STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GENERATOR OUTPUT AND DERATING CONSIDERATIONS<br />

• Gasoline is a poor fuel <strong>for</strong> remote generators, with a limited storage life <strong>and</strong> highly flammable<br />

properties. Gasoline generators also have difficulty with remote starting.<br />

• Liquid fuel storage tanks shall be equipped with secondary containment capable of retaining 110%<br />

(or greater) of the maximum volume of fuel stored.<br />

• The storage tank secondary containment shall be designed such that storm water <strong>and</strong> debris cannot<br />

collect inside it.<br />

• All fuel lines or other system components that extend beyond the storage tank secondary<br />

containment area shall be designed with secondary containment.<br />

• Local Environmental Protection Agency (EPA) rules shall be adhered to following a fuel spill. All<br />

fuel spills shall be cleaned up.<br />

• Fuel storage tanks are required <strong>for</strong> all fuels except natural gas, which is provided by a utility.<br />

(However, a storage tank in conjunction with utility-provided natural gas provides additional<br />

backup in the case of gas main breakage.) Manufacturer specifications as to size <strong>and</strong> length of fuel<br />

supply lines as well as lift shall be followed.<br />

• Fuel storage tanks located outside of a structure should be protected from damage <strong>and</strong> tampering,<br />

<strong>and</strong> shall be enclosed within a fenced area. In many areas local codes require a double wall<br />

construction <strong>for</strong> the tank or a catch basin to prevent fuel from contaminating the site. Minimum<br />

recommended distance between the storage tank <strong>and</strong> fence is 1.2 m (4 ft.); minimum recommended<br />

distance between the tank <strong>and</strong> site building is 3 m (10 ft.). See NFPA 58 <strong>for</strong> additional in<strong>for</strong>mation.<br />

• Fuel storage tanks shall be secured to concrete pads using captive hardware.<br />

• LPG fuel tanks shall utilize a fuel vent pressure relief valve. The relief valve vent shall be directed<br />

away from the tank, sources of ignition, <strong>and</strong> flammable material.<br />

• Fuel lines shall be protected within the fuel storage area as well as along the route to the generator.<br />

Location <strong>and</strong> installation of the fuel tank <strong>and</strong> fuel lines shall meet all applicable environmental,<br />

building, <strong>and</strong> fire safety codes.<br />

• All generator installations shall be equipped with secondary containment capable of retaining<br />

110% of the volume of the largest tank within the containment structure, if the tanks system is a<br />

single-wall system. Alternatively, if the tank system is a double-walled system, the system shall be<br />

designed with interstitial monitoring devices that is capable of detecting a leak in the primary or<br />

secondary containment system unless tertiary containment is provided (<strong>for</strong> example, a convault or<br />

equivalent). Special tanks (double wall or fiberglass) <strong>and</strong> containment barriers are strongly<br />

recommended. Earthquake prone areas may require special fuel line considerations. Local codes<br />

<strong>and</strong> manufacturer's recommendations shall be followed.<br />

• In potential flood zones, above ground fuel tanks should be secured with a safety cable around the<br />

tank attached to an anchoring device in the soil. This helps prevent the tank from breaking loose<br />

<strong>and</strong> floating away during a flood condition.<br />

• Critical placement <strong>and</strong> orientation of the tank pressure relief valve is required. This is required, in<br />

the case of a fire, to prevent an over-pressure gas release cloud from feeding its own fire.<br />

68P81089E50-B 9/1/05 6-39