AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES<br />

Electrical meter <strong>and</strong> main<br />

service disconnect are<br />

located on the cabinet<br />

exterior, an adjacent<br />

pedestal or utility pole.<br />

See Notes 1 <strong>and</strong> 2.<br />

Main Service<br />

Disconnect<br />

Meter<br />

Utility Feed<br />

AC<br />

240/120 Single Phase<br />

To Alarms Panel<br />

(Recommended)<br />

SPD<br />

(Surge Suppressor)<br />

Type 1 or 2 ,<br />

optional<br />

Utility<br />

Panelboard<br />

See Note 2<br />

All Loads<br />

St<strong>and</strong> alone Pole or Pad mounted equipment<br />

cabinet with single Repeater, Base Station,<br />

Receiver or Control Station.<br />

Type 3 SPD required<br />

<strong>for</strong> all equipment<br />

loads.<br />

See Note 6<br />

NOTES: 1. The main service disconnect may be located outside the equipment pole or pad mounted cabinet, typically on the cabinet<br />

exterior, an adjacent pedestal or utility pole.<br />

2. The Main service disconnect may be a part of the Utility Panelboard.<br />

3. When installed the Type 1 or Type 2 SPD shall be installed per the manufacturer's installation instructions.<br />

4. All conductors between the SPD <strong>and</strong> the associated disconnecting device shall be as short as possible <strong>and</strong> routed<br />

together with a minimal number of bends or angles of less than 90 degrees.<br />

5. The SPD disconnecting devices should be installed in the top most space available in the Utility Panelboard.<br />

6. Installation of Type 3 SPDs on each load is required unless a Type 1 SPD is installed on the Utility Panelboard.<br />

FIGURE 7-17 SPD INTERCONNECT BLOCK DIAGRAM ‘P’<br />

7-26 68P81089E50-B 9/1/05