AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES<br />

TABLE 7-1 REQUIRED TVSS PROTECTION FOR VARIOUS SERVICE TYPES (CONTINUED)<br />

Service Type<br />

• Within other building or<br />

structure utilizing a<br />

separately derived system<br />

supplying equipment area<br />

C<br />

(Figure 7-4)<br />

St<strong>and</strong>-alone Building/shelter with Generator<br />

Main service disconnect <strong>and</strong> all<br />

panelboards located within the<br />

same shelter, room or equipment<br />

area<br />

Main service disconnect located<br />

outside the equipment area<br />

(greater than 3 m (10 ft.)):<br />

• At fence or property line<br />

utilizing a separately<br />

derived system supplying<br />

equipment area<br />

• Within other building or<br />

structure utilizing a<br />

separately derived system<br />

supplying equipment area<br />

D<br />

(Figure 7-5)<br />

E<br />

(Figure 7-6)<br />

F<br />

(Figure 7-7)<br />

Type 2<br />

or<br />

Type 1 2<br />

Type 2<br />

or<br />

Type 1 2<br />

Type 2<br />

or<br />

Type 1 2<br />

Equipment Area Located within a Larger Structure without Generator<br />

Main service disconnect located<br />

in another part of same structure<br />

utilizing a separately derived<br />

system supplying equipment area<br />

Main service disconnect located<br />

within another structure utilizing<br />

a separately derived system<br />

supplying equipment area<br />

G<br />

(Figure 7-8)<br />

H<br />

(Figure 7-9)<br />

Equipment Area Located within a Larger Structure with Generator<br />

Main service disconnect located<br />

in another part of same structure<br />

utilizing a separately derived<br />

system supplying equipment area<br />

Main service disconnect located<br />

within another structure utilizing<br />

a separately derived system<br />

supplying equipment area<br />

Interconnect<br />

Diagram<br />

(Fig. No.)<br />

I<br />

(Figure 7-10)<br />

J<br />

(Figure 7-11)<br />

Main<br />

Disconnect<br />

Main<br />

Panelboard<br />

or Feeder<br />

Side of ATS<br />

Type 2<br />

or<br />

Type 1 2<br />

Type 2<br />

or<br />

Type 1 2<br />

Utility<br />

Panelboard<br />

Utility<br />

Panelboard<br />

in Other<br />

Bldg./Shelter<br />

Equipment<br />

(If > 3 m<br />

(10 ft.) from<br />

panelboard)<br />

Type1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

7-8 68P81089E50-B 9/1/05