AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES<br />

To Alarms Panel<br />

(Recommended)<br />

To Alarms Panel<br />

(Recommended)<br />

Shelter, equipment room or area.<br />

SPD<br />

(Surge<br />

Suppressor)<br />

Type 1 SAD/MOV<br />

SPD<br />

(Surge<br />

Suppressor)<br />

Type 2 MOV<br />

Disconnect<br />

Switch<br />

To Alarms Panel<br />

Main Service<br />

Disconnect<br />

Utility<br />

Panelboard UPS<br />

Automatic<br />

Transfer<br />

Switch<br />

Type 3 SPD<br />

optional<br />

To Alarms<br />

Panel<br />

Utility Feed<br />

AC<br />

240/120 Single Phase<br />

208/120 3 Phase<br />

FIGURE 7-5 SPD INTERCONNECT BLOCK DIAGRAM ‘D’<br />

NOTES: 1. All electrical panelboards shown are collocated within the shelter, room or equipment area.<br />

2. The SPDs shall be installed per the manufacturer’s installation instructions.<br />

3. All conductors between the SPD <strong>and</strong> the associated disconnecting devices shall be as<br />

short as possible <strong>and</strong> routed together with a minimal number of bends or angles.<br />

4. The SPD disconnecting device in the Utility Panelboard should be installed in the top most space available.<br />

5. Installation of Type 3 SPDs on each critical load is recommended where the level of exposure is high.<br />

6. Installation of Type 3 SPDs on each non-critical load that is located greater than 3 m (10 ft.) of conductor length from the<br />

panelboard is recommended where the level of exposure is high.<br />

7-14 68P81089E50-B 9/1/05<br />

Meter<br />

Critical<br />

Loads<br />

Non-Critical<br />

Loads UPS<br />

Panelboard<br />

Type 3 SPD<br />

optional when<br />

greater than 10<br />

conductor feet from<br />

panelboard.<br />

Generator