STANDARDS AND GUIDELINES FOR COMMUNICATION SITES MINIMUM SITE GROUNDING (EARTHING) REQUIREMENTS<br />

NOTE: It is recommended to use two grounding electrodes as the minimum installation, even if 25 ohms is<br />

achieved with a single grounding electrode.<br />

Type “A” <strong>sites</strong> typically have the following characteristics:<br />

• No tower associated with the site<br />

• Non-critical installation<br />

• Not part of a larger system infrastructure<br />

• Single control station<br />

• RF alarm/reporting site<br />

• Small telemetry cabinet utilizing an existing utility pole to support the antenna<br />

• Single voting receiver site<br />

• May be located in a commercial office or residence<br />

4.7.4.2 TYPE “B” SITES - STANDARD DUTY<br />

Type “B” <strong>sites</strong> shall have a grounding (earthing) electrode system resistance design goal as low as<br />

practical <strong>and</strong> not over 10 ohms (AS 3516.2-1998, BS 6651:1999, FAA STD 019d-2002, MIL-HDBK-<br />

419A, <strong>and</strong> MIL-STD-188-124A); Motorola recommends a design goal of 5 ohms or less (also see the<br />

International Association of Electrical Inspectors publication, “Soares Book on Grounding <strong>and</strong><br />

Bonding” - 9th Edition, Appendix B <strong>and</strong> the United States National Weather Service Manual 30-4106-<br />

2004, “Lightning Protection, Grounding, Bonding, Shielding, <strong>and</strong> Surge Protection Requirements”). If<br />

the design goal of 10 ohms (or recommended 5 ohms) cannot be achieved with the minimum accepted<br />

grounding electrode system, reasonable ef<strong>for</strong>ts shall be made to achieve the design goal using<br />

supplemental grounding techniques. The supplemental grounding techniques are described in<br />

“Supplemental Grounding (Earthing)” on page 4-48.<br />

Type “B” <strong>sites</strong> typically have the following characteristics:<br />

• A tower is associated with the site<br />

• 911 dispatch center<br />

• Communications dispatch center<br />

• Base station <strong>and</strong>/or repeater site<br />

• Tele<strong>communication</strong> repeater equipment is installed, such as cellular, PCS, or wide-area repeater<br />

site<br />

• Large installation or multiple systems, such as telephone or electronic switches, LANs/WANs, <strong>and</strong><br />

Mobile Switching Offices (MSO) are installed<br />

• Critical public safety or military installation<br />

68P81089E50-B 9/1/05 4-47