified UL client testing data laboratory detailing<br />

the procedures used, <strong>and</strong> the results obtained shall be made available to the Motorola National Site<br />

Design <strong>and</strong> Integration Process <strong>and</strong> Product Manager.<br />

• Each multiple receptacle outlet strip type device incorporating telephone or data circuit protection<br />

shall be UL 1449 <strong>and</strong> UL 497A listed or recognized. Devices may con<strong>for</strong>m to the international CE<br />

certification mark.<br />

68P81089E50-B 9/1/05 7-31