STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />

4.7.10 METALLIC OBJECTS REQUIRING BONDING<br />

The objective of bonding metallic objects is to equalize the potential between conductive parts. This is<br />

done <strong>for</strong> personnel safety <strong>and</strong> to prevent arcing between metallic components that might otherwise be at<br />

different potentials. Bonding conductors shall be as short <strong>and</strong> straight as possible. (ANSI T1.313-2003,<br />

section 6.3)<br />

Metallic objects that are located within 1.8 m (6 ft.) of the external grounding (earthing) electrode<br />

system, or within 1.8 m (6 ft.) of a grounded metallic item, shall be bonded to the external grounding<br />

electrode system using 16 mm 2 csa (#6 AWG) or coarser conductors as described in “Grounding<br />

(Earthing) Conductors” on page 4-28 (ANSI T1.334-2002, section 5.3.3). Bonding to the metallic<br />

objects shall be made as allowed by the manufacturer. In high lightning prone geographical areas, or<br />

areas of high soil resistivity, it is recommended to bond all metallic objects that are located within 3 m<br />

(10 ft.) of the external grounding electrode system, or within 3 m (10 ft.) of a grounded metallic item<br />

(ANSI T1.313-2003, section 10.3.2). Metallic objects requiring bonding include, but are not limited to,<br />

the items listed below. (ANSI T1.313-2003, section 10.3.2; ANSI T1.334-2002, section 5.3.3.)<br />

• Fences<br />

• Fence posts<br />

• Fence gates<br />

• Cable Bridge/Ice Bridge<br />

• Generator frame<br />

• Skid plate or metal support frame of a prefabricated shelter<br />

• Metallic members of all incoming tele<strong>communication</strong>s cables, including paired-conductor <strong>and</strong><br />

optical fiber (ANSI T1.313-2003, section 8.2)<br />

• Facility grounding electrode system<br />

• Main telephone company ground (if external)<br />

• Metallic entry points<br />

• Metallic conduits, piping, <strong>and</strong> raceways<br />

• HVAC units<br />

• Vent covers (if not already grounded inside)<br />

• Storage tanks (above <strong>and</strong> below grade) if allowed<br />

• External light fixtures or support masts<br />

• Any other grounding electrode systems at the site<br />

(see “Common Grounding (Earthing)” on page 4-5)<br />

NOTE: Bonding conductors installed underground shall be constructed of 35 mm 2 csa (#2 AWG) or coarser<br />

conductor. See “Grounding (Earthing) Conductors” on page 4-28.<br />

Series or daisy chain 1 connection arrangements shall not be used. (See Figure 5-20 on page 5-34 <strong>for</strong> an<br />

example of a “daisy-chained” ground connection.)<br />

68P81089E50-B 9/1/05 4-67