standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
GROUNDING (EARTHING) FOR INTEGRATED COMMUNICATION SITES CHAPTER 5: INTERNAL GROUNDING (EARTHING) AC Service To Tower or Antenna Mast MGB To Communication Equipment Connection from antenna is made below the MGB Down conductor Water pipe Water pipe effectively grounded NOTES: 1. 35 mm2 csa (#2 AWG) conductor for runs of 10 m (33 ft.) or less. 2. 95 mm2 csa (#3/0 AWG) conductor for runs longer than 26 m (84 ft.) 3. See Table 5-3 on page 5-27 for other cable lengths and conductor sizing requirements. FIGURE 5-42 SITE ON DIFFERENT FLOOR THAN AC SERVICE FEED, BUILDING STEEL NOT AVAILABLE AC Service To Tower or Antenna Mast MGB M To Communication Equipment Connection from antenna is made below the MGB Building Steel Water pipe Building steel effectively grounded Water pipe effectively grounded NOTES: 1. 35 mm2 csa (#2 AWG) conductor for runs of 10 m (33 ft.) or less 2. 95 mm2 csa (#3/0 AWG) conductor for runs longer than 26 m (84 ft.) 3. See Table 5-3 on page 5-27 for other cable lengths and conductor sizing requirements. FIGURE 5-43 SITE ON DIFFERENT FLOOR THAN AC SERVICE FEED, BUILDING STEEL AVAILABLE 5-70 68P81089E50-B 9/1/05
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) FOR INTEGRATED COMMUNICATION SITES Communication Site Building Communication Site Building FIGURE 5-44 GROUNDING ROOFTOP INSTALLATIONS Antenna mounting structures and rooftop mounted tower shall follow grounding specifications with Chapter 4, paragraphs 4.8 on page 4-74 and 4.9 on page 4-79. Antenna Structure Ground Conductors 35 mm 2 csa (#2 AWG) or coarser down conductor for runs 10 m (33 ft.) or less. 95 mm 2 csa (#3/0 AWG) or coarser down conductor for runs greater than 26 m (84 ft.) Main AC service feed into building shall be bonded at entrance. Minimum 3 grounding rods in basement or garden if available Antenna Structure Ground Conductors 35 mm 2 csa (#2 AWG) or coarser down conductor for runs 10 m (33 ft.) or less. 95 mm 2 csa (#3/0 AWG) or coarser down conductor for runs greater than 26 m (84 ft.) Structural Steel See Table 5-3 on page 5-27 for other cable lengths and conductor sizing requirements. 68P81089E50-B 9/1/05 5-71
- Page 213 and 214: STANDARDS AND GUIDELINES FOR COMMUN
- Page 215 and 216: STANDARDS AND GUIDELINES FOR COMMUN
- Page 217 and 218: STANDARDS AND GUIDELINES FOR COMMUN
- Page 219 and 220: STANDARDS AND GUIDELINES FOR COMMUN
- Page 221 and 222: STANDARDS AND GUIDELINES FOR COMMUN
- Page 223 and 224: STANDARDS AND GUIDELINES FOR COMMUN
- Page 225 and 226: STANDARDS AND GUIDELINES FOR COMMUN
- Page 227 and 228: STANDARDS AND GUIDELINES FOR COMMUN
- Page 229 and 230: STANDARDS AND GUIDELINES FOR COMMUN
- Page 231 and 232: STANDARDS AND GUIDELINES FOR COMMUN
- Page 233 and 234: STANDARDS AND GUIDELINES FOR COMMUN
- Page 235 and 236: STANDARDS AND GUIDELINES FOR COMMUN
- Page 237 and 238: STANDARDS AND GUIDELINES FOR COMMUN
- Page 239 and 240: STANDARDS AND GUIDELINES FOR COMMUN
- Page 241 and 242: STANDARDS AND GUIDELINES FOR COMMUN
- Page 243 and 244: STANDARDS AND GUIDELINES FOR COMMUN
- Page 245 and 246: STANDARDS AND GUIDELINES FOR COMMUN
- Page 247 and 248: STANDARDS AND GUIDELINES FOR COMMUN
- Page 249 and 250: STANDARDS AND GUIDELINES FOR COMMUN
