STANDARDS AND GUIDELINES FOR COMMUNICATION SITES INTRODUCTION<br />

Telephone service<br />

conduit<br />

Electrical<br />

service conduit<br />

Electrical Service<br />

Main Disconnect<br />

with Type 1 SPD<br />

Interior MGB<br />

Transmission<br />

Line SPDs<br />

bonded to MGB<br />

Equipment<br />

Room<br />

Electrical service conduit<br />

Cable TV<br />

Electrical Service<br />

Main Disconnect with<br />

Type 1 SPD<br />

Telephone <strong>and</strong> data<br />

circuit secondary<br />

SPDs must be<br />

installed at equipment<br />

within the CEB area.<br />

MGB<br />

SSGB<br />

Tower<br />

Antennas, transmission lines <strong>and</strong><br />

exterior ground omitted <strong>for</strong> clarity.<br />

E-911 equipment <strong>and</strong><br />

computer area<br />

External Ground<br />

System<br />

Telephone/data circuit<br />

backboard with primary SPDs<br />

Conduit to Dispatch Center<br />

Corridor<br />

Telephone <strong>and</strong> data circuit<br />

secondary SPDs must be installed<br />

at the equipment within the<br />

equipment room.<br />

Conduit(s) between Office Building <strong>and</strong> Dispatch Center<br />

AC Power, Telephone Circuits, Cable TV, CCTV, <strong>and</strong> card<br />

access control cables must all enter within the same area.<br />

Primary SPDs on CCTV, Cable TV <strong>and</strong> card access control cable bonded to MGB.<br />

CEB area<br />

Telephone circuit backboard<br />

with secondary SPDs<br />

Telephone/data circuit backboard with primary SPDs<br />

SSGB<br />

Dispatch Center<br />

St<strong>and</strong> alone Dispatch Center with separate electrical service.<br />

Telephone/data feed from adjacent Office Building<br />

Office Building with equipment room. Building is<br />

served by separate electrical service.<br />

CCTV, Cable TV <strong>and</strong> card access control in Control Center furniture.<br />

CCTV camera mounted on building<br />

Card Access control cable<br />

Parking Area<br />

Gate with card<br />

access control<br />

FIGURE 7-1 MINIMUM REQUIRED SPD FOR TYPICAL INSTALLATION<br />

68P81089E50-B 9/1/05 7-3