STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER SPD REQUIREMENTS<br />

Main Service<br />

Disconnect<br />

Meter<br />

To Alarms Panel<br />

(Recommended)<br />

SPD<br />

(Surge Suppressor)<br />

Type 1 SAD/MOV<br />

Utility<br />

Panelboard<br />

Type 3 SPD optional<br />

when greater than<br />

10 conductor feet<br />

from panelboard.<br />

Utility Feed<br />

AC<br />

240/120 Single Phase<br />

208/120 3 Phase<br />

Non-Critical<br />

Loads<br />

To Alarms Panel<br />

NOTES: 1. The main service disconnect may be an integral part of the Utility Panelboard.<br />

2. The main service disconnect <strong>and</strong> Utility Panelboard are collocated within the equipment area.<br />

3. The Type 1 SPD shall be installed per the manufacturer's installation instructions.<br />

4. All conductors between the SPD <strong>and</strong> the associated disconnecting device (60 Amp<br />

Circuit Breaker typical) shall be as short as possible <strong>and</strong> routed together with a minimal<br />

number of bends or angles of less than 90 degrees.<br />

5. The SPD disconnecting device should be installed in the top most space available within the panelboard.<br />

6. Installation of Type 3 SPDs on each critical load is recommended where the level of exposure is high.<br />

7. Installation of Type 3 SPDs on each non-critical load that is located greater than 3 m (10 ft.) of conductor length from the<br />

panelboard is recommended where the level of exposure is high.<br />

FIGURE 7-2 SPD INTERCONNECT BLOCK DIAGRAM ‘A’<br />

68P81089E50-B 9/1/05 7-11<br />

UPS<br />

Shelter, equipment room or area.<br />

UPS<br />

Panelboard<br />

Type 3 SPD<br />

optional<br />

Critical<br />

Loads