GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />

5.3.5 GROUND (EARTH) BUS CONDUCTORS<br />

GROUND BUS<br />

CONDUCTORS -<br />

ALL CONDUCTORS<br />

ROUTED TO MGB<br />

INDIVIDUAL EQUIPMENT<br />

GROUNDING<br />

CONDUCTORS FROM<br />

EACH PIECE OF<br />

EQUIPMENT AND RACK<br />

TO THE GROUND BUS<br />

CONDUCTOR<br />

RGB MOUNTED ON<br />

RACK CABLE<br />

MANAGEMENT<br />

SYSTEM<br />

GROUND BUS<br />

CONDUCTOR EXTENDED<br />

TO BOTTOM OF RACK<br />

TO ACCOMMODATE<br />

FUTURE GROWTH<br />

Ground (earth) bus conductors interconnect the MGB, SSGB, RGB <strong>and</strong> the equipment grounding<br />

conductor with the cabinets, racks or individual system or subsystem components. The end of the<br />

conductor opposite the MGB or SSGB typically remains unterminated, although this end of the<br />

conductor may be terminated to a cabinet, rack, individual system component or RGB.<br />

Ground bus conductors typically originate at the MGB <strong>and</strong> radiate throughout the equipment area<br />

generally within the cable tray system. These conductors may extend into an adjoining subsystem<br />

equipment area <strong>and</strong> may serve as the grounding conductor <strong>for</strong> a SSGB, or RGB. Ground bus conductors<br />

shall be bonded to the MGB, SSGB, or RGB using methods described within this chapter.<br />

Ground bus conductors may have ground bus extension conductors to provide a ground bus within cross<br />

section segments of a cable tray system. These ground bus extension conductors shall be of the same<br />

specification as the ground bus conductor <strong>and</strong> shall be routed with all connections to the ground bus<br />

conductor pointed in the direction of the MGB or SSGB. The ground bus extension conductor shall be<br />

bonded to the ground bus conductor using suitable methods described within this chapter.<br />

Equipment grounding conductors from each cabinet, rack or individual system component chassis shall<br />

be bonded to the ground bus conductor or ground bus extension conductor using methods described<br />

within this chapter. See Figure 5-17. Ground bus conductors are not required to be installed at all<br />

locations, provided that equipment grounding conductors from each cabinet, rack <strong>and</strong> individual system<br />

component extend to the MGB or SSGB.<br />

TOP-MOUNTED RGB<br />

EQUIPMENT<br />

GROUNDING<br />

CONDUCTORS<br />

EQUIPMENT<br />

GROUNDING<br />

TERMINAL<br />

(TYPICAL EACH<br />

PIECE OF<br />

EQUIPMENT)<br />

VERTICALLY<br />

MOUNTED RGB<br />

MINIMUM BENDING<br />

RADIUS MUST BE<br />

MAINTAINED ON ALL<br />

CONDUCTORS<br />

FIGURE 5-17 ACCEPTABLE METHODS FOR BONDING FROM THE EQUIPMENT TO THE MGB<br />

5-24 68P81089E50-B 9/1/05