standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS CHAPTER 4: EXTERNAL GROUNDING (EARTHING) 4.7.6.3 WOODEN STRUCTURES (POLES) Wooden pole structure towers (and other non-metallic towers) shall minimally be grounded (earthed) as follows: • The wooden pole shall have a vertical grounding conductor installed over the length of the wooden pole. • The vertical grounding conductor shall be constructed of 35 mm 2 csa (#2 AWG) or coarser solid, bare, tinned or un-tinned copper conductor (ANSI T1.334-2002, section 6.5). • The grounding conductor shall be installed in accordance with “Grounding (Earthing) Conductors” on page 4-28. • The vertical grounding conductor shall terminate into a radial grounding conductor or tower ground ring (with rods) (ANSI T1.334-2002, section 6.5). • The radial grounding conductor shall be installed in accordance with “Radial (Counterpoise) Grounding Conductors” on page 4-24. • The tower ground ring shall be installed in accordance with “External Building and Tower Ground Ring” on page 4-22. • Ground rods shall meet the specifications and be installed in accordance with “Ground Rods” on page 4-11. • The wooden pole grounding electrode system shall be bonded to the building grounding electrode system. See “Common Grounding (Earthing)” on page 4-5. WOODEN POLE 35 mm 2 csa (#2 AWG) OR COARSER BARE COPPER CONDUCTOR ROUTED ON OPPOSITE SIDE FROM TRANSMISSION LINE GROUND KITS GROUND RODS FIGURE 4-39 WOODEN POLE GROUNDING ANTENNA TRANSMISSION LINE TO SHELTER 4-58 68P81089E50-B 9/1/05 GRADE
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS 4.7.7 DEDICATED COMMUNICATIONS BUILDING GROUNDING (EARTHING) All dedicated communications buildings shall have a properly installed external grounding (earthing) electrode system. The grounding electrode system resistance shall meet the requirements of “Grounding (Earthing) Electrode System Resistance Requirements” on page 4-46. A typical site grounding electrode system layout is shown in Figure 4-4 on page 4-8. The building grounding electrode system requirements are listed below and shall also include any additional grounding electrode system components required to achieve the resistance requirements of the site. See “Minimum Site Grounding (Earthing) Requirements” on page 4-44. • Installation of concrete encased electrodes as part of new construction. See “Concrete-Encased Electrodes” on page 4-20. • The building shall be encircled by a ground ring installed in accordance with “External Building and Tower Ground Ring” on page 4-22. • The building ground ring shall have a ground rod installed near the external ground bus bar (EGB), at each corner of the shelter, and as follows: • If 2.4 m (8 ft.) ground rods are used, additional ground rods shall be installed as needed to reduce the distance between rods from 3 m to 4.6 m (10 to 15 ft.) (ANSI T1.334-2002). • If longer ground rods are used, a larger separation proportional to the increase in rod length may be used. • Ground rods shall be placed a minimum of one rod length apart along the ground rings (ANSI T1.313-2003, figure 3(a)). • Ground rods shall not be separated from an adjacent ground rod along the ground ring by more than the sum of their respective lengths. (MIL-HDBK-419A). • The ground rods shall be installed in accordance with “Ground Rods” on page 4-11. • The ground rods shall be exothermically welded to the ground ring, or as otherwise allowed in “Bonding to the External Grounding (Earthing) Electrode System” on page 4-40. • The building ground ring shall be bonded to the tower ground ring using a minimum of two 35 mm 2 csa (#2 AWG) or coarser, bare, solid, tinned or