STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) SYSTEM COMPONENTS AND INSTALLATION REQUIREMENTS<br />

Utility<br />

Panelboard<br />

Generator<br />

Automatic<br />

Transfer Switch<br />

Tele<strong>communication</strong>s<br />

cable entry port<br />

Transmission<br />

Line entry port<br />

MGB Grounding<br />

Electrode<br />

Conductor<br />

UPS<br />

Panelboard<br />

UPS<br />

Electrical Service<br />

Main Disconnect<br />

Electrical Service<br />

ground<br />

Required #2 AWG Grounding Conductor<br />

<strong>for</strong> bonding Primary SPD to the MGB.<br />

MGB<br />

IPGB System<br />

Primary SPD <strong>for</strong><br />

Tele<strong>communication</strong><br />

cable entry port<br />

Shelter External Ground Ring Conductor<br />

#2 AWG grounding electrode conductor<br />

Required because telecom cable entry port<br />

is located more than 20 linear ft from<br />

MGB grounding electrode conductor<br />

FIGURE 5-2 STAND-ALONE SHELTER WITH DIFFERENT ENTRY LOCATIONS<br />

SSGB <strong>for</strong><br />

RF SPDs<br />

Alternate Transmission Line entry port<br />

Note: This configuration is to be avoided whenever possible.<br />

The preferred configuration <strong>for</strong> a single-story building is to have all utilities enter the structure through<br />

a common wall, room or adjacent rooms as close as practical to each other. The single point grounding<br />

location <strong>for</strong> this type of structure must be located at the utilities entrance location, preferably close to<br />

the building's electrical service (power) ground. See Figure 5-3 <strong>for</strong> an overview of the preferred internal<br />

grounding system design.<br />

68P81089E50-B 9/1/05 5-5