24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

Depending on the building construction, building size, <strong>communication</strong> system requirements, <strong>and</strong> the<br />

tele<strong>communication</strong> cable pathways, one or more <strong>communication</strong> bonding backbone conductors may be<br />

installed. Each <strong>communication</strong> bonding backbone conductor shall be consistent with the design of the<br />

<strong>communication</strong> bonding backbone cabling system, <strong>and</strong> it shall be installed so that it is protected from<br />

physical damage.<br />

Typically when the equipment rooms or areas are located on different floors of a large multi-story<br />

building, a separate <strong>communication</strong> bonding backbone conductor is routed up each of the opposite sides<br />

of the building. To equalize potential, the <strong>communication</strong> bonding backbone conductors are bonded<br />

together with a grounding equalizer conductor at the top floor <strong>and</strong> at a minimum of every third floor in<br />

between using methods described within this chapter (ANSI-J-STD-607-A-2002).<br />

5.3.6.2 SPECIFICATIONS<br />

All <strong>communication</strong> bonding backbone conductors <strong>and</strong> grounding (earthing) equalizer conductors shall<br />

be established of 35 mm 2 csa (#2 AWG) or coarser, solid or str<strong>and</strong>ed copper conductor. When the<br />

conductors are jacketed, they shall be listed <strong>for</strong> the space in which they are intended to be placed <strong>and</strong><br />

the jacket shall be green or properly marked with a distinctive green color (ANSI-J-STD-607-A-2002).<br />

In the buildings that do not have effectively bonded structural steel, additional conductor sizing should<br />

be considered. All <strong>communication</strong> bonding backbone conductors <strong>and</strong> grounding equalizer conductors<br />

shall be of the same size. The linear length of a 35 mm 2 csa (#2 AWG) <strong>communication</strong> bonding<br />

backbone conductor or a grounding equalizer conductor should not exceed 10 m (33 ft.). If a greater<br />

conductor length is required, these conductors should be sized at 2 kcmil per linear foot of conductor<br />

length up to a maximum size of 95 mm 2 csa (#3/0 AWG). See Table 5-3 <strong>and</strong> Table 5-4 on page 5-27 <strong>for</strong><br />

conductor sizing requirements (ANSI-J-STD-607-A-2002; MIL-HDBK-419A).<br />

All <strong>communication</strong> bonding backbone conductors <strong>and</strong> grounding equalizer conductors should be<br />

installed without splices. When splices are necessary, the number of splices shall be kept to a minimum<br />

<strong>and</strong> the splices shall be accessible <strong>and</strong> located in tele<strong>communication</strong> spaces<br />

(ANSI-J-STD-607-A-2002). All <strong>communication</strong> bonding backbone <strong>and</strong> grounding equalizer conductor<br />

splices shall be established using suitable methods described within the chapter.<br />

NOTE: The interior water piping system of the building <strong>and</strong> metallic cable shields shall not be used as<br />

<strong>communication</strong> bonding backbone conductors or grounding equalizer conductors<br />

(ANSI-J-STD-607-A-2002).<br />

Each equipment area's main SSGB shall be bonded to the <strong>communication</strong> bonding backbone conductor<br />

or to the grounding equalizer conductor with a grounding conductor of the same size as the<br />

<strong>communication</strong> bonding backbone conductor using suitable methods described within this chapter. The<br />

building's MGB shall be bonded to the service equipment (power) grounding electrode system using a<br />

grounding conductor of the same size as the <strong>communication</strong> bonding backbone conductor by using<br />

suitable methods described within this chapter (ANSI-J-STD-607-A-2002).<br />

5-26 68P81089E50-B 9/1/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!