MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

4.7.6.2.1 GUY ANCHOR POINTS<br />

Grounding (earthing) guy anchor points requires special attention due to the possibility of galvanic<br />

corrosion damage to the anchor points. Although various methods <strong>for</strong> grounding guy anchor points are<br />

possible, any variation from the requirements <strong>and</strong> <strong>guidelines</strong> in this section shall be designed by a<br />

licensed professional engineer. Guy wire anchors shall minimally be grounded as outlined in the<br />

following sections.<br />

New Construction:<br />

• The guy anchor shall not be permitted to make direct contact with soil by being encased in<br />

rein<strong>for</strong>ced concrete over the entire embedded length of the anchor. The concrete encasement shall<br />

extend a minimum of 152 mm (6 in.) above grade.<br />

NOTE: Encasing the anchor in rein<strong>for</strong>ced concrete over the entire embedded length of the anchor helps prevent<br />

galvanic corrosion from the guy anchor to copper components of the grounding electrode system.<br />

Galvanized steel encased in concrete has a similar potential to that of copper (see “Miscellaneous<br />

General In<strong>for</strong>mation” on page 4-38). Additionally, encasing the anchor in rein<strong>for</strong>ced concrete over the<br />

entire embedded length of the anchor will help prevent the galvanic corrosion that would otherwise<br />

exist from the portion of the anchor in direct contact with soil to the portion encased in concrete.<br />

35 mm 2<br />

CSA (#2 AWG)<br />

OR COARSER TINNED COPPER<br />

GROUNDING CONDUCTOR<br />

COPPER GROUND ROD<br />

2.4 M (8 FT.) MINIMUM<br />

610 mm<br />

(2 FT.)<br />

MINIMUM<br />

GUY WIRE<br />

CLAMPS<br />

CONCRETE ANCHOR<br />

152 mm<br />

(6 IN.)<br />

MINIMUM<br />

GRADE<br />

CONCRETE ANCHOR SIZED ACCORDING TO PROFESSIONAL ENGINEER<br />

FIGURE 4-36 GUY ANCHOR POINT GROUNDING FOR NEW CONSTRUCTION<br />

4-54 68P81089E50-B 9/1/05<br />

}