GENERATOR OUTPUT AND DERATING CONSIDERATIONS CHAPTER 6: POWER SOURCES<br />

6.9.7 GENERATOR INSTALLATION GROUNDING<br />

All generators, fuel storage tanks above or at grade level, <strong>and</strong> fences discussed within this chapter shall<br />

be grounded as described below.<br />

6.9.7.1 INDOOR GENERATOR GROUNDING<br />

Generator systems located indoors shall be bonded to the internal grounding system as follows:<br />

• Using the intended chassis grounding connection on the generator, the generator shall be bonded to<br />

the internal Master Ground Bus Bar in accordance with methods specified in Chapter 5, “Internal<br />

Grounding (Earthing).”<br />

• A transfer switch (if not part of the generator unit) shall be bonded to the interior Master Ground<br />

Bus Bar in accordance with methods specified in Chapter 5, “Internal Grounding (Earthing).”<br />

6.9.7.2 OUTDOOR GENERATOR GROUNDING<br />

Generator systems located outdoors shall be bonded to the external grounding system as follows:<br />

• Using the intended chassis grounding connection on the generator, the generator shall be bonded to<br />

the external site Ground Ring in accordance with methods specified in Chapter 4, “External<br />

Grounding (Earthing).”<br />

• If a metallic fuel tank is utilized, the fuel tank shall be bonded to the external site Ground Ring in<br />

accordance with methods specified in Chapter 4, “External Grounding (Earthing).”<br />

• Metallic fencing surrounding the generator installation shall be bonded to the external site Ground<br />

Ring in accordance with methods specified in Chapter 4, “External Grounding (Earthing).”<br />

• A transfer switch (if not part of the generator unit) is typically installed in the site building or<br />

shelter <strong>and</strong> collocated with the site electrical service panel. In this case, the transfer switch shall be<br />

bonded to the interior Master Ground Bus Bar in accordance with methods specified in Chapter 5,<br />

“Internal Grounding (Earthing).”<br />

6.9.8 GENERATOR INSTALLATION<br />

The generator system shall be installed using all manufacturer's recommended installation practices. In<br />

general, observe the following considerations:<br />

• In outdoor installations all foundations shall be of proper size to support the load (check local<br />

codes <strong>for</strong> special considerations).<br />

• The generator, fuel tank(s), transfer switch/control panel <strong>and</strong> all associated components shall be<br />

securely fastened to the intended foundations.<br />

• Fuel lines shall be adequately secured, protected <strong>and</strong> free of leaks.<br />

• All parts of the system shall be installed in such a manner that it shall be easily serviceable without<br />

undue safety risk while the equipment is operational.<br />

• Installations in earthquake prone areas (Moment Magnitude rating 3 or greater) may require<br />

additional fuel, exhaust system <strong>and</strong> muffler supports. Manufacturer recommendations <strong>and</strong> local<br />

codes shall be followed in these areas.<br />

• In earthquake prone areas (Moment Magnitude rating 3 or greater), it is recommended that st<strong>and</strong>by<br />

generators be installed on vibration isolators, with flexible cables used <strong>for</strong> electrical <strong>and</strong> grounding,<br />

<strong>and</strong> flexible tubing be provided <strong>for</strong> fuel systems.<br />

6-42 68P81089E50-B 9/1/05