AC POWER CHAPTER 6: POWER SOURCES<br />

6.2.9 HARDWIRING OF EQUIPMENT AND DEDICATED RECEPTACLES<br />

Extension cords shall not be used to power permanent <strong>communication</strong> equipment at a site.<br />

When an open equipment rack is used, hardwiring of power is not always possible. Mounting a<br />

dedicated simplex receptacle or receptacle assembly on the rack may be the most convenient method of<br />

supplying power, especially if multiple pieces of equipment are mounted on the rack. This is also a<br />

convenient way to install personal protection Type 3 SPD devices to the equipment.<br />

These receptacle assemblies can be pre-manufactured <strong>and</strong> mounted to the top face of an equipment<br />

rack. Mounting can also use a fabricated power pole mounted between racks.<br />

6.2.10 RECEPTACLES<br />

The following requirements shall be observed when specifying <strong>and</strong> installing receptacles <strong>for</strong> powering<br />

<strong>communication</strong>s equipment:<br />

• To ensure reliability, each major piece of equipment <strong>and</strong> each half of a redundant power supply<br />

shall have its own dedicated individual branch circuit <strong>and</strong> dedicated simplex receptacle.<br />

• Equipment racks may require special attention to support the dedicated simplex receptacle scheme.<br />

To comply with the dedicated simplex receptacle concept, receptacles have to be located on or very<br />

near the rack of equipment. One method is to use a specialized Multi-Receptacle AC panel with<br />

dedicated circuits that shall be mounted on the equipment rack or enclosure. (These Multi-<br />

Receptacle AC panels shall be hard wired to the breaker panel, <strong>and</strong> each simplex receptacle shall<br />

use an individual branch circuit.)<br />

• To eliminate the possibility of two pieces of equipment turning on at the same time <strong>and</strong><br />

momentarily exceeding the amperage capacity of the circuit, simplex receptacles should be used<br />

instead of duplex receptacles.<br />

NOTE: Duplex receptacles may be fed from two separate circuits only if the connecting tabs on the receptacles<br />

are removed. The neutral shall not be shared by two receptacles. In this case, only one equipment<br />

grounding conductor is required <strong>for</strong> the two circuits.<br />

• Receptacle ratings should be determined by conductor <strong>and</strong> circuit breaker current ratings. Consider<br />

future expansions.<br />

• Isolated ground receptacles should not be used unless recommended by the equipment<br />

manufacturer (IEEE STD 1100-1999). Isolated ground receptacles are not recommended <strong>for</strong> use at<br />

operator positions. See “Grounding (Earthing) <strong>for</strong> Dispatch Centers <strong>and</strong> Network Operator<br />

Positions” on page 5-62.<br />

• All 120 VAC receptacles shall have three conductors: phase, neutral, <strong>and</strong> ground (IEEE STD 1100-<br />

1999).<br />

• Power cord plugs shall be supported with strain reliefs adequate to prevent accidental<br />

disconnection where applicable. Twist-lock plugs shall not be used in lieu of strain relief.<br />

• All <strong>communication</strong>s equipment receptacles shall have the electrical box or cover plate permanently<br />

marked with the service panel <strong>and</strong> appropriate circuit identification. This identification shall be<br />

readily visible without requiring removal of the plug.<br />

6-10 68P81089E50-B 9/1/05