AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES<br />

Electrical meter <strong>and</strong> main<br />

service disconnect are<br />

located on the cabinet<br />

exterior, an adjacent<br />

pedestal or utility pole.<br />

See Notes 1 & 2<br />

Main Service<br />

Disconnect<br />

Meter<br />

Utility Feed<br />

AC<br />

240/120 Single Phase<br />

NOTES:<br />

To Alarms Panel<br />

(Recommended)<br />

SPD<br />

(Surge Suppressor)<br />

Type 1 (SAD/MOV)<br />

Utility<br />

Panelboard<br />

See Note 2<br />

Non-Critical<br />

Loads<br />

Type 3 SPD optional when greater<br />

than 10 conductor feet from<br />

panelboard.<br />

To Alarms Panel<br />

1. The main service disconnect may be located outside the pole or pad mounted equipment cabinet, typically on the cabinet<br />

exterior, an adjacent pedestal or utility pole.<br />

2. The main service disconnect may be an integral part of the Utility Panelboard.<br />

3. The UPS may not be present in which case all loads will be fed from the Utility Panelboard<br />

4. The Type 1 SPD shall be installed per the manufacturer's installation instructions.<br />

5. All conductors between the SPD <strong>and</strong> the associated disconnecting device shall be as short as possible <strong>and</strong> routed together<br />

with a minimal number of bends or angles of less than 90 degrees.<br />

6. The SPD disconnecting device should be installed in the top most space available in the Utility Panelboard.<br />

7. Installation of Type 3 SPDs on critical <strong>and</strong> non critical loads, although optional, is recommended where the level of<br />

exposure is high.<br />

FIGURE 7-15 SPD INTERCONNECT BLOCK DIAGRAM ‘N’<br />

Pole or Pad mounted equipment cabinet(s)<br />

UPS<br />

See Note 2<br />

UPS<br />

Panelboard<br />

Type 3 SPD<br />

optional<br />

Critical<br />

Loads<br />

7-24 68P81089E50-B 9/1/05