SPECIAL GROUNDING (EARTHING) SITUATIONS CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

• Installation of down conductors to a lower area where there is usable soil <strong>for</strong> the installation of<br />

vertical ground rods. The down conductors would be more effective if buried below ground like a<br />

radial grounding conductor, wherever possible. The down conductors shall be sized according to<br />

length as shown below in Table 4-8 (based on MIL-HDBK-419A). See Figure 4-69 on page 4-96.<br />

TABLE 4-8 GROUNDING CONDUCTOR SIZING<br />

Conductor length in<br />

linear m (ft)<br />

Conductor size in<br />

mm 2 csa (AWG / MCM)<br />

Less than 10 (Less than 33) 33.62 (2)<br />

10.36 – 12.5 (34 – 41) 42.4 (1)<br />

12.8 – 16 (42 – 53) 52 (1/0)<br />

16.5 – 20 (54 – 66) 67.4 (2/0)<br />

20.4 – 25.6 (67 – 84) 85 (3/0)<br />

25.9 – 32 (85 – 105) 107 (4/0)<br />

32.3 – 38.1 (106 – 125) 126.70 (250 MCM)<br />

38.4 – 45.7 (126 – 150) 152 (300 MCM)<br />

46 – 53.34 (151 – 175) 177 (350 MCM)<br />

53 – 76.1 (176 – 250) 253.4 (500 MCM)<br />

76.4 – 91.39 (251 – 300) 300 (600 MCM)<br />

Greater than 91.39 (300) 380 (750 MCM)<br />

4-94 68P81089E50-B 9/1/05