standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS CHAPTER 5: INTERNAL GROUNDING (EARTHING) Through wall at 45 degree angle, sealed with RTV silicone after grounding conductor is routed through 12.5 mm (0.5 in.) diameter PVC conduit FIGURE 5-9 ROUTING OF MGB GROUNDING ELECTRODE CONDUCTOR • The MGB grounding conductor should not be placed in ferrous metallic conduit. If local building codes require metallic conduit or sleeves, the grounding conductor shall be bonded to each end of the conduit using a listed grounding bushing or a bonding jumper of the same size, or coarser than, the required enclosed grounding electrode conductor (ANSI T1.334-2002, ANSI T1.313-2003 and NFPA 70-2005, Article 250.64(E)). • Unless both ends of the grounding conductor are clearly visible, the conductor must be clearly labeled on both ends (ANSI T1.333-2001). In large and multi-story commercial buildings, each communication grounding and bonding conductor should be labeled as close as practicable to its point of termination in a readable location. The label shall be nonmetallic and should include the following information shown below (ANSI-J-STD-607-A-2002). IF THIS CONNECTOR OR CABLE IS LOOSE OR MUST BE REMOVED, PLEASE CALL THE BUILDING TELECOMMUNICATIONS MANAGER 5.3.1.4 ACCEPTABLE GROUNDING (EARTHING) OF THE MGB The following are considered acceptable for use as a grounding (earthing) electrode system at a communications system facility: • In stand-alone building or equipment shelter, the MGB shall be bonded back to the common external grounding electrode system ground ring conductor (ANSI T1.334-2002 and ANSI T1.313- 2003). See Chapter 4, “External Grounding (Earthing),” for external grounding electrode system requirements. 5-14 68P81089E50-B 9/1/05 MGB GROUND RING
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS • In a small, large or multi-story building, the MGB grounding conductor shall extend from the MGB to the service equipment (power) grounding electrode system (ANSI-J-STD-607-A-2002). • Where any of the following exist at a building or structure, they shall be effectively bonded together to form a common grounding electrode system and the MGB may bond to any point on this grounding electrode system: a metallic underground water pipe, the metal frame of the building or structure, concrete-encased electrodes, a ground ring conductor encircling the building or structure, rod or pipe electrodes and plate electrodes. (See NFPA 70-2005, Article 250.50 and 250.52 for additional information.) See Chapter 4, “External Grounding (Earthing),” for external grounding electrode system bonding requirements. MIN. #2 AWG A GROUND RING LABEL BUILDING STEEL TWO HOLE LUG P A N I MIN. #2 AWG A MIN. #6 AWG A AC SYSTEM GROUND MIN. #2 AWG A MIN. #2 AWG A FIGURE 5-10 TYPES OF ACCEPTABLE GROUNDING ELECTRODE SYSTEMS 5.3.2 SUB SYSTEM GROUND (EARTH) BUS BAR A Sub System Ground Bus Bar (SSGB) may be installed within a generator or power distribution room, a communications subsystem equipment room or area separate from, but associated with, the main communications equipment room or area and located within the same building as the MGB. In some applications the SSGB may be referred to as a telecommunications ground bus bar (TCGB), an isolated zone ground bus bar (IZGB), an ancillary ground bus bar (AGB), a logic ground bus bar (LGB), a frame ground bus bar (FGB), a telephone cable ground bus bar (TCGB), or an equipment reference ground bus bar (ERGB). 68P81089E50-B 9/1/05 5-15 MIN. #4 CLAMP PLATE A ELECTRODE METAL T L UNDERGROUND W A ATER PIPE MIN. 3 M (10 FT) IN EARTH CONCRETE ENCASED ELECTRODE
- Page 157 and 158: STANDARDS AND GUIDELINES FOR COMMUN
- Page 159 and 160: STANDARDS AND GUIDELINES FOR COMMUN
- Page 161 and 162: STANDARDS AND GUIDELINES FOR COMMUN
- Page 163 and 164: STANDARDS AND GUIDELINES FOR COMMUN
- Page 165 and 166: STANDARDS AND GUIDELINES FOR COMMUN
- Page 167 and 168: STANDARDS AND GUIDELINES FOR COMMUN
- Page 169 and 170: STANDARDS AND GUIDELINES FOR COMMUN
- Page 171 and 172: STANDARDS AND GUIDELINES FOR COMMUN
- Page 173 and 174: STANDARDS AND GUIDELINES FOR COMMUN
- Page 175 and 176: STANDARDS AND GUIDELINES FOR COMMUN
- Page 177 and 178: STANDARDS AND GUIDELINES FOR COMMUN
- Page 179 and 180: STANDARDS AND GUIDELINES FOR COMMUN
