standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
GROUNDING (EARTHING) ROOF-MOUNTED ANTENNA MASTS AND METAL SUPPORT STRUCTURES CHAPTER 4: EXTERNAL GROUNDING (EARTHING) 35 mm 2 csa (#2 AWG) CONDUCTOR FIGURE 4-55 SIDE-MOUNTED ANTENNA GROUNDING USING COPPER STRAP DOWN CONDUCTOR When multiple side mounted antennas are installed together, a single horizontal grounding conductor should bond all antenna masts together. The horizontal grounding conductor should bond to the grounding electrode system from each side of the side mounted antennas with a grounding downconductor. When several antennas are installed together, therefore, creating a long horizontal grounding conductor, it is recommended to install intermediate grounding down-conductors every 6.1 m (20 ft.). ANTENNA MOUNT 35 mm 2 csa (#2 AWG) CONDUCTORS ANTENNA MOUNT EGB EGB ANTENNA TRANSMISSION LINE GROUND KIT GROUND RODS ANTENNA GROUND RODS TRANSMISSION LINE GROUND KITS FIGURE 4-56 GROUNDING OF MULTIPLE SIDE-MOUNTED ANTENNAS 508 mm (2 in.) STRAP (RECOMMENDED) 35 mm 2 csa (#2 AWG) MINIMUM ELECTRICAL SERVICE ELECTRICAL SERVICE 4-78 68P81089E50-B 9/1/05
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) ROOFTOP MOUNTED TOWER STRUCTURES 4.9 GROUNDING (EARTHING) ROOFTOP MOUNTED TOWER STRUCTURES Rooftop mounted towers may increase the lightning risk index for the buildings they are installed upon. Due to their increased height and lightning risk probability, all exposed buildings with rooftop towers shall be equipped with a lightning protection system, as outlined in NFPA 780-2004 (ANSI T1.313- 2003, section 10.3.3). See “Lightning Activity and Exposure” on page 4-3 for information regarding lightning exposure to buildings and towers. NOTE: Consult the building engineer or manager to determine information about any existing building grounding (earthing) electrode systems. The building engineer should also be informed before attempting to weld or drill on the building rooftop. An engineering firm specializing in the design and installation of lightning protection systems should be consulted for proper design and installation of the building lightning protection system. A licensed contractor specializing in the installation of lightning protection systems should be used. The lightning protection system shall be constructed of only listed components. The lightning protection system shall meet the requirements of BS 6651:1999, IEC 61024-1-2, NFPA 780-2004, or other standard in effect and recognized by the local authority having jurisdiction. As a minimum the lightning protection system shall contain the following: • The lightning protection system shall contain a grounding conductor installed around the roof perimeter to form the main roof perimeter lightning protection ring. The main roof perimeter lightning protection ring shall be sized as follows: • The conductor shall be a 35 mm 2 csa (#2 AWG) or coarser, bare, copper or equivalent, for buildings not exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(A)). • The conductor shall be a 70 mm 2 csa (#2/0 AWG) or coarser, bare, copper or equivalent, for buildings equal to or exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(B)). • Strike termination devices, also known as air terminals, are typically installed along the length of the main roof perimeter lightning protection ring, typically every 6.1 m (20 ft.) or as otherwise required by the standard in effect and recognized by the local authority having jurisdiction. • The main roof perimeter lightning protection ring shall contain at least two down conductors connected to the grounding electrode system. The down conductors shall be physically separated from one another as much as practical. The down conductors shall be sized as follows: • The conductor shall be a 35 mm2 csa (#2 AWG) or coarser, bare, copper or equivalent, for buildings not exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(A)). • The conductor shall be a 70 mm2 csa (#2/0 AWG) or coarser, bare, copper or equivalent, for buildings equal to or exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(B)). NOTE: Available effectively grounded structural building steel can typically be used as a grounding downconductor. The conductor used to bond the main roof perimeter lightning protection ring to the structural building steel shall be sized as required in this section for down-conductors. See Figure 4-53 on page 4-75 for an example of acceptable structural building steel bonding connections. • Structures exceeding 76 m (250 ft.) in perimeter shall have a down conductor for every 30.5 m (100 ft) of perimeter or fraction thereof (NFPA 780-2004, section 4.9.10.1). 68P81089E50-B 9/1/05 4-79
- Page 121 and 122: STANDARDS AND GUIDELINES FOR COMMUN
- Page 123 and 124: STANDARDS AND GUIDELINES FOR COMMUN
- Page 125 and 126: STANDARDS AND GUIDELINES FOR COMMUN
- Page 127 and 128: STANDARDS AND GUIDELINES FOR COMMUN
- Page 129 and 130: STANDARDS AND GUIDELINES FOR COMMUN
- Page 131 and 132: STANDARDS AND GUIDELINES FOR COMMUN
- Page 133 and 134: STANDARDS AND GUIDELINES FOR COMMUN
- Page 135 and 136: STANDARDS AND GUIDELINES FOR COMMUN
- Page 137 and 138: STANDARDS AND GUIDELINES FOR COMMUN
- Page 139 and 140: STANDARDS AND GUIDELINES FOR COMMUN
- Page 141 and 142: STANDARDS AND GUIDELINES FOR COMMUN
- Page 143 and 144: STANDARDS AND GUIDELINES FOR COMMUN
- Page 145 and 146: STANDARDS AND GUIDELINES FOR COMMUN
- Page 147 and 148: STANDARDS AND GUIDELINES FOR COMMUN
- Page 149 and 150: STANDARDS AND GUIDELINES FOR COMMUN
- Page 151 and 152: STANDARDS AND GUIDELINES FOR COMMUN
- Page 153 and 154: STANDARDS AND GUIDELINES FOR COMMUN
- Page 155 and 156: STANDARDS AND GUIDELINES FOR COMMUN
- Page 157 and 158: STANDARDS AND GUIDELINES FOR COMMUN
- Page 159 and 160: STANDARDS AND GUIDELINES FOR COMMUN
- Page 161 and 162: STANDARDS AND GUIDELINES FOR COMMUN
- Page 163 and 164: STANDARDS AND GUIDELINES FOR COMMUN
- Page 165 and 166: STANDARDS AND GUIDELINES FOR COMMUN
- Page 167 and 168: STANDARDS AND GUIDELINES FOR COMMUN
- Page 169 and 170: STANDARDS AND GUIDELINES FOR COMMUN
- Page 171: STANDARDS AND GUIDELINES FOR COMMUN
- Page 175 and 176: STANDARDS AND GUIDELINES FOR COMMUN
- Page 177 and 178: STANDARDS AND GUIDELINES FOR COMMUN
- Page 179 and 180: STANDARDS AND GUIDELINES FOR COMMUN
- Page 181 and 182: STANDARDS AND GUIDELINES FOR COMMUN
- Page 183 and 184: STANDARDS AND GUIDELINES FOR COMMUN
- Page 185 and 186: STANDARDS AND GUIDELINES FOR COMMUN
- Page 187 and 188: STANDARDS AND GUIDELINES FOR COMMUN
- Page 189 and 190: STANDARDS AND GUIDELINES FOR COMMUN
- Page 191 and 192: STANDARDS AND GUIDELINES FOR COMMUN
- Page 193 and 194: STANDARDS AND GUIDELINES FOR COMMUN
- Page 195 and 196: CHAPTER 5 INTERNAL GROUNDING (EARTH
- Page 197 and 198: STANDARDS AND GUIDELINES FOR COMMUN
- Page 199 and 200: STANDARDS AND GUIDELINES FOR COMMUN
- Page 201 and 202: STANDARDS AND GUIDELINES FOR COMMUN
- Page 203 and 204: STANDARDS AND GUIDELINES FOR COMMUN
- Page 205 and 206: STANDARDS AND GUIDELINES FOR COMMUN
- Page 207 and 208: STANDARDS AND GUIDELINES FOR COMMUN
- Page 209 and 210: STANDARDS AND GUIDELINES FOR COMMUN
- Page 211 and 212: STANDARDS AND GUIDELINES FOR COMMUN
- Page 213 and 214: STANDARDS AND GUIDELINES FOR COMMUN
- Page 215 and 216: STANDARDS AND GUIDELINES FOR COMMUN
- Page 217 and 218: STANDARDS AND GUIDELINES FOR COMMUN
- Page 219 and 220: STANDARDS AND GUIDELINES FOR COMMUN
- Page 221 and 222: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) ROOFTOP MOUNTED TOWER STRUCTURES<br />
4.9 GROUNDING (EARTHING) ROOFTOP MOUNTED TOWER<br />
STRUCTURES<br />
Rooftop mounted towers may increase the lightning risk index <strong>for</strong> the buildings they are installed upon.<br />
