24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES POWER QUALITY<br />

6.3.3 COMMON EFFECTS OF POWER QUALITY PROBLEMS<br />

The following table summarizes the common effects of power quality problems on connected<br />

equipment:<br />

TABLE 6-2 COMMON EFFECTS OF POWER QUALITY PROBLEMS<br />

Problem Common Effect<br />

Frequency Deviation • Writing errors in any electronic writing device<br />

• Incorrect clock timing<br />

Voltage Sags (or dips) • Equipment shutdown<br />

• Power supply interruptions<br />

• CPU lock up<br />

• Data errors<br />

Voltage Swells • Microprocessor failure<br />

• Progressive damage to power supplies<br />

Transients • Damage to microprocessors<br />

• Data errors or loss<br />

• Lock ups<br />

• Catastrophic failure of electronic equipment<br />

Total Harmonic<br />

Distortion (> 5%)<br />

• Failure of microprocessor controlled equipment<br />

• Overheating of electrical system components<br />

• Decreased life expectancy of electrical system trans<strong>for</strong>mers<br />

• Circuit breakers tripping<br />

68P81089E50-B 9/1/05 6-15