MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

GROUNDING CONDUCTOR<br />

3 m<br />

(10 ft.)<br />

610 mm<br />

(2 ft)<br />

2.4 m<br />

(8 ft.)<br />

FIGURE 4-32 TYPICAL SINGLE GROUNDING ELECTRODE INSTALLATION<br />

4.7.6 TOWER GROUNDING (EARTHING)<br />

An external grounding (earthing) electrode system <strong>for</strong> a <strong>communication</strong>s tower is required to disperse<br />

lightning energy to earth be<strong>for</strong>e it is able to enter the associated <strong>communication</strong>s structure (or<br />

enclosure). Although is impossible to prevent all lightning energy from entering the <strong>communication</strong>s<br />

structure (or enclosure), the majority of the lightning energy can be controlled <strong>and</strong> diverted to earth<br />

(ANSI T1.313-2003 <strong>and</strong> ANSI T1.334-2002). Antenna masts <strong>and</strong> metal support structures shall be<br />

grounded (NFPA 70-2005, Article 810.15).<br />

IMPORTANT: For towers installed at high lightning prone geographical areas or <strong>sites</strong> normally<br />

occupied (such as 911 dispatch centers), radial grounding conductors should be employed to improve<br />

equalization of the grounding electrode system (ANSI T1.334-2002, section 5.4). See “Radial<br />

(Counterpoise) Grounding Conductors” on page 4-24. This is recommended even if the grounding<br />

electrode system resistance requirement is met without the use of radial grounding conductors.<br />

Towers can be classified into three basic categories (ANSI T1.334-2002, section 6.3):<br />

• Self-Supporting Towers (including monopoles)<br />

• Guyed Towers<br />

• Wooden Structures (poles)<br />

GROUNDING CONDUCTOR<br />

RECOMMENDED DEPTH MINIMUM DEPTH<br />

TOP OF ROD JUST<br />

BELOW SOIL<br />

SURFACE<br />

4-50 68P81089E50-B 9/1/05<br />

2.4 m<br />

(8 ft.)