GENERATOR OUTPUT AND DERATING CONSIDERATIONS CHAPTER 6: POWER SOURCES<br />

This section describes requirements <strong>for</strong> backup/st<strong>and</strong>by generators. The purpose of a backup or st<strong>and</strong>by<br />

generator is to supply reliable power to critical loads during times when commercial power has failed. It<br />

is very important that generators used <strong>for</strong> this purpose be capable of reliably h<strong>and</strong>ling the required loads<br />

<strong>for</strong> the desired time while maintaining proper voltage <strong>and</strong> frequency. Backup/st<strong>and</strong>by generators are not<br />

required to be installed to the same <strong>st<strong>and</strong>ards</strong> as emergency generators. The <strong>st<strong>and</strong>ards</strong> included in this<br />

section do not apply to emergency generators or power systems. Emergency power systems are required<br />

to comply with NFPA 70-2005, Article 700. There<strong>for</strong>e, it is recommended to know <strong>and</strong> underst<strong>and</strong> the<br />

difference between back-up/st<strong>and</strong>by generator <strong>and</strong> emergency generator systems be<strong>for</strong>e procuring a<br />

generator equipment or installation work.<br />

NOTE: There are certain locations where commercial power is not available <strong>and</strong> generators must be used <strong>for</strong><br />

primary power. Primary power generators or generating systems shall be rated <strong>for</strong> continuous duty <strong>and</strong><br />

shall, at a minimum, be installed to the <strong>st<strong>and</strong>ards</strong> covered in this section. All domestic installations<br />

shall meet NFPA 70-2005, (National Electrical Code (NEC)), <strong>and</strong> any other local governing codes<br />

applicable to continuous duty, primary power generators. Installations per<strong>for</strong>med in non-domestic<br />

locations shall meet all applicable national <strong>and</strong> local codes. (NFPA 110)<br />

A generator system includes the generator, along with a cooling system, a fuel supply system, a transfer<br />

switch, <strong>and</strong> a control panel with required alarms. Liquid fueled generators may incorporate the fuel tank<br />

into one housing, such as a base mounted tank. The transfer switch <strong>and</strong> control panel may also be<br />

incorporated into one cabinet. The generator may be placed outside as a st<strong>and</strong>-alone piece of equipment<br />

or inside a building or structure. The location may depend on several factors that include generator size,<br />

fuel supply, noise restrictions <strong>and</strong> space availability. Local codes may additionally dictate the fuel type<br />

allowed.<br />

6.9 GENERATOR OUTPUT AND DERATING CONSIDERATIONS<br />

To ensure that the backup generator can h<strong>and</strong>le the power requirements of the equipment at the site,<br />

always consider the following factors when calculating generator output power requirements:<br />

• Voltage, phase, <strong>and</strong> load requirements of the equipment to be supplied by the generator must be<br />

obtained, including unusual loads such as UPS power supplies <strong>and</strong> switched power supplies. The<br />

customer or an electrical engineer may specify these values.<br />

• Consider site expansion. A 30% expansion factor is not unreasonable.<br />

• Consider worse-case scenarios <strong>for</strong> generator load, such as all transmitters keyed simultaneously at a<br />

trunking site.<br />

• Consider whether the generator load will be 3-phase or single-phase. Many generators are rated <strong>for</strong><br />

operation with a 3-phase load <strong>and</strong> must be derated when working with a single-phase load. If the<br />

load is single phase, be certain that the generator is capable of supporting the maximum load while<br />

connected in a single-phase configuration. When balancing the single phase loads across three<br />

phases, always account <strong>for</strong> transmitter current.<br />

• Consider physical requirements of the site. Generators may be derated based on operating altitude,<br />

type of fuel, <strong>and</strong> operating temperatures.<br />

• The generator shall not be used under conditions that could exceed the manufacturer's<br />

specifications <strong>for</strong> the particular generator equipment.<br />

6-36 68P81089E50-B 9/1/05