BONDING EQUIPMENT TO INTERNAL GROUNDING (EARTHING) SYSTEM CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

• The SSGB bonding conductor shall be connected to the <strong>communication</strong> bonding backbone<br />

conductor or to the grounding equalizer conductor with an exothermic welding or listed irreversible<br />

compression-type connection (ANSI-J-STD-607-A-2002)<br />

• When a grounding equalizer conductor is installed as described within this chapter, it shall be<br />

bonded back to the SSGBs <strong>and</strong> not to the <strong>communication</strong> bonding backbone conductors.<br />

• The grounding equalizer conductor shall be connected to the SSGBs with exothermic welding,<br />

listed compression-type two-hole lugs, or listed irreversible compression type connections.<br />

• Only the far end of a <strong>communication</strong> bonding backbone conductor may be connected directly to the<br />

SSGB. If the <strong>communication</strong> bonding conductor is connected directly to the SSGB, it shall be<br />

connected with exothermic welding or irreversible compression type connection. See Figure 5-4 on<br />

page 5-7 <strong>for</strong> an example of this type of grounding system configuration.<br />

5.5 BONDING EQUIPMENT TO INTERNAL GROUNDING<br />

(EARTHING) SYSTEM<br />

All equipment <strong>and</strong> ancillary support apparatus shall be bonded to the MGB, SSGB, RGB, ground<br />

(earth) bus conductor or internal perimeter ground bus (IPGB) conductor with an equipment grounding<br />

conductor as described within this chapter.<br />

TABLE 5-6 BONDING TO THE INTERNAL GROUNDING SYSTEM FROM ITEM TOWARD EARTH<br />

From To<br />

Item MGB SSGB RGB<br />

Ground<br />

Bus<br />

Conductor IPGB<br />

Minimum Conductor Size Unless<br />

Otherwise Specified<br />

35 mm 2 csa<br />

(#2 AWG)<br />

SSGB ✔ ✔ ✔ ✔<br />

RGB ✔ ✔ ✔ ✔ ✔<br />

Equipment ground<br />

bus extension<br />

✔ ✔ ✔ ✔ ✔<br />

16 mm 2 csa<br />

(#6 AWG)<br />

Equipment cabinet ✔ ✔ ✔ ✔ ✔<br />

Equipment rack ✔ ✔ ✔ ✔<br />

Equipment<br />

grounding conductor<br />

Individual system<br />

component chassis<br />

Control or Dispatch<br />

Centers electronic<br />

equipment <strong>and</strong><br />

metallic parts of<br />

furniture<br />

✔ ✔ ✔ ✔ ✔<br />

✔ ✔ ✔ ✔ ✔<br />

✔ ✔ ✔ ✔ ✔<br />

5-40 68P81089E50-B 9/1/05