STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS<br />

Grounding<br />

Conductor<br />

Metal Frame<br />

of Building<br />

ELECTRICAL<br />

ENTRANCE<br />

FACILITY F<br />

Electrode<br />

System<br />

SSGB<br />

SSGB<br />

Groundding<br />

Conductor <strong>for</strong> MGB<br />

POLICE DISPA PATCH ROOM<br />

Equipment<br />

OTHER<br />

TELECOMMUNICATIONS A<br />

ROOM<br />

Equipment<br />

TELECOMMUNICATIONS A<br />

ENTRANCE FFACILITY<br />

Equipment<br />

Master Ground<br />

Bus Bar (MGB)<br />

FIGURE 5-4 MULTI-STORY BUILDING WITH COMMON ENTRY LOCATION<br />

An effective low-impedance internal grounding system can be achieved through the use of the<br />

components listed below, all of which must be effectively bonded together so that there is minimal<br />

difference in potential among them. Figure 5-5 shows the major components of a typical internal<br />

grounding system.<br />

• Master Ground Bus Bar (MGB)<br />

• Sub System Ground Bus Bar (SSGB)<br />

• Rack Ground Bus Bar (RGB)<br />

• Grounding conductors<br />

Grounding<br />

Equalizer<br />

Pathways<br />

Communication<br />

Bonding<br />

Backbone<br />

FIRE DISPA PATCH ROOM<br />

Equipment<br />

NETWORK<br />

EQUIPMENT<br />

ROOM<br />

Equipment<br />

= ELECTRICAL PANELBOARD<br />

EQUIPMENT<br />

ROOM<br />

Equipment<br />

Sub System<br />

Bus Bar (SSGB)<br />

68P81089E50-B 9/1/05 5-7<br />

SSGB<br />

SSGB