24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />

• Transmission line ground kits shall be attached to an effectively grounded vertical member of the<br />

tower, using tower manufacturer-approved methods (typically a type of mechanical clamp).<br />

Transmission line ground kits may attach to a tower bus bar in lieu of directly attaching to the tower<br />

structure, see “Tower Ground Bus Bar” on page 4-32. See Figure 4-42 through Figure 4-46 <strong>for</strong><br />

examples of methods used to attach to the tower. (ANSI T1.313-2003, section 10.5)<br />

• Transmission line ground kit grounding conductors shall be installed without drip loops, parallel to<br />

the transmission line, <strong>and</strong> pointed down towards the ground to provide a direct discharge path <strong>for</strong><br />

lightning (ANSI T1.313-2003, section 10.5.1).<br />

• Transmission line ground kits shall be installed at the first point of contact, near the antenna (ANSI<br />

T1.334-2002, section 6.6; ANSI T1.313-2003, section 10.5.1; <strong>and</strong> MIL-HDBK-419A).<br />

• Transmission line ground kits shall be installed at the bottom of the tower near the vertical to<br />

horizontal transition point (ANSI T1.313-2003, section 10.5.1; ANSI T1.334-2002, section 6.6;<br />

<strong>and</strong> MIL-HDBK-419A). The ground kits shall be bonded to the tower or tower ground bus bar<br />

(TGB) if installed.<br />

• If the tower is greater than 61 m (200 ft.) in height, an additional ground kit shall be installed at the<br />

tower midpoint (ANSI T1.334-2002, section 6.6 <strong>and</strong> MIL-HDBK-419A). Additional ground kits<br />

shall be installed as necessary to reduce the distance between ground kits to 61 m (200 ft.) or less.<br />

• In high lightning prone geographical areas, additional ground kits should be installed at spacing<br />

between 15.2 to 22.9 m (50 to 75 ft.) (ANSI T1.313, section 10.5.1 <strong>and</strong> ANSI T1.334-2002,<br />

section 6.6). This is especially important on towers taller than 45.7 m (150 ft.).<br />

NOTE: The use of down-conductors on metallic towers is not recommended <strong>for</strong> grounding/bonding<br />

transmission lines. The down-conductor has a much higher impedance to earth than the tower. The use<br />

of down-conductors does not provide equipotential bonding between the transmission lines <strong>and</strong> tower.<br />

Transmission line ground kits shall be installed near the building, shelter, equipment housing, or cabinet<br />

entry point (ANSI T1.334-2002, section 6.6; MIL-HDBK-419A; <strong>and</strong> NFPA 70-2005, Articles 810.20<br />

<strong>and</strong> 820.93). The ground kits shall bond to the external ground bus bar (EGB) if installed, or directly to<br />

the grounding electrode system, ensuring a continuous downward flow toward the grounding electrode<br />

system is maintained.<br />

NOTE: Transmission lines installed on a wooden pole structure shall bond to the wooden pole vertical<br />

grounding conductor in the same manner as described above.<br />

CAUTION<br />

Braided grounding conductors shall not be used under any circumstances. Braided<br />

conductors corrode easily <strong>and</strong> become a point <strong>for</strong> RF interference.<br />

68P81089E50-B 9/1/05 4-63

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!