STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER SPD REQUIREMENTS<br />

7.4.1.2 INSTALLATION WITH MAIN DISCONNECT AWAY FROM AREA<br />

For installations where the main disconnecting means is located away from the shelter, room or<br />

equipment area (Diagrams B through J; Figures 7-6 through 7-11 on pages 7-15 through 7-20,<br />

respectively), a separately derived electrical system is an option within the shelter, room or equipment<br />

area to establish the neutral-ground bond. Other means are described in “Location of Neutral-Ground<br />

Bond” on page 6-4.<br />

A separately derived electrical system can be achieved by installation of a step down or isolation<br />

trans<strong>for</strong>mer, or by the installation of a suitable UPS that qualifies as a separately derived electrical<br />

system. Similarly, when a power feed is provided to another building, shelter or equipment area<br />

(Diagrams K through M; Figures 7-12 through 7-14 on pages 7-21 through 7-23, respectively), a<br />

separately derived electrical system should be installed within that shelter, building or equipment area to<br />

minimize potential damage resulting from power line anomalies generated by loads or lightning activity<br />

within that shelter, building or equipment area.<br />

7.4.1.3 INSTALLATION WITH EQUIPMENT INSTALLED IN POLE OR PAD MOUNTED CABINETS<br />

For installations where the equipment is installed within pole or pad mounted cabinets (Diagrams N<br />

through P; Figures 7-15 through 7-17 on pages 7-24 through 7-26), SPDs are required as specified in<br />

Table 7-1. Where a pole or pad mounted cabinet is installed <strong>and</strong> the electrical feeder originates from<br />

within another building or shelter (Diagram Q; Figure 7-18 on page 7-27), a Type 3 SPD is required to<br />

be installed on all equipment within the cabinet. In installations of this type it may be desirable to install<br />

additional SPDs at the branch circuit panelboard. Where the level of exposure is high a Type 1 SPD is<br />

recommended. See Table 7-1 <strong>and</strong> footnotes <strong>for</strong> further in<strong>for</strong>mation.<br />

NOTE: Single conversion (<strong>for</strong>ward transfer mode) UPS systems do not provide transient voltage surge<br />

suppression. Double conversion (reverse transfer mode or rectifier-inverter) UPS systems offer surge<br />

suppression to source induced transients. No surge suppression is af<strong>for</strong>ded <strong>for</strong> load induced transients<br />

on either type.<br />

TABLE 7-1 REQUIRED TVSS PROTECTION FOR VARIOUS SERVICE TYPES<br />

Service Type<br />

Interconnect<br />

Diagram<br />

(Fig. No.)<br />

St<strong>and</strong>-alone Building/shelter without Generator<br />

Main service disconnect <strong>and</strong> all<br />

panelboards located within the<br />

same shelter, room or equipment<br />

area<br />

Main service disconnect located<br />

outside the equipment area<br />

(greater than 3 m (10 ft.)):<br />

• At fence or property line<br />

utilizing a separately<br />

derived system supplying<br />

equipment area<br />

A<br />

(Figure 7-2)<br />

B<br />

(Figure 7-3)<br />

Main<br />

Disconnect<br />

Main<br />

Panelboard<br />

or Feeder<br />

Side of ATS<br />

Utility<br />

Panelboard<br />

Utility<br />

Panelboard<br />

in Other<br />

Bldg./Shelter<br />

Equipment<br />

(If > 3 m<br />

(10 ft.) from<br />

panelboard)<br />

Type 1 Type 3 1<br />

Type 1 Type 3 1<br />

68P81089E50-B 9/1/05 7-7