- Page 251 and 252: STANDARDS AND GUIDELINES FOR COMMUN
- Page 253 and 254: STANDARDS AND GUIDELINES FOR COMMUN
- Page 255 and 256: STANDARDS AND GUIDELINES FOR COMMUN
- Page 257 and 258: STANDARDS AND GUIDELINES FOR COMMUN
- Page 259 and 260: STANDARDS AND GUIDELINES FOR COMMUN
- Page 261 and 262: STANDARDS AND GUIDELINES FOR COMMUN
- Page 263: STANDARDS AND GUIDELINES FOR COMMUN
- Page 267 and 268: CHAPTER 6 POWER SOURCES 6 6.1 LOCKO
- Page 269 and 270: STANDARDS AND GUIDELINES FOR COMMUN
- Page 271 and 272: STANDARDS AND GUIDELINES FOR COMMUN
- Page 273 and 274: STANDARDS AND GUIDELINES FOR COMMUN
- Page 275 and 276: STANDARDS AND GUIDELINES FOR COMMUN
- Page 277 and 278: STANDARDS AND GUIDELINES FOR COMMUN
- Page 279 and 280: STANDARDS AND GUIDELINES FOR COMMUN
- Page 281 and 282: STANDARDS AND GUIDELINES FOR COMMUN
- Page 283 and 284: STANDARDS AND GUIDELINES FOR COMMUN
- Page 285 and 286: STANDARDS AND GUIDELINES FOR COMMUN
- Page 287 and 288: STANDARDS AND GUIDELINES FOR COMMUN
- Page 289 and 290: STANDARDS AND GUIDELINES FOR COMMUN
- Page 291 and 292: STANDARDS AND GUIDELINES FOR COMMUN
- Page 293 and 294: STANDARDS AND GUIDELINES FOR COMMUN
- Page 295 and 296: STANDARDS AND GUIDELINES FOR COMMUN
- Page 297 and 298: STANDARDS AND GUIDELINES FOR COMMUN
- Page 299 and 300: STANDARDS AND GUIDELINES FOR COMMUN
- Page 301 and 302: STANDARDS AND GUIDELINES FOR COMMUN
- Page 303 and 304: STANDARDS AND GUIDELINES FOR COMMUN
- Page 305 and 306: STANDARDS AND GUIDELINES FOR COMMUN
- Page 307 and 308: STANDARDS AND GUIDELINES FOR COMMUN
- Page 309 and 310: STANDARDS AND GUIDELINES FOR COMMUN
- Page 311 and 312: CHAPTER 7 SURGE PROTECTIVE DEVICES
- Page 313 and 314: STANDARDS AND GUIDELINES FOR COMMUN
GROUNDING (EARTHING) FOR INTEGRATED COMMUNICATION SITES CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />
AC<br />
Service<br />
To Tower or Antenna Mast<br />
MGB<br />
To Communication Equipment<br />
Connection from antenna<br />
is made below the MGB<br />
Down conductor<br />
Water pipe<br />
Water pipe<br />
effectively grounded<br />
NOTES:<br />
1. 35 mm2 csa (#2 AWG) conductor<br />
<strong>for</strong> runs of 10 m (33 ft.) or less.<br />
2. 95 mm2 csa (#3/0 AWG)<br />
conductor <strong>for</strong> runs longer than<br />
26 m (84 ft.)<br />
3. See Table 5-3 on page 5-27 <strong>for</strong><br />
other cable lengths <strong>and</strong><br />
conductor sizing requirements.<br />
FIGURE 5-42 SITE ON DIFFERENT FLOOR THAN AC SERVICE FEED, BUILDING STEEL NOT<br />
AVAILABLE<br />
AC<br />
Service<br />
To Tower or Antenna Mast<br />
MGB M<br />
To Communication Equipment<br />
Connection from antenna<br />
is made below the MGB<br />
Building Steel<br />
Water pipe<br />
Building steel<br />
effectively grounded<br />
Water pipe<br />
effectively grounded<br />
NOTES:<br />
1. 35 mm2 csa (#2 AWG) conductor<br />
<strong>for</strong> runs of 10 m (33 ft.) or less<br />
2. 95 mm2 csa (#3/0 AWG)<br />
conductor <strong>for</strong> runs longer than<br />
26 m (84 ft.)<br />
3. See Table 5-3 on page 5-27 <strong>for</strong><br />
other cable lengths <strong>and</strong><br />
conductor sizing requirements.<br />
FIGURE 5-43 SITE ON DIFFERENT FLOOR THAN AC SERVICE FEED, BUILDING STEEL AVAILABLE<br />
5-70 68P81089E50-B 9/1/05