- Page 181 and 182: STANDARDS AND GUIDELINES FOR COMMUN
- Page 183 and 184: STANDARDS AND GUIDELINES FOR COMMUN
- Page 185 and 186: STANDARDS AND GUIDELINES FOR COMMUN
- Page 187 and 188: STANDARDS AND GUIDELINES FOR COMMUN
- Page 189 and 190: STANDARDS AND GUIDELINES FOR COMMUN
- Page 191 and 192: STANDARDS AND GUIDELINES FOR COMMUN
- Page 193 and 194: STANDARDS AND GUIDELINES FOR COMMUN
- Page 195 and 196: CHAPTER 5 INTERNAL GROUNDING (EARTH
- Page 197 and 198: STANDARDS AND GUIDELINES FOR COMMUN
- Page 199 and 200: STANDARDS AND GUIDELINES FOR COMMUN
- Page 201 and 202: STANDARDS AND GUIDELINES FOR COMMUN
- Page 203 and 204: STANDARDS AND GUIDELINES FOR COMMUN
- Page 205 and 206: STANDARDS AND GUIDELINES FOR COMMUN
- Page 207: STANDARDS AND GUIDELINES FOR COMMUN
- Page 211 and 212: STANDARDS AND GUIDELINES FOR COMMUN
- Page 213 and 214: STANDARDS AND GUIDELINES FOR COMMUN
- Page 215 and 216: STANDARDS AND GUIDELINES FOR COMMUN
- Page 217 and 218: STANDARDS AND GUIDELINES FOR COMMUN
- Page 219 and 220: STANDARDS AND GUIDELINES FOR COMMUN
- Page 221 and 222: STANDARDS AND GUIDELINES FOR COMMUN
- Page 223 and 224: STANDARDS AND GUIDELINES FOR COMMUN
- Page 225 and 226: STANDARDS AND GUIDELINES FOR COMMUN
- Page 227 and 228: STANDARDS AND GUIDELINES FOR COMMUN
- Page 229 and 230: STANDARDS AND GUIDELINES FOR COMMUN
- Page 231 and 232: STANDARDS AND GUIDELINES FOR COMMUN
- Page 233 and 234: STANDARDS AND GUIDELINES FOR COMMUN
- Page 235 and 236: STANDARDS AND GUIDELINES FOR COMMUN
- Page 237 and 238: STANDARDS AND GUIDELINES FOR COMMUN
- Page 239 and 240: STANDARDS AND GUIDELINES FOR COMMUN
- Page 241 and 242: STANDARDS AND GUIDELINES FOR COMMUN
- Page 243 and 244: STANDARDS AND GUIDELINES FOR COMMUN
- Page 245 and 246: STANDARDS AND GUIDELINES FOR COMMUN
- Page 247 and 248: STANDARDS AND GUIDELINES FOR COMMUN
- Page 249 and 250: STANDARDS AND GUIDELINES FOR COMMUN
- Page 251 and 252: STANDARDS AND GUIDELINES FOR COMMUN
- Page 253 and 254: STANDARDS AND GUIDELINES FOR COMMUN
- Page 255 and 256: STANDARDS AND GUIDELINES FOR COMMUN
- Page 257 and 258: STANDARDS AND GUIDELINES FOR COMMUN
GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS CHAPTER 5: INTERNAL GROUNDING (EARTHING)<br />
Through wall at 45 degree<br />
angle, sealed with RTV<br />
silicone after grounding<br />
conductor is routed through<br />
12.5 mm (0.5 in.)<br />
diameter PVC conduit<br />
FIGURE 5-9 ROUTING OF MGB GROUNDING ELECTRODE CONDUCTOR<br />
• The MGB grounding conductor should not be placed in ferrous metallic conduit. If local building<br />
codes require metallic conduit or sleeves, the grounding conductor shall be bonded to each end of<br />
the conduit using a listed grounding bushing or a bonding jumper of the same size, or coarser than,<br />
the required enclosed grounding electrode conductor (ANSI T1.334-2002, ANSI T1.313-2003 <strong>and</strong><br />
NFPA 70-2005, Article 250.64(E)).<br />
• Unless both ends of the grounding conductor are clearly visible, the conductor must be clearly<br />
labeled on both ends (ANSI T1.333-2001). In large <strong>and</strong> multi-story commercial buildings, each<br />
<strong>communication</strong> grounding <strong>and</strong> bonding conductor should be labeled as close as practicable to its<br />
point of termination in a readable location. The label shall be nonmetallic <strong>and</strong> should include the<br />
following in<strong>for</strong>mation shown below (ANSI-J-STD-607-A-2002).<br />
IF THIS CONNECTOR OR CABLE IS LOOSE OR MUST BE<br />
REMOVED, PLEASE CALL THE BUILDING<br />
TELECOMMUNICATIONS MANAGER<br />
5.3.1.4 ACCEPTABLE GROUNDING (EARTHING) OF THE MGB<br />
The following are considered acceptable <strong>for</strong> use as a grounding (earthing) electrode system at a<br />
<strong>communication</strong>s system facility:<br />
• In st<strong>and</strong>-alone building or equipment shelter, the MGB shall be bonded back to the common<br />
external grounding electrode system ground ring conductor (ANSI T1.334-2002 <strong>and</strong> ANSI T1.313-<br />
2003). See Chapter 4, “External Grounding (Earthing),” <strong>for</strong> external grounding electrode system<br />
requirements.<br />
5-14 68P81089E50-B 9/1/05<br />
MGB<br />
GROUND RING