24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />

4.7.8 OUTDOOR CABINET GROUNDING (EARTHING)<br />

Outdoor cabinets are grounded (earthed) in a very similar manner as a dedicated <strong>communication</strong>s<br />

building (ANSI T1.313-2003, section 1.1). See “Dedicated Communications Building Grounding<br />

(Earthing)” on page 4-59 <strong>for</strong> details.<br />

Outdoor cabinets shall be grounded as follows:<br />

• The cabinet shall be encircled with a ground ring. The ground ring shall meet the requirements<br />

defined in “External Building <strong>and</strong> Tower Ground Ring” on page 4-22.<br />

• The ground ring shall be installed at least 610 mm (2 ft.) from the cabinet foundation/pad.<br />

• The cabinet ground ring shall have a ground rod installed at each corner <strong>and</strong> as needed to limit the<br />

distance between rods from 3 m to 4.6 m (10 to 15 ft.). Ground rods shall have a minimum<br />

separation from other ground rods equal to its length (ANSI T1.313-2003).<br />

• The cabinet ground ring shall bond to the tower ground ring as detailed in “External Building <strong>and</strong><br />

Tower Ground Ring” on page 4-22.<br />

• Towers associated with outdoor cabinets shall be grounded as detailed in “Tower Grounding<br />

(Earthing)” on page 4-50.<br />

• RF transmission lines shall be grounded/bonded as detailed in “RF Transmission Line <strong>and</strong><br />

Preamplifier Grounding (Earthing)” on page 4-62.<br />

• Metallic objects near the cabinet shall be bonded to the cabinet grounding electrode system as<br />

detailed in “Metallic Objects Requiring Bonding” on page 4-67.<br />

• The cabinet grounding electrode system shall bond to the cabinet's internal ground point <strong>and</strong><br />

cabinet housing using a 35 mm 2 csa (#2 AWG) or coarser, tinned or un-tinned, copper conductor.<br />

The conductor shall be run in a direct manner with no sharp bends or narrow loops (ANSI T1.313-<br />

2003, section 11.3, <strong>and</strong> ANSI T1.334-2002, section 13.4). See “Bending <strong>And</strong> Routing Grounding<br />

(Earthing) Conductors” on page 4-29.<br />

In addition to the above requirements, the follow recommendations should be considered:<br />

• Cabinets installed on pads that incorporate a footing should consider the use of concrete encased<br />

electrodes, in addition to the ground ring. See “Concrete-Encased Electrodes” on page 4-20.<br />

• Depending on the location of the cabinet's internal ground point, the grounding conductor installed<br />

between the grounding electrode system <strong>and</strong> the cabinet's internal ground point may need to be<br />

routed through the concrete footing/pad in order to allow conductor routing in a direct manner. This<br />

requires the grounding conductor to be installed be<strong>for</strong>e the concrete is poured.<br />

68P81089E50-B 9/1/05 4-61

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!