standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...

radioandtrunking.com
from radioandtrunking.com More from this publisher
24.12.2012 Views

MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS CHAPTER 4: EXTERNAL GROUNDING (EARTHING) GRADE COPPER GROUND ROD STEEL ANCHOR SHAFT 1 2 1. CORROSION FROM STEEL ANCHOR SHAFT TO COPPER GROUND ROD AND OTHER COPPER GROUNDING ELECTRODE SYSTEM COMPONENTS 2. CORROSION FROM STEEL ANCHOR SHAFT TO THE PORTION OF ANCHOR SHAFT ENCASED IN CONCRETE (STEEL ENCASED IN CONCRETE IS SIMILAR TO COPPER.) FIGURE 4-37 GUY ANCHOR GALVANIC CORROSION EXAMPLE • All guy wires at a guy anchor point shall bond to the ground rod (ANSI T1.313-2003, section 10.3.1, and ANSI/TIA/EIA-222-F-R2003) using a grounding conductor of 35 mm2 csa (#2 AWG) or coarser, bare, solid, tinned copper conductor. Do not use un-tinned wire. • The grounding conductor shall be connected to each guy wire using stainless steel or other approved clamps. Each connection shall be coated with a listed conductive anti-oxidant compound. 4-56 68P81089E50-B 9/1/05

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS CAUTION Do not attempt to exothermically weld to tower guy wires. • The grounding conductor shall be connected to the guy wires above the turnbuckles (see Figure 4-38). • The grounding conductor shall maintain a continuous vertical drop from the guy wire attachment point to the grounding electrode. FIGURE 4-38 GUY ANCHOR POINT GROUNDING FOR EXISTING CONSTRUCTION 4.7.6.2.2 CATHODIC PROTECTION Additional corrosion control can be obtained through the use of Cathodic Protection. See MIL-HDBK- 419A Volume I, section 2.10 and TIA/EIA-222-F-R2003, section 4.4 for additional information. Cathodic protection should only be installed under the advice of a licensed professional engineer. WARNING GUY WIRE CLAMPS 35 mm 2 CSA (#2 AWG) TINNED COPPER GROUNDING CONDUCTOR GRADE 610 mm (2 FT) MINIMUM CONCRETE ANCHOR GALVANIZED GROUND ROD 2.4 M (8 FT) MINIMUM ANCHOR SHAFT SURROUNDED BY 152 mm (6 IN.) OF GRAVEL Any type of corrosion control installation techniques does not eliminate the need for proper monitoring and maintenance over the life of the structure (TIA/EIA-222-F-R2003, section 4). 68P81089E50-B 9/1/05 4-57

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />

CAUTION<br />

Do not attempt to exothermically weld to tower guy wires.<br />

• The grounding conductor shall be connected to the guy wires above the turnbuckles (see<br />

Figure 4-38).<br />

• The grounding conductor shall maintain a continuous vertical drop from the guy wire<br />

attachment point to the grounding electrode.<br />

FIGURE 4-38 GUY ANCHOR POINT GROUNDING FOR EXISTING CONSTRUCTION<br />

4.7.6.2.2 CATHODIC PROTECTION<br />

Additional corrosion control can be obtained through the use of Cathodic Protection. See MIL-HDBK-<br />

419A Volume I, section 2.10 <strong>and</strong> TIA/EIA-222-F-R2003, section 4.4 <strong>for</strong> additional in<strong>for</strong>mation.<br />

Cathodic protection should only be installed under the advice of a licensed professional engineer.<br />

WARNING<br />

GUY WIRE<br />

CLAMPS<br />

35 mm 2 CSA (#2 AWG)<br />

TINNED COPPER<br />

GROUNDING CONDUCTOR<br />

GRADE<br />

610 mm<br />

(2 FT)<br />

MINIMUM<br />

CONCRETE ANCHOR<br />

GALVANIZED GROUND ROD<br />

2.4 M (8 FT) MINIMUM<br />

ANCHOR SHAFT<br />

SURROUNDED BY<br />

152 mm (6 IN.) OF<br />

GRAVEL<br />

Any type of corrosion control installation techniques does not eliminate the need <strong>for</strong><br />

proper monitoring <strong>and</strong> maintenance over the life of the structure (TIA/EIA-222-F-R2003,<br />

section 4).<br />

68P81089E50-B 9/1/05 4-57

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!