CONNECTION METHODS FOR INTERNAL GROUNDING (EARTHING) SYSTEM CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

• An appropriate type of listed, conductive anti-oxidant shall be applied on all connections of<br />

dissimilar metals. Copper enhanced anti-oxidant compound should be used between copper, brass,<br />

bronze <strong>and</strong> tin-plated bonding surfaces. Zinc enhanced anti-oxidant compound should be used<br />

between tin-plated connection devices <strong>and</strong> steel, galvanized steel, zinc-chromate steel, aluminum,<br />

<strong>and</strong> tin-plated copper bus bar bonding surfaces.<br />

• Where threaded or tapped holes are provided <strong>for</strong> attachment purposes, a star or split type lock<br />

washer shall be installed under the head of the screw or bolt <strong>and</strong>/ or between the nut <strong>and</strong> the ground<br />

bus bar. See Figure 5-19 on page 5-32 <strong>for</strong> the correct location of the star or split washer in these<br />

instances.<br />

• Self-tapping or sheet metal type screws shall not be used <strong>for</strong> attaching ground or grounding<br />

conductors to any surface. (See NFPA 70-2005, Article 250.8 <strong>for</strong> additional in<strong>for</strong>mation.)<br />

• Paint, enamel, lacquer, or other nonconductive coatings shall be removed from threads <strong>and</strong> surface<br />

areas where connections are made (NFPA 70-2005, Article 250.12). Use of a star washer shall not<br />

alleviate the requirement to remove nonconductive coatings from attachment surfaces. Star or split<br />

type washers shall not be installed between the conductive surfaces. Proper placement of<br />

lockwasher is shown in Figure 5-19.<br />

NOTE: Do not install a washer of any kind between the ground lug <strong>and</strong> the bonding surface.<br />

METALLIC BONDING<br />

SURFACE<br />

GROUND LUG<br />

REMOVE PAINT (IF PRESENT)<br />

AND APPLY ANTIOXIDANT<br />

COMPOUND<br />

LOCKWASHER<br />

FIGURE 5-19 PROPER LOCATION OF WASHER WHEN CONNECTING GROUND LUG<br />

• All two-hole lugs shall have bolts in both holes with lock washers placed on the nut side of the<br />

bonding surface.<br />

• All securing hardware <strong>for</strong> mechanically bolted clamps <strong>and</strong> lugs shall be stainless steel or approved<br />

<strong>for</strong> the application.<br />

The following methods of connection are unacceptable <strong>and</strong> shall not be used:<br />

• Insulation piercing connectors.<br />

• Self-tapping or sheet metal type screws shall not be used to provide continuous <strong>and</strong> permanent<br />

electrical bonds (NFPA 70-2005, Article 250.8 <strong>and</strong> FAA-STD-019d-2002).<br />

• Tinnerman or similar type clips (FAA-STD-019d-2002).<br />

• Aluminum connection devices.<br />

5-32 68P81089E50-B 9/1/05