STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS<br />

5.3.2.1 SSGB SPECIFICATIONS<br />

TABLE 5-2 SSGB Specifications<br />

The SSGB shall be a copper bus bar with predrilled holes that provide <strong>for</strong> the use of st<strong>and</strong>ard sized lugs.<br />

It is recommended that the bus bar be electrotin plated <strong>for</strong> reduced contact resistance. The SSGB shall<br />

be sized in accordance with the immediate application <strong>and</strong> consideration should be given to future<br />

growth of the site. The SSGB shall be listed by a nationally recognized testing laboratory when it is<br />

placed within a building facility (ANSI-J-STD-607-A-2002) <strong>and</strong> it should be listed when placed within<br />

other type equipment locations. See Figure 5-12 <strong>for</strong> a typical layout of conductor mounting holes <strong>and</strong><br />

see Table 5-2 <strong>for</strong> additional specifications <strong>and</strong> requirements.<br />

FIGURE 5-12 EXAMPLE OF SSGB<br />

Item Specification<br />

Material Bare, solid Alloy 110 (99.9%) copper bus bar or plate of one piece construction.<br />

May be electrotin-plated.<br />

Minimum Dimensions<br />

(ANSI-STD-J-607-A-2002)<br />

Mounting brackets Must be suitable <strong>for</strong> the application.<br />

Height: 50.8 mm (2 in.)<br />

Thickness: 6.35 mm (0.25 in.)<br />

Length: Variable to meet the application requirements <strong>and</strong> allow <strong>for</strong> future growth.<br />

305 mm (12 in) is recommended as the minimum length.<br />

Insulators Polyester<br />

Fiberglass<br />

15 kV minimum dielectric strength<br />

Flame resistant per UL 94 VO classification<br />

Conductor mounting holes Dependent on number of conductors to be attached. Holes should be 11 mm (0.4375 in.)<br />

minimum on 19 mm (0.75 in.) centers to permit the convenient use of two-hole lugs.<br />

Method of attachment of grounding<br />

conductor.<br />

Exothermic welding<br />

Irreversible crimp connection<br />

Other suitable irreversible crimped 2-hole lug<br />

68P81089E50-B 9/1/05 5-17