Due to their increased height <strong>and</strong> lightning risk probability, all exposed buildings with rooftop towers<br />
shall be equipped with a lightning protection system, as outlined in NFPA 780-2004 (ANSI T1.313-<br />
2003, section 10.3.3). See “Lightning Activity <strong>and</strong> Exposure” on page 4-3 <strong>for</strong> in<strong>for</strong>mation regarding<br />
lightning exposure to buildings <strong>and</strong> towers.<br />
NOTE: Consult the building engineer or manager to determine in<strong>for</strong>mation about any existing building<br />
grounding (earthing) electrode systems. The building engineer should also be in<strong>for</strong>med be<strong>for</strong>e<br />
attempting to weld or drill on the building rooftop.<br />
An engineering firm specializing in the design <strong>and</strong> installation of lightning protection systems should be<br />
consulted <strong>for</strong> proper design <strong>and</strong> installation of the building lightning protection system. A licensed<br />
contractor specializing in the installation of lightning protection systems should be used. The lightning<br />
protection system shall be constructed of only listed components. The lightning protection system shall<br />
meet the requirements of BS 6651:1999, IEC 61024-1-2, NFPA 780-2004, or other st<strong>and</strong>ard in effect<br />
<strong>and</strong> recognized by the local authority having jurisdiction. As a minimum the lightning protection system<br />
shall contain the following:<br />
• The lightning protection system shall contain a grounding conductor installed around the roof<br />
perimeter to <strong>for</strong>m the main roof perimeter lightning protection ring. The main roof perimeter<br />
lightning protection ring shall be sized as follows:<br />
• The conductor shall be a 35 mm 2 csa (#2 AWG) or coarser, bare, copper or equivalent, <strong>for</strong><br />
buildings not exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(A)).<br />
• The conductor shall be a 70 mm 2 csa (#2/0 AWG) or coarser, bare, copper or equivalent, <strong>for</strong><br />
buildings equal to or exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(B)).<br />
• Strike termination devices, also known as air terminals, are typically installed along the length of<br />
the main roof perimeter lightning protection ring, typically every 6.1 m (20 ft.) or as otherwise<br />
required by the st<strong>and</strong>ard in effect <strong>and</strong> recognized by the local authority having jurisdiction.<br />
• The main roof perimeter lightning protection ring shall contain at least two down conductors<br />
connected to the grounding electrode system. The down conductors shall be physically separated<br />
from one another as much as practical. The down conductors shall be sized as follows:<br />
• The conductor shall be a 35 mm2 csa (#2 AWG) or coarser, bare, copper or equivalent, <strong>for</strong><br />
buildings not exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(A)).<br />
• The conductor shall be a 70 mm2 csa (#2/0 AWG) or coarser, bare, copper or equivalent, <strong>for</strong><br />
buildings equal to or exceeding 22.9 m (75 ft.) in height (NFPA 780-2004, Table 4.1.1.1(B)).<br />
NOTE: Available effectively grounded structural building steel can typically be used as a grounding downconductor.<br />
The conductor used to bond the main roof perimeter lightning protection ring to the<br />
structural building steel shall be sized as required in this section <strong>for</strong> down-conductors. See Figure 4-53<br />
on page 4-75 <strong>for</strong> an example of acceptable structural building steel bonding connections.<br />
• Structures exceeding 76 m (250 ft.) in perimeter shall have a down conductor <strong>for</strong> every 30.5 m<br />
(100 ft) of perimeter or fraction thereof (NFPA 780-2004, section 4.9.10.1).<br />
68P81089E50-B 9/1/05 4-79