SPECIAL GROUNDING (EARTHING) APPLICATIONS CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

• Electrostatic discharge (ESD) precautions as defined in “Protecting Against Electrostatic Discharge<br />

in Equipment Rooms <strong>and</strong> Dispatch Centers” on page C-1.<br />

• External grounding (earthing) as follows:<br />

• Grounding electrode system resistance design goal of 5 ohms or less. See “Type “B” Site -<br />

St<strong>and</strong>ard Duty” on page 4-45.<br />

• Installation of all minimum required grounding electrode system components as described in<br />

“External Building <strong>and</strong> Tower Ground Ring” on page 4-22.<br />

• Bonding of all metallic objects as described in “Metallic Objects Requiring Bonding” on<br />

page 4-67.<br />

• Installation of radial grounding conductors as described in “Radial (Counterpoise) Grounding<br />

Conductors” on page 4-24. Radial grounding conductors should be installed regardless if the<br />

grounding electrode system resistance is 5 ohms or less without the radial grounding<br />

conductors. A minimum of five radial grounding conductors should be installed.<br />

9.1 m (30 ft) MINIMUM<br />

BETWEEN TOWER AND<br />

BUILDING (PREFERRED)<br />

CABLE ENTRY PORT WITHIN<br />

610 mm (2 ft) OF FLOOR<br />

(PREFERRED)<br />

ICE BRIDGE<br />

SIDE VIEW OF BUILDING<br />

NOTE: EGB AND COAX<br />

GROUNDING NOT SHOWN.<br />

FIGURE 4-58 GROUNDING ELECTRODE SYSTEM FOR DISPATCH CENTER CO-LOCATED WITH A<br />

TOWER<br />

4-82 68P81089E50-B 9/1/05