un-tinned, copper conductors. See “External Building and Tower Ground Ring” on page 4-22 and Figure 4-4 on page 4-8. • The tower shall be grounded in accordance with “Tower Grounding (Earthing)” on page 4-50. • Determine if radial grounding conductors should be installed at the site, see “Radial (Counterpoise) Grounding Conductors” on page 4-24 4.7.7.1 GENERATORS EXTERNAL TO THE BUILDING Generators installed outside of the building, within 1.8 m (6 ft.) of the building, shall be bonded to the nearest practical location on the grounding (earthing) electrode system as shown in Figure 4-40 on page 4-60, using a 16 mm 2 csa (#6 AWG) or coarser, copper conductor (ANSI T1.334-2002, section 5.3.3). Grounding conductors routed below ground, or partially below ground, shall be a 35 mm 2 csa (#2 AWG) or coarser, bare, solid, tinned or un-tinned, copper conductor. External generator grounding shall comply with the following: • Bonding to the generator chassis shall be done in accordance with the manufacturer's requirements. 68P81089E50-B 9/1/05 4-59
- Page 101 and 102: STANDARDS AND GUIDELINES FOR COMMUN
- Page 103 and 104: STANDARDS AND GUIDELINES FOR COMMUN
- Page 105 and 106: STANDARDS AND GUIDELINES FOR COMMUN
- Page 107 and 108: STANDARDS AND GUIDELINES FOR COMMUN
- Page 109 and 110: STANDARDS AND GUIDELINES FOR COMMUN
- Page 111 and 112: STANDARDS AND GUIDELINES FOR COMMUN
- Page 113 and 114: STANDARDS AND GUIDELINES FOR COMMUN
- Page 115 and 116: STANDARDS AND GUIDELINES FOR COMMUN
- Page 117 and 118: STANDARDS AND GUIDELINES FOR COMMUN
- Page 119 and 120: STANDARDS AND GUIDELINES FOR COMMUN
- Page 121 and 122: STANDARDS AND GUIDELINES FOR COMMUN
- Page 123 and 124: STANDARDS AND GUIDELINES FOR COMMUN
- Page 125 and 126: STANDARDS AND GUIDELINES FOR COMMUN
- Page 127 and 128: STANDARDS AND GUIDELINES FOR COMMUN
- Page 129 and 130: STANDARDS AND GUIDELINES FOR COMMUN
- Page 131 and 132: STANDARDS AND GUIDELINES FOR COMMUN
- Page 133 and 134: STANDARDS AND GUIDELINES FOR COMMUN
- Page 135 and 136: STANDARDS AND GUIDELINES FOR COMMUN
- Page 137 and 138: STANDARDS AND GUIDELINES FOR COMMUN
- Page 139 and 140: STANDARDS AND GUIDELINES FOR COMMUN
- Page 141 and 142: STANDARDS AND GUIDELINES FOR COMMUN
- Page 143 and 144: STANDARDS AND GUIDELINES FOR COMMUN
- Page 145 and 146: STANDARDS AND GUIDELINES FOR COMMUN
- Page 147 and 148: STANDARDS AND GUIDELINES FOR COMMUN
- Page 149 and 150: STANDARDS AND GUIDELINES FOR COMMUN
- Page 151: STANDARDS AND GUIDELINES FOR COMMUN
- Page 155 and 156: STANDARDS AND GUIDELINES FOR COMMUN
- Page 157 and 158: STANDARDS AND GUIDELINES FOR COMMUN
- Page 159 and 160: STANDARDS AND GUIDELINES FOR COMMUN
- Page 161 and 162: STANDARDS AND GUIDELINES FOR COMMUN
- Page 163 and 164: STANDARDS AND GUIDELINES FOR COMMUN
- Page 165 and 166: STANDARDS AND GUIDELINES FOR COMMUN
- Page 167 and 168: STANDARDS AND GUIDELINES FOR COMMUN
- Page 169 and 170: STANDARDS AND GUIDELINES FOR COMMUN
- Page 171 and 172: STANDARDS AND GUIDELINES FOR COMMUN
- Page 173 and 174: STANDARDS AND GUIDELINES FOR COMMUN
- Page 175 and 176: STANDARDS AND GUIDELINES FOR COMMUN
- Page 177 and 178: STANDARDS AND GUIDELINES FOR COMMUN
- Page 179 and 180: STANDARDS AND GUIDELINES FOR COMMUN
- Page 181 and 182: STANDARDS AND GUIDELINES FOR COMMUN
- Page 183 and 184: STANDARDS AND GUIDELINES FOR COMMUN
- Page 185 and 186: STANDARDS AND GUIDELINES FOR COMMUN
- Page 187 and 188: STANDARDS AND GUIDELINES FOR COMMUN
- Page 189 and 190: STANDARDS AND GUIDELINES FOR COMMUN
- Page 191 and 192: STANDARDS AND GUIDELINES FOR COMMUN
- Page 193 and 194: STANDARDS AND GUIDELINES FOR COMMUN
- Page 195 and 196: CHAPTER 5 INTERNAL GROUNDING (EARTH
