standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
INTRODUCTION CHAPTER 5: INTERNAL GROUNDING (EARTHING) Safety of personnel and protection of sensitive electronics equipment from ground faults, lightning, ground potential rise, electrical surges, and power quality anomalies is of utmost importance at any communications site. Though unexpected electrical events like lightning strikes and power surges cannot be prevented, this chapter provides design and installation information on communications site grounding (earthing) systems that may help minimize damage caused by these events. WARNING Grounding and bonding alone are not enough to adequately protect a communications site. Transient voltage surge suppression (TVSS) techniques, using appropriate surge protection devices (SPD), shall be incorporated at a communications site in order to provide an adequate level of protection. See Chapter 7 for details and requirements. WARNING The AC power system ground shall be sized appropriately for the electrical service and shall be approved by the authority having jurisdiction. An internal grounding system shall have low electrical impedance, with conductors large enough to withstand high fault currents. The lower the grounding system impedance, the more effectively the grounding electrode system can dissipate high-energy impulses into the earth. All site development and equipment installation work shall comply with all applicable codes in use by the authority having jurisdiction. Grounding systems shall be installed in a neat and workmanlike manner (NFPA 70-2005, Article 110.12 and NFPA 780-2004, section 1.4). Where conflicting, the more stringent standard should be followed. Government and local codes shall take precedence over the requirements of this manual. Unusual site conditions may require additional effort to achieve an effectively bonded and grounded (earthed) site. See Chapter 2, “Site Design and Development”. In these instances, consultation with Motorola Engineering or with an engineering firm specializing in grounding system design is recommended. Some of the benefits of a properly designed and installed low-impedance grounding system are described below. See ANSI T1.333-2001, section 4; ANSI T1.334-2002, section 5.1; IEEE STD 142- 1991, section 1.3; IEEE STD 1100-1999, section 3.3.1; and NFPA 70-2005, Article 250.4 for additional information. • To help limit potential differences between conductive surfaces caused by electrical disturbances such as electrical power faults, lightning strikes and electrostatic discharges. • To help provide fault current paths of sufficient current carrying capacity and low impedance to allow overcurrent protection devices to operate. • To help limit the voltage caused by accidental contact of the site AC supply conductors with conductors of higher voltage. • To help dissipate electrical surges and faults, to minimize the chances of injury from grounding system potential differences. • To help dissipate the voltages caused by lightning. • To help maintain a low potential difference among exposed metallic objects. 5-2 68P81089E50-B 9/1/05
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES COMMON GROUNDING (EARTHING) • To contribute to reliable equipment operation. • To provide a common signal reference ground. 5.2 COMMON GROUNDING (EARTHING) At a communications site, there shall be only one grounding (earthing) electrode system. For example, the AC power system ground, communications tower ground, lightning protection system ground, telephone system ground, exposed structural building steel, underground metallic piping, and any other existing grounding system shall be bonded together to form a single grounding electrode system. Underground metallic piping systems typically include water service, well castings located within 7.6 m (25 ft.) of the structure, gas piping, underground conduits, and underground liquefied petroleum gas piping systems. (ANSI T1.313-2003; ANSI T1.333-2001; ANSI T1.334-2002; IEC 61024-1-2, section 2.4.4; IEEE STD 1100-1999; NFPA 70-2005, Articles 250.58, 250.104, 250.106, 800.100, 810.21, and 820.100; and NFPA 780-2004, Section 