24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS<br />

• The SSGB grounding conductor shall be bonded to the MGB, a collocated SSGB, or to a<br />

<strong>communication</strong> bonding backbone conductor as described within this chapter.<br />

• When its required that the SSGB be bonded back to the external grounding electrode system, it is<br />

strongly recommended that the SSGB grounding electrode conductor be multi-str<strong>and</strong>ed, bare,<br />

individually tinned, copper.<br />

• The SSGB grounding electrode conductor shall be bonded back to the external grounding electrode<br />

system with an exothermic weld or a listed irreversible compression device (ANSI T1.334-2002).<br />

• SSGB grounding electrode conductors located in areas with the potential <strong>for</strong> physical damage shall<br />

be protected <strong>and</strong> the conductor or its enclosure shall be securely fastened to the surface on which it<br />

is carried (NFPA 70-2005, Article 250.64(B)).<br />

• The SSGB grounding electrode conductor shall be run to the grounding electrode system in a direct<br />

manner with no sharp bends or narrow loops. The grounding conductor bend angles (included<br />

angle) shall not be less than 90 degrees nor have a bending radius of less than 203 mm (8 in.)<br />

(ANSI T1.313-2003). See Figure 5-13.<br />

Radius<br />

The radius of any bend shall not<br />

be less than 203 mm (8 in.)<br />

90 degrees<br />

minimum<br />

The angle of any bend shall not<br />

be less than 90 degrees.<br />

FIGURE 5-13 ACCEPTABLE GROUND CONDUCTOR BENDING<br />

• When routing the SSGB grounding conductor through a perimeter wall to the external grounding<br />

electrode system, the grounding conductor should be routed through the wall in a PVC or flexible<br />

non-metallic conduit sleeve at a 45 degree angle towards the grounding electrode system.<br />

• The SSGB grounding conductor should not be placed in ferrous metallic conduit. If local building<br />

codes require metallic conduit or sleeves, the grounding electrode conductor shall be bonded to<br />

each end of the conduit using a listed grounding bushing or a bonding jumper of the same size, or<br />

coarser than, the required enclosed grounding electrode conductor (ANSI-J-STD-607-A-2002,<br />

ANSI T1.334-2002, ANSI T1.313-2003 <strong>and</strong> NFPA 70-2005, Article 250.64(E)).<br />

• Unless both ends of the grounding conductor are clearly visible, the conductor shall be clearly<br />

labeled on both ends (ANSI T1.333-2001). In large <strong>and</strong> multi-story commercial buildings, each<br />

<strong>communication</strong> grounding <strong>and</strong> bonding conductor should be labeled as close as practicable to its<br />

point of termination in a readable location. The label shall be nonmetallic <strong>and</strong> should include the<br />

in<strong>for</strong>mation shown below (ANSI-J-STD-607-A-2002).<br />

IF THIS CONNECTOR OR CABLE IS LOOSE OR MUST BE<br />

REMOVED, PLEASE CALL THE BUILDING<br />

TELECOMMUNICATIONS MANAGER<br />

68P81089E50-B 9/1/05 5-19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!