GROUNDING (EARTHING) FOR DISPATCH CENTERS AND NETWORK OPERATOR POSITIONS CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

At the location where tele<strong>communication</strong>s cabling enters the building, the metallic shields shall be<br />

bonded to the building's grounding system by one of the methods described in paragraph 5.5.1.8.4<br />

beginning on page 5-51. Where internal backbone tele<strong>communication</strong> cables (telephone system cables)<br />

incorporate a shield or metallic member, the shield or metallic member shall be effectively bonded to<br />

the closest MGB or main SSGB with a 16 mm 2 csa (#6 AWG) or coarser green jacketed grounding<br />

conductor at the point where cables terminate or where they are broken out. Primary SPDs <strong>for</strong> interbuilding<br />

<strong>communication</strong> cables shall be bonded to the MGB or SSGB with a 16 mm 2 csa (#6 AWG) or<br />

coarser, green jacketed grounding conductor as described in paragraph 5.5.1.8.2 on page 5-50. When<br />

secondary SPDs are installed at the equipment location, the SPD grounding conductor shall be<br />

effectively bonded to the closest MGB or SSGB as described in paragraph 5.5.1.8.3 on page 5-51.<br />

Where external antenna cables enter the building, that point of entry shall be treated as a cable entrance<br />

location (ANSI-J-STD-607-A-2002). The cable entrance location shall have an accessible bonding<br />

location to the building's common grounding electrode system (e.g., an external ground bus bar or<br />

structural building steel). The outer metallic shields of each transmission line <strong>and</strong> other <strong>communication</strong>s<br />

cables shall be bonded to the building's common grounding electrode system (NFPA 70-2005, Articles<br />

770.93, 800.100, 810.20, 820.93, 820.100, <strong>and</strong> 830.100). See “External Ground Bus Bar” on page 4-30<br />

<strong>for</strong> additional in<strong>for</strong>mation.<br />

5.8 GROUNDING (EARTHING) FOR DISPATCH CENTERS AND<br />

NETWORK OPERATOR POSITIONS<br />

Dispatch centers co-located with <strong>communication</strong> towers require special protection considerations due to<br />

the critical nature of their operation <strong>and</strong> due to the inherent risk to personnel from lightning events. For<br />

optimum protection of a dispatch center, the following shall be considered:<br />

• Site design recommendations given in “Design Considerations to Help Reduce Effects of<br />

Lightning” on page 2-19.<br />

• External grounding (earthing) <strong>and</strong> bonding as defined in Chapter 4, “External Grounding<br />

(Earthing).”<br />

• Transient voltage surge suppression (TVSS) as defined in “Telephone/Control/Data Network<br />

Circuit SPDs” on page 7-34.<br />

• Electrostatic discharge (ESD) precautions as defined in Appendix C.<br />

This section provides electrical protection measures that are intended to help protect network operators,<br />

<strong>and</strong> to help ensure reliable equipment operation during periods of lightning activity or surges from AC<br />

power lines <strong>and</strong> power switching operations.<br />

5-62 68P81089E50-B 9/1/05