24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS<br />

NOTE: Conductors installed within a plenum shall be compliant with NFPA 70-2005, Article 300.22 <strong>and</strong> cables<br />

installed within In<strong>for</strong>mation Technology rooms shall be compliant with NFPA 70-2005, Article 645.<br />

Ground conductors shall have an approved covering (insulation) or may be bare. When bare conductors<br />

are used they shall be solidly supported on suitable st<strong>and</strong>off insulators at intervals of no more than<br />

610 mm (24 in.). These conductors shall not be in contact with metallic surfaces or other conductors<br />

unless intended to be bonded to these surfaces or conductors. These conductors shall be covered or<br />

jacketed upon exit from the plenum area <strong>and</strong> may be spliced at this point using an approved splicing<br />

method described within this chapter.<br />

All grounding conductors shall be installed <strong>and</strong> routed so that personal safety is not compromised <strong>and</strong><br />

that all equipment is serviceable. The following requirements shall apply:<br />

• Length: conductors shall be no longer than required to achieve their purpose <strong>and</strong> shall be installed<br />

<strong>and</strong> routed in a professional <strong>and</strong> workmanlike manner.<br />

• Support: conductors shall be secured or attached to surfaces as required to ensure they do not<br />

become damaged or disconnected. Conductors shall be secured in a manner that permits associated<br />

equipment to be easily serviced. Conductors shall be secured at no greater than 914 mm (3 ft.)<br />

intervals.<br />

• Protection: conductors installed in areas where they may be subjected to damage shall be sleeved<br />

in electrical non-metallic tubing, or other conduit, that is securely attached to the surface over<br />

which it is routed.<br />

• In locations where metallic tubing or conduit is required <strong>for</strong> adequate protection, the<br />

conductor(s) routed through the metallic tubing or conduct must be effectively bonded to each<br />

end of the conduit using suitable listed means <strong>and</strong> devices (NFPA 70-2005, Articles 250.92<br />

(A)(3) <strong>and</strong> 250.64(E)).<br />

• When ground conductor tap joints are used, they shall be properly insulated as to prevent the<br />

bare conductor or connection device from making incidental contact with metallic surfaces.<br />

• Routing:<br />

• At points where conductors are routed through holes within metallic surfaces, the surfaces<br />

shall be suitably protected with grommets or other material to minimize damage to the<br />

conductor or insulation.<br />

• Conductors shall be routed toward the MGB, SSGB, or RGB. Connections to bus conductors<br />

shall always be made with the tap conductors routed toward the MGB, SSGB, or RGB. See<br />

Figure 5-1 on page 5-4 <strong>and</strong> Figure 5-17 on page 5-24.<br />

• At points where conductors must pass through a hole in a metallic surface <strong>and</strong> the hole is<br />

slightly larger than the conductor, the conductor shall be bonded to the metallic surface<br />

through which it passes. If the hole or opening is much larger than the conductor <strong>and</strong> is<br />

intended to accommodate several conductors, the conductor is not required to be bonded. See<br />

Figure 5-14 on page 5-22.<br />

• Ground bus conductors may be routed within cable trays, on the outside of cable trays where<br />

suitable support is provided, or along equipment plat<strong>for</strong>ms. See Figure 5-15 <strong>and</strong> Figure 5-16<br />

on page 5-23.<br />

• Equipment grounding conductors shall be installed along the rack rail or other suitable support<br />

medium leading to the cable tray system or ground bus conductor.<br />

68P81089E50-B 9/1/05 5-21

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!