24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES AC POWER<br />

• The site electric meter shall be located where it is visible <strong>and</strong> accessible to power company meter<br />

readers <strong>and</strong> shall comply with all applicable codes <strong>and</strong>/or power company requirements.<br />

• Meter access by power company personnel should be considered when determining meter location<br />

(especially where a fence is involved). (See NFPA 70-2005, Article 100 <strong>and</strong> Article 230 <strong>for</strong> details<br />

regarding locations <strong>and</strong> service conductors.)<br />

NOTE: The following refers to the Main Disconnect <strong>for</strong> the separately derived system feeding the equipment<br />

room. The Main Disconnect may not be located in the same building as the equipment (a meter farm at<br />

a tower site, <strong>for</strong> example). This makes the panel in the building with the equipment a sub-panel <strong>and</strong> not<br />

the main disconnect.<br />

• At all <strong>sites</strong>, there is either or both a main service disconnect <strong>and</strong> a fused disconnect. A main service<br />

disconnect may be located at a meter location away from the building. A main disconnect located<br />

within the shelter, equipment room or area may be fed by a feeder circuit originating at a main<br />

service disconnect located in an electrical room in a different location in the building or even a<br />

separate building. Typically, the neutral <strong>and</strong> ground conductors are bonded in the main service<br />

disconnect. When the main service disconnect is located remotely from the equipment room or<br />

area, a separately derived system should be installed in the equipment room. (See NFPA 70-2005,<br />

Article 250.30 <strong>and</strong> 250.32 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

One of the reasons <strong>for</strong> the separately derived system is to reestablish the neutral/ground bond,<br />

thereby improving the effectiveness of normal mode suppression.<br />

NOTE: See Table 7-1 on page 7-7 <strong>and</strong> associated Chapter 7 figures <strong>for</strong> additional in<strong>for</strong>mation regarding<br />

connections <strong>for</strong> separately derived systems.<br />

• A fused disconnect shall always be installed be<strong>for</strong>e all other panels <strong>and</strong> equipment, including a<br />

generator transfer switch. (See NFPA 70-2005, Article 445.18 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

• For a st<strong>and</strong>-alone equipment shelter, the main disconnect shall be located on the same wall as the<br />

coaxial cable entry port, the telephone entry point, <strong>and</strong> the MGB. If it is not possible to locate these<br />

components on the same wall, then these components shall be located on an adjacent wall as close<br />

together as possible. (See IEEE 1100-1999 Section 8.3.2.1.2 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

• The main bonding jumper shall be installed between the neutral bus <strong>and</strong> the ground bus within the<br />

main service disconnect. This is to ensure an effective low-impedance neutral-to-ground bond<br />

connection. (See NFPA 70-2005, Article 250.24(B) <strong>for</strong> additional in<strong>for</strong>mation.)<br />

• Self-tapping or sheet metal type screws shall not be used <strong>for</strong> attaching ground or grounding<br />

conductors to any surface. (See NFPA 70-2005, Article 250.8 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

• Paint, enamel, lacquer, or other nonconductive coatings shall be removed from threads <strong>and</strong> surface<br />

areas where connections are made. (See NFPA 70-2005, Article 250.12 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

68P81089E50-B 9/1/05 6-3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!