4.14). Interconnection to a gas line shall be made on the customer's side of the meter (NFPA 780-2004, Section 4.14.1.3). See Chapter 6, “Power Sources” for additional information on grounding and bonding requirements of power sources. The objective of grounding and bonding system components to a single point is to minimize any difference of potential that may develop between individual components within the system and within the equipment site or area. To reach this objective a low-impedance internal single-point ground system is required for all communication equipment, support equipment, power systems, and other items and materials located within the building, shelter, room or area of the same building. A single point ground system is defined as a single point, typically a master ground bus bar (MGB), within a shelter, equipment building or room, where all communications equipment, ancillary support equipment, antenna transmission lines, surge protection devices (SPDs), and utility grounds are bonded. The single point ground system must be effectively connected to a grounding electrode system as described in this chapter and in Chapter 4, “External Grounding (Earthing)”. The system is defined as all equipment required for proper communications system functionality at the site, and includes but is not limited to: • Communications and support equipment • Power systems • Power distribution systems • Voice, data and video circuits • Antenna systems • Global Positioning System (GPS) • Surge protection devices • Support components and material. The equipment site or area is defined as the equipment building, shelter, room or area within another room where communications equipment or systems may be located and includes but is not limited to: • Heating, ventilation and air conditioning (HVAC) systems • Fire suppression systems • Power distribution systems • The building structure 68P81089E50-B 9/1/05 5-3
- Page 145 and 146: STANDARDS AND GUIDELINES FOR COMMUN
- Page 147 and 148: STANDARDS AND GUIDELINES FOR COMMUN
- Page 149 and 150: STANDARDS AND GUIDELINES FOR COMMUN
- Page 151 and 152: STANDARDS AND GUIDELINES FOR COMMUN
- Page 153 and 154: STANDARDS AND GUIDELINES FOR COMMUN
- Page 155 and 156: STANDARDS AND GUIDELINES FOR COMMUN
- Page 157 and 158: STANDARDS AND GUIDELINES FOR COMMUN
- Page 159 and 160: STANDARDS AND GUIDELINES FOR COMMUN
- Page 161 and 162: STANDARDS AND GUIDELINES FOR COMMUN
- Page 163 and 164: STANDARDS AND GUIDELINES FOR COMMUN
- Page 165 and 166: STANDARDS AND GUIDELINES FOR COMMUN
- Page 167 and 168: STANDARDS AND GUIDELINES FOR COMMUN
- Page 169 and 170: STANDARDS AND GUIDELINES FOR COMMUN
- Page 171 and 172: STANDARDS AND GUIDELINES FOR COMMUN
- Page 173 and 174: STANDARDS AND GUIDELINES FOR COMMUN
- Page 175 and 176: STANDARDS AND GUIDELINES FOR COMMUN
- Page 177 and 178: STANDARDS AND GUIDELINES FOR COMMUN
- Page 179 and 180: STANDARDS AND GUIDELINES FOR COMMUN
- Page 181 and 182: STANDARDS AND GUIDELINES FOR COMMUN
- Page 183 and 184: STANDARDS AND GUIDELINES FOR COMMUN
- Page 185 and 186: STANDARDS AND GUIDELINES FOR COMMUN
- Page 187 and 188: STANDARDS AND GUIDELINES FOR COMMUN
- Page 189 and 190: STANDARDS AND GUIDELINES FOR COMMUN
- Page 191 and 192: STANDARDS AND GUIDELINES FOR COMMUN
- Page 193 and 194: STANDARDS AND GUIDELINES FOR COMMUN
- Page 195: CHAPTER 5 INTERNAL GROUNDING (EARTH
- Page 199 and 200: STANDARDS AND GUIDELINES FOR COMMUN
- Page 201 and 202: STANDARDS AND GUIDELINES FOR COMMUN
- Page 203 and 204: STANDARDS AND GUIDELINES FOR COMMUN
- Page 205 and 206: STANDARDS AND GUIDELINES FOR COMMUN
- Page 207 and 208: STANDARDS AND GUIDELINES FOR COMMUN
- Page 209 and 210: STANDARDS AND GUIDELINES FOR COMMUN
- Page 211 and 212: STANDARDS AND GUIDELINES FOR COMMUN
- Page 213 and 214: STANDARDS AND GUIDELINES FOR COMMUN
- Page 215 and 216: STANDARDS AND GUIDELINES FOR COMMUN
- Page 217 and 218: STANDARDS AND GUIDELINES FOR COMMUN
- Page 219 and 220: STANDARDS AND GUIDELINES FOR COMMUN
- Page 221 and 222: STANDARDS AND GUIDELINES FOR COMMUN
- Page 223 and 224: STANDARDS AND GUIDELINES FOR COMMUN
- Page 225 and 226: STANDARDS AND GUIDELINES FOR COMMUN
- Page 227 and 228: STANDARDS AND GUIDELINES FOR COMMUN
