BATTERY SYSTEMS CHAPTER 6: POWER SOURCES<br />

6.7.4 BATTERY SIZING<br />

Battery sizing can be straight<strong>for</strong>ward or fairly complex, depending on the characteristics of the load<br />

being backed up. Stationary batteries (those used <strong>for</strong> fixed locations) are rated in Amp-Hours (AH).<br />

An 8-hour duration represents a rated amperage. The amp hour rating of stationary batteries is generally<br />

stated as the number of amps a battery can deliver <strong>for</strong> an 8-hour period. For example, 100 A <strong>for</strong> 8 hours<br />

is a 800 AH battery. If durations of other than 8 hours are desired, a correction factor must be applied.<br />

Table8-1 provides the correction factors <strong>for</strong> several durations. Note that new batteries do not deliver<br />

100% of their rating. It takes several charge/discharge cycles to bring a battery plant to full capacity.<br />

Also, as a battery continues to age its capacity gradually falls to 80% of its initial rating, at which point<br />

it is considered to be at end of life. These characteristics should be considered when choosing batteries.<br />

TABLE 6-5 BATTERY RATING CORRECTION FACTORS<br />

The DC load <strong>for</strong> most digital systems can be assumed to be steady-state, as it does not vary (even during<br />

busy times). Multiply the load by the back-up duration, <strong>and</strong> apply the correction factor, if necessary.<br />

For example, given a load of 32 amps <strong>and</strong> a back-up duration of 4 hours, multiply the load (32) by the<br />

duration in hours (4) <strong>and</strong> the correction factor of 1.157. This means that a battery with at least a 148<br />

amp hour rating will be required <strong>for</strong> this application.<br />

To calculate battery size, the power required <strong>and</strong> duration of each change must be known. Graph out the<br />

entire discharge profile. When the discharge profile is graphed, divide the discharge into blocks based<br />

on duration.<br />

6.7.5 BATTERY RATING<br />

1 Hour 2 Hours 4 Hours 6 Hours 8 Hours<br />

1.763 1.378 1.157 1.061 1.0<br />

Batteries shall be accurately sized to ensure they will maintain proper voltage <strong>for</strong> the required time<br />

duration. Use worst-case scenarios with respect to age/deterioration, lowest temperature, expected load,<br />

<strong>and</strong> the availability of alternate power generators.<br />

6.7.6 MULTIPLE BATTERY STRINGS<br />

General practice stipulates that battery types, ratings, <strong>and</strong> service life shall not be mixed among a rack.<br />

If a site is exp<strong>and</strong>ed, then all fresh, similar batteries shall be installed <strong>and</strong> the old batteries removed. A<br />

mixture of batteries results in unequal current distribution <strong>and</strong> charging, <strong>and</strong> the probability of ongoing<br />

power system problems as batteries of different ages fail.<br />

6-32 68P81089E50-B 9/1/05