- Page 197 and 198: STANDARDS AND GUIDELINES FOR COMMUN
- Page 199 and 200: STANDARDS AND GUIDELINES FOR COMMUN
- Page 201 and 202: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />
4.7.7 DEDICATED COMMUNICATIONS BUILDING GROUNDING<br />
(EARTHING)<br />
All dedicated <strong>communication</strong>s buildings shall have a properly installed external grounding (earthing)<br />
electrode system. The grounding electrode system resistance shall meet the requirements of<br />
“Grounding (Earthing) Electrode System Resistance Requirements” on page 4-46.<br />
A typical site grounding electrode system layout is shown in Figure 4-4 on page 4-8. The building<br />
grounding electrode system requirements are listed below <strong>and</strong> shall also include any additional<br />
grounding electrode system components required to achieve the resistance requirements of the site. See<br />
“Minimum Site Grounding (Earthing) Requirements” on page 4-44.<br />
• Installation of concrete encased electrodes as part of new construction. See “Concrete-Encased<br />
Electrodes” on page 4-20.<br />
• The building shall be encircled by a ground ring installed in accordance with “External Building<br />
<strong>and</strong> Tower Ground Ring” on page 4-22.<br />
• The building ground ring shall have a ground rod installed near the external ground bus bar (EGB),<br />
at each corner of the shelter, <strong>and</strong> as follows:<br />
• If 2.4 m (8 ft.) ground rods are used, additional ground rods shall be installed as needed to<br />
reduce the distance between rods from 3 m to 4.6 m (10 to 15 ft.) (ANSI T1.334-2002).<br />
• If longer ground rods are used, a larger separation proportional to the increase in rod length<br />
may be used.<br />
• Ground rods shall be placed a minimum of one rod length apart along the ground rings (ANSI<br />
T1.313-2003, figure 3(a)).<br />
• Ground rods shall not be separated from an adjacent ground rod along the ground ring by more<br />
than the sum of their respective lengths. (MIL-HDBK-419A).<br />
• The ground rods shall be installed in accordance with “Ground Rods” on page 4-11.<br />
• The ground rods shall be exothermically welded to the ground ring, or as otherwise allowed in<br />
“Bonding to the External Grounding (Earthing) Electrode System” on page 4-40.<br />
• The building ground ring shall be bonded to the tower ground ring using a minimum of two<br />
35 mm 2 csa (#2 AWG) or coarser, bare, solid, tinned or un-tinned, copper conductors. See<br />
“External Building <strong>and</strong> Tower Ground Ring” on page 4-22 <strong>and</strong> Figure 4-4 on page 4-8.<br />
• The tower shall be grounded in accordance with “Tower Grounding (Earthing)” on page 4-50.<br />
• Determine if radial grounding conductors should be installed at the site, see “Radial (Counterpoise)<br />
Grounding Conductors” on page 4-24<br />
4.7.7.1 GENERATORS EXTERNAL TO THE BUILDING<br />
Generators installed outside of the building, within 1.8 m (6 ft.) of the building, shall be bonded to the<br />
nearest practical location on the grounding (earthing) electrode system as shown in Figure 4-40 on<br />
page 4-60, using a 16 mm 2 csa (#6 AWG) or coarser, copper conductor (ANSI T1.334-2002, section<br />
5.3.3). Grounding conductors routed below ground, or partially below ground, shall be a 35 mm 2 csa<br />
(#2 AWG) or coarser, bare, solid, tinned or un-tinned, copper conductor.<br />
External generator grounding shall comply with the following:<br />
• Bonding to the generator chassis shall be done in accordance with the manufacturer's requirements.<br />
68P81089E50-B 9/1/05 4-59