AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES To Alarms Panel (Recommended) To Alarms Panel (Recommended) Shelter, equipment room or area. SPD (Surge Suppressor) Type 1 SAD/MOV SPD (Surge Suppressor) Type 2 MOV To Alarms Panel Electrical meter and service disconnect are located outside the equipment room or area within another building or structure. Utility Panelboard UPS Automatic Transfer Switch Main Panelboard with a main breaker Circuit Breaker Main Service Disconnect Type 3 SPD optional Meter To Alarms Panel FIGURE 7-7 SPD INTERCONNECT BLOCK DIAGRAM ‘F’ NOTES: 1. The main service disconnect is located outside the equipment shelter, room or area, typically within another building or structure. 2. The service to the equipment shelter, room or area is 3 conductors with ground for single phase or 4 conductors with ground for 3 phase. 3. The step-down or isolation transformer creates a separately derived system where the neutral and ground conductors are bonded together within the transformer and bonded to the equipment room MGB. The main disconnect ground and the MGB shall be bonded to the site grounding electrode system. 4. The Main panelboard shall use a main disconnecting device to serve the equipment area. 5. The Type 1 and Type 2 SPDs shall be installed per the manufacturer’s installation instructions. 6. All conductors between the SPDs and the associated disconnecting device shall be as short as possible and routed together with a minimal number of bends or angles of less than 90 degrees. 7. The SPD disconnecting devices should be installed in the top most space available in the Utility Panelboard. 8. Installation of Type 3 SPDs on each critical load is recommended where the level of exposure is high. 9. Installation of Type 3 SPDs on each non-critical load that is located greater than 3 m (10 ft.) of conductor length from the panelboard is recommended where the level of exposure is high. 7-16 68P81089E50-B 9/1/05 UPS Panelboard Non-Critical Loads Critical Loads Generator Step Down or Isolation Transformer Utility Feed AC Type 3 SPD optional when greater than 10 conductor feet from panelboard. 240/120 Single Phase 208/120 3 Phase 480/277 3 Phase
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER SPD REQUIREMENTS To Alarms Panel (Recommended) Equipment room or area. SPD (Surge Suppressor) Type 1 SAD/MOV To Alarms Panel Typical distribution on floor within multi- story structure Electrical meter and service disconnect Switchgear are located outside the equipment room or area within the same structure. UPS Utility Panelboard with a main breaker Step Down or Isolation Transformer Circuit Breaker Distribution Panelboard Main Service Disconnect Switchgear Type 3 SPD optional Meter FIGURE 7-8 SPD INTERCONNECT BLOCK DIAGRAM ‘G’ 1. The main service disconnect is located outside the equipment room or area within the same structure. Additional distribution panelboards may be located within the structure, typically one per floor. 2. The service to the equipment room or area is 3 conductors with ground for single phase or 4 conductors with ground for 3 phase. 3. The step-down or isolation transformer creates a separately derived system where the neutral and ground conductors are bonded together within the transformer and bonded to the equipment room MGB. The main disconnect ground and the MGB shall be bonded to the site grounding electrode system at the same point. 4. The Utility panelboard shall use a main disconnecting device to serve the equipment area. 5. The Type 1 SPD shall be installed per the manufacturer’s installation instructions. 6. All conductors between the SPD and the associated disconnecting device shall be as short as possible and routed together with a minimal number of bends or angles of less than 90 degrees. 7. The SPD disconnecting device should be installed in the topmost space available in the Utility Panelboard. 8. Installation of Type 3 SPDs on each critical load is recommended where the level of exposure is high. 9. Installation of Type 3 SPDs on each non-critical load that is located greater than 3 m (10 ft.) of conductor length from the panelboard is recommended where the level of exposure is high. 68P81089E50-B 9/1/05 7-17 UPS Panelboard Non-Critical Loads Type 3 SPD optional when greater than 10 conductor feet from panelboard. Critical Loads Feeders to other loads on same floor Utility Feed AC 240/120 Single Phase 208/120 3 Phase 480/277 3 Phase NOTES:
- Page 275 and 276: STANDARDS AND GUIDELINES FOR COMMUN
- Page 277 and 278: STANDARDS AND GUIDELINES FOR COMMUN
- Page 279 and 280: STANDARDS AND GUIDELINES FOR COMMUN
- Page 281 and 282: STANDARDS AND GUIDELINES FOR COMMUN
- Page 283 and 284: STANDARDS AND GUIDELINES FOR COMMUN
- Page 285 and 286: STANDARDS AND GUIDELINES FOR COMMUN
- Page 287 and 288: STANDARDS AND GUIDELINES FOR COMMUN
- Page 289 and 290: STANDARDS AND GUIDELINES FOR COMMUN
- Page 291 and 292: STANDARDS AND GUIDELINES FOR COMMUN
- Page 293 and 294: STANDARDS AND GUIDELINES FOR COMMUN
