24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

BONDING EQUIPMENT TO INTERNAL GROUNDING (EARTHING) SYSTEM CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

Utility<br />

Panelboard<br />

Generator<br />

Automatic<br />

Transfer Switch<br />

Tele<strong>communication</strong>s<br />

cable entry port<br />

Transmission<br />

Line entry port<br />

MGB Grounding<br />

Electrode<br />

Conductor<br />

UPS<br />

Panelboard<br />

Where a RF transmission line SPD is placed at the equipment shelter, equipment room or equipment<br />

area entry point <strong>and</strong> that entry point is greater than 6.1 linear metres (20 linear feet) away from the<br />

MGB's grounding electrode conductor connection to the grounding electrode system, a grounding<br />

electrode conductor shall properly installed between the SPD <strong>and</strong> the nearest accessible location of the<br />

common grounding electrode system as covered under NFPA 70-2005, Articles 810.21 <strong>and</strong> 820.100.<br />

The SPD shall also be effectively bonded back to the MGB by way of its SSGB or a ground bus<br />

conductor.<br />

UPS<br />

Electrical Service<br />

Main Disconnect<br />

Electrical Service<br />

ground<br />

Required #2 AWG Grounding Conductor<br />

<strong>for</strong> bonding Primary SPD to the MGB.<br />

MGB<br />

IPGB System<br />

Primary SPD <strong>for</strong><br />

Tele<strong>communication</strong><br />

cable entry port<br />

Shelter External Ground Ring Conductor<br />

FIGURE 5-32 CABLE ENTRY GREATER THAN 6.1 LINEAR METRES (20 LINEAR FEET) FROM MGB<br />

GROUNDING ELECTRODE SYSTEM.<br />

5.5.1.8.2 PRIMARY SURGE PROTECTION DEVICES<br />

#2 AWG grounding electrode conductor<br />

Required because telecom cable entry port<br />

is located more than 20 linear ft from<br />

MGB grounding electrode conductor<br />

SSGB <strong>for</strong><br />

RF SPDs<br />

Alternate Transmission Line entry port<br />

Note: This configuration is to be avoided whenever possible.<br />

Primary SPDs <strong>for</strong> telephone circuits, data circuits, <strong>and</strong> control circuits shall have the ground (earth)<br />

terminal bonded to the MGB, SSGB or a dedicated ground bus conductor with an equipment grounding<br />

conductor using bonding methods described within this chapter. The grounding conductor <strong>for</strong> a single<br />

line primary SPD shall be 6 mm 2 csa (# 10 AWG) or coarser; the grounding conductor <strong>for</strong> multiple line<br />

primary SPDs shall be 16 mm 2 csa (# 6 AWG) or coarser. Where a primary SPD is placed at an entry<br />

point other than adjacent to the MGB <strong>and</strong> that point is greater than 6.1 linear metres (20 linear feet)<br />

away from the MGB's grounding electrode, a grounding electrode conductor shall properly installed<br />

between the primary SPD grounding terminal or its SSGB to the nearest accessible location on the<br />

common grounding electrode system as covered under NFPA 70-2005, Articles 800.100, 830.100. See<br />

Figure 5-32 <strong>for</strong> an example of this type of grounding configuration. In both cases, the conductors should<br />

maintain a minimum 305 mm (1 ft.) separation between cables of different cable groups, even when<br />

conductor is placed in rigid metallic conduit (ANSI-J-STD-607-A-2002).<br />

5-50 68P81089E50-B 9/1/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!