- Page 229 and 230: STANDARDS AND GUIDELINES FOR COMMUN
- Page 231 and 232: STANDARDS AND GUIDELINES FOR COMMUN
- Page 233 and 234: STANDARDS AND GUIDELINES FOR COMMUN
- Page 235 and 236: STANDARDS AND GUIDELINES FOR COMMUN
- Page 237 and 238: STANDARDS AND GUIDELINES FOR COMMUN
- Page 239 and 240: STANDARDS AND GUIDELINES FOR COMMUN
- Page 241 and 242: STANDARDS AND GUIDELINES FOR COMMUN
- Page 243 and 244: STANDARDS AND GUIDELINES FOR COMMUN
- Page 245 and 246: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES COMMON GROUNDING (EARTHING)<br />
• To contribute to reliable equipment operation.<br />
• To provide a common signal reference ground.<br />
5.2 COMMON GROUNDING (EARTHING)<br />
At a <strong>communication</strong>s site, there shall be only one grounding (earthing) electrode system. For example,<br />
the AC power system ground, <strong>communication</strong>s tower ground, lightning protection system ground,<br />
telephone system ground, exposed structural building steel, underground metallic piping, <strong>and</strong> any other<br />
existing grounding system shall be bonded together to <strong>for</strong>m a single grounding electrode system.<br />
Underground metallic piping systems typically include water service, well castings located within 7.6 m<br />
(25 ft.) of the structure, gas piping, underground conduits, <strong>and</strong> underground liquefied petroleum gas<br />
piping systems. (ANSI T1.313-2003; ANSI T1.333-2001; ANSI T1.334-2002; IEC 61024-1-2, section<br />
2.4.4; IEEE STD 1100-1999; NFPA 70-2005, Articles 250.58, 250.104, 250.106, 800.100, 810.21, <strong>and</strong><br />
820.100; <strong>and</strong> NFPA 780-2004, Section 4.14).<br />
Interconnection to a gas line shall be made on the customer's side of the meter (NFPA 780-2004,<br />
Section 4.14.1.3). See Chapter 6, “Power Sources” <strong>for</strong> additional in<strong>for</strong>mation on grounding <strong>and</strong><br />
bonding requirements of power sources.<br />
The objective of grounding <strong>and</strong> bonding system components to a single point is to minimize any<br />
difference of potential that may develop between individual components within the system <strong>and</strong> within<br />
the equipment site or area. To reach this objective a low-impedance internal single-point ground system<br />
is required <strong>for</strong> all <strong>communication</strong> equipment, support equipment, power systems, <strong>and</strong> other items <strong>and</strong><br />
materials located within the building, shelter, room or area of the same building.<br />
A single point ground system is defined as a single point, typically a master ground bus bar (MGB),<br />
within a shelter, equipment building or room, where all <strong>communication</strong>s equipment, ancillary support<br />
equipment, antenna transmission lines, surge protection devices (SPDs), <strong>and</strong> utility grounds are bonded.<br />
The single point ground system must be effectively connected to a grounding electrode system as<br />
described in this chapter <strong>and</strong> in Chapter 4, “External Grounding (Earthing)”.<br />
The system is defined as all equipment required <strong>for</strong> proper <strong>communication</strong>s system functionality at the<br />
site, <strong>and</strong> includes but is not limited to:<br />
• Communications <strong>and</strong> support equipment<br />
• Power systems<br />
• Power distribution systems<br />
• Voice, data <strong>and</strong> video circuits<br />
• Antenna systems<br />
• Global Positioning System (GPS)<br />
• Surge protection devices<br />
• Support components <strong>and</strong> material.<br />
The equipment site or area is defined as the equipment building, shelter, room or area within another<br />
room where <strong>communication</strong>s equipment or systems may be located <strong>and</strong> includes but is not limited to:<br />
• Heating, ventilation <strong>and</strong> air conditioning (HVAC) systems<br />
• Fire suppression systems<br />
• Power distribution systems<br />
• The building structure<br />
68P81089E50-B 9/1/05 5-3