- Page 295 and 296: STANDARDS AND GUIDELINES FOR COMMUN
- Page 297 and 298: STANDARDS AND GUIDELINES FOR COMMUN
- Page 299 and 300: STANDARDS AND GUIDELINES FOR COMMUN
- Page 301 and 302: STANDARDS AND GUIDELINES FOR COMMUN
- Page 303 and 304: STANDARDS AND GUIDELINES FOR COMMUN
- Page 305 and 306: STANDARDS AND GUIDELINES FOR COMMUN
- Page 307 and 308: STANDARDS AND GUIDELINES FOR COMMUN
- Page 309 and 310: STANDARDS AND GUIDELINES FOR COMMUN
- Page 311 and 312: CHAPTER 7 SURGE PROTECTIVE DEVICES
- Page 313 and 314: STANDARDS AND GUIDELINES FOR COMMUN
- Page 315 and 316: STANDARDS AND GUIDELINES FOR COMMUN
- Page 317 and 318: STANDARDS AND GUIDELINES FOR COMMUN
- Page 319 and 320: STANDARDS AND GUIDELINES FOR COMMUN
- Page 321 and 322: STANDARDS AND GUIDELINES FOR COMMUN
- Page 323 and 324: STANDARDS AND GUIDELINES FOR COMMUN
- Page 325: STANDARDS AND GUIDELINES FOR COMMUN
- Page 329 and 330: STANDARDS AND GUIDELINES FOR COMMUN
- Page 331 and 332: STANDARDS AND GUIDELINES FOR COMMUN
- Page 333 and 334: STANDARDS AND GUIDELINES FOR COMMUN
- Page 335 and 336: STANDARDS AND GUIDELINES FOR COMMUN
- Page 337 and 338: STANDARDS AND GUIDELINES FOR COMMUN
- Page 339 and 340: STANDARDS AND GUIDELINES FOR COMMUN
- Page 341 and 342: STANDARDS AND GUIDELINES FOR COMMUN
- Page 343 and 344: STANDARDS AND GUIDELINES FOR COMMUN
- Page 345 and 346: STANDARDS AND GUIDELINES FOR COMMUN
- Page 347 and 348: STANDARDS AND GUIDELINES FOR COMMUN
- Page 349 and 350: STANDARDS AND GUIDELINES FOR COMMUN
- Page 351 and 352: STANDARDS AND GUIDELINES FOR COMMUN
- Page 353 and 354: STANDARDS AND GUIDELINES FOR COMMUN
- Page 355 and 356: STANDARDS AND GUIDELINES FOR COMMUN
- Page 357 and 358: STANDARDS AND GUIDELINES FOR COMMUN
- Page 359 and 360: STANDARDS AND GUIDELINES FOR COMMUN
- Page 361 and 362: STANDARDS AND GUIDELINES FOR COMMUN
- Page 363 and 364: CHAPTER 8 MINIMIZING SITE INTERFERE
- Page 365 and 366: STANDARDS AND GUIDELINES FOR COMMUN
- Page 367 and 368: STANDARDS AND GUIDELINES FOR COMMUN
- Page 369 and 370: STANDARDS AND GUIDELINES FOR COMMUN
- Page 371 and 372: STANDARDS AND GUIDELINES FOR COMMUN
- Page 373 and 374: CHAPTER 9 EQUIPMENT INSTALLATION 9
- Page 375 and 376: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER SPD REQUIREMENTS<br />
To Alarms Panel<br />
(Recommended)<br />
Equipment room or area.<br />
SPD<br />
(Surge Suppressor)<br />
Type 1 SAD/MOV<br />
To Alarms Panel<br />
Typical distribution<br />
on floor within<br />
multi- story<br />
structure<br />
Electrical meter <strong>and</strong><br />
service disconnect<br />
Switchgear are located<br />
outside the equipment<br />
room or area within the<br />
same structure.<br />
UPS<br />
Utility<br />
Panelboard<br />
with a main<br />
breaker<br />
Step Down or<br />
Isolation<br />
Trans<strong>for</strong>mer<br />
Circuit<br />
Breaker<br />
Distribution<br />
Panelboard<br />
Main Service<br />
Disconnect<br />
Switchgear<br />
Type 3 SPD<br />
optional<br />
Meter<br />
FIGURE 7-8 SPD INTERCONNECT BLOCK DIAGRAM ‘G’<br />
1. The main service disconnect is located outside the equipment room or area within the same structure. Additional<br />
distribution panelboards may be located within the structure, typically one per floor.<br />
2. The service to the equipment room or area is 3 conductors with ground <strong>for</strong> single phase or 4<br />
conductors with ground <strong>for</strong> 3 phase.<br />
3. The step-down or isolation trans<strong>for</strong>mer creates a separately derived system where the neutral <strong>and</strong> ground conductors are<br />
bonded together within the trans<strong>for</strong>mer <strong>and</strong> bonded to the equipment room MGB. The main disconnect ground <strong>and</strong> the MGB<br />
shall be bonded to the site grounding electrode system at the same point.<br />
4. The Utility panelboard shall use a main disconnecting device to serve the equipment area.<br />
5. The Type 1 SPD shall be installed per the manufacturer’s installation instructions.<br />
6. All conductors between the SPD <strong>and</strong> the associated disconnecting device shall be as short as possible <strong>and</strong> routed together<br />
with a minimal number of bends or angles of less than 90 degrees.<br />
7. The SPD disconnecting device should be installed in the topmost space available in the Utility Panelboard.<br />
8. Installation of Type 3 SPDs on each critical load is recommended where the level of exposure is high.<br />
9. Installation of Type 3 SPDs on each non-critical load that is located greater than 3 m (10 ft.) of conductor length from the<br />
panelboard is recommended where the level of exposure is high.<br />
68P81089E50-B 9/1/05 7-17<br />
UPS<br />
Panelboard<br />
Non-Critical<br />
Loads<br />
Type 3 SPD optional<br />
when greater than 10<br />
conductor feet from<br />
panelboard.<br />
Critical<br />
Loads<br />
Feeders to other<br />
loads on same<br />
floor<br />
Utility Feed<br />
AC<br />
240/120 Single Phase<br />
208/120 3 Phase<br />
480/277 3 Phase<br />
NOTES: