STANDARDS AND GUIDELINES FOR COMMUNICATION SITES POWER QUALITY<br />

6.3.5 POWER QUALITY TESTING THRESHOLDS<br />

The table below lists the recommended thresholds when testing AC power quality in most single-phase<br />

<strong>and</strong> three-phase configurations (IEEE STD 1100-1999). The actual thresholds used should be based on<br />

the installation requirements of the connected equipment, as the connected equipment may have more<br />

stringent requirements. See IEEE STD 1159-R2001 <strong>for</strong> additional in<strong>for</strong>mation.<br />

TABLE 6-4 MINIMUM RECOMMENDED AC POWER QUALITY TESTING THRESHOLDS<br />

Category Suggested Not-to-Exceed Thresholds<br />

Frequency Deviation ± 0.5 Hz<br />

Phase Voltage Testing Thresholds<br />

High Frequency Noise Approximately 1% of the phase-neutral voltage<br />

Voltage Sags –10% of nominal supply voltage (108 V <strong>for</strong> a 120 VAC circuit)<br />

Voltage Swells +5% of nominal supply voltage (126 V <strong>for</strong> a 120 VAC circuit)<br />

Transients Approximately 100 V over the nominal phase-neutral voltage<br />

Distortion 5% Total Harmonic Distortion (THD) – the voltage distortion level at<br />

which loads may be affected<br />

High Frequency Noise 2-3 Vpeak<br />

Neutral-ground Voltage Testing Thresholds<br />

Voltage Swells 1% to 2.5% of nominal phase-neutral voltage<br />

6.3.6 STEPS TO DEVELOPING A POWER QUALITY PLAN<br />

Prior to deployment of electronic equipment, a power quality action plan should be established. To help<br />

determine necessary corrective action, the equipment's operating norms should be reviewed according<br />

to the manufacturers’ stated requirements <strong>for</strong> optimal per<strong>for</strong>mance. Next, a complete assessment of the<br />

facility's current electrical environment should be conducted <strong>and</strong> compared to the requirements <strong>for</strong> the<br />

equipment. Load requirements, grounding, bonding, isolation <strong>and</strong> protection requirements should be<br />

considered.<br />

To help maintain an optimal electrical environment, a power quality monitoring plan should be in place.<br />

The power quality monitoring plan should require regular review of the per<strong>for</strong>mance of the site's<br />

operating norms. This should include regular monitoring <strong>and</strong> recording of the site's power system, its<br />

connected loads, failures <strong>and</strong> interruptions. The objective of the power quality monitoring program is to<br />

identify problems <strong>and</strong> take corrective actions be<strong>for</strong>e incidental interference results in a wide area<br />

failure.<br />

68P81089E50-B 9/1/05 6-17