BONDING TO THE EXTERNAL GROUNDING (EARTHING) ELECTRODE SYSTEM CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

4.6 BONDING TO THE EXTERNAL GROUNDING (EARTHING)<br />

ELECTRODE SYSTEM<br />

4.6.1 REQUIREMENTS<br />

All below-grade grounding (earthing) electrode system connections shall be joined using exothermic<br />

welding or listed irreversible high-compression fittings compressed to a minimum of 13.3 tonnes<br />

(12 tons) of pressure, or as otherwise required by the specific component manufacturer (ANSI T1.313-<br />

2003, figure 3(a)). Manufacturer requirements shall be followed <strong>for</strong> all connections. Connectors <strong>and</strong><br />

fitting used shall be listed <strong>for</strong> the purpose, <strong>for</strong> the type of conductor, <strong>and</strong> <strong>for</strong> the size <strong>and</strong> number of<br />

conductors used.<br />

All above grade grounding electrode system connections (such as grounding electrode conductor<br />

connection to ground bus bars <strong>and</strong> tower legs) shall be joined using exothermic welding, or listed<br />

irreversible high-compression fittings compressed to a minimum of 13.3 tonnes (12 tons) of pressure, or<br />

as otherwise required by the specific component manufacturer (ANSI T1.313-2003, figure 3(a)).<br />

All above grade bonding connections (such as bonding to ancillary equipment, or bonding coaxial<br />

ground kits to bus bars) shall be joined using exothermic welding, listed lugs, listed pressure<br />

connectors, listed clamps, or other listed means required by the specific component manufacturer.<br />

Connecting hardware shall be designed <strong>for</strong> the purpose, <strong>for</strong> the type of conductor, <strong>and</strong> <strong>for</strong> the size <strong>and</strong><br />

number of conductors used. All mechanical connections shall be coated with a listed conductive antioxidant<br />

compound. The anti-oxidant compound shall be liberally applied between the two metals (see<br />

Figure 4-27)(NFPA 70-2005, Article 250.70).<br />

BOLT GROUND<br />

LUG<br />

NUT<br />

LOCKWASHER<br />

GROUND BUS BAR<br />

OR EQUIPMENT SURFACE<br />

METALLIC BONDING<br />

SURFACE<br />

GROUND LUG<br />

FIGURE 4-27 PROPER LOCATION OF WASHER WHEN CONNECTING GROUNDING LUG<br />

REMOVE PAINT (IF PRESENT)<br />

AND APPLY ANTIOXIDANT<br />

COMPOUND<br />

LOCKWASHER<br />

NOTE: In some instances, exothermic welding may not be possible or may be prohibited by the specific<br />

component manufacturer (such as towers or fences); in these cases, other suitable means <strong>for</strong> bonding is<br />

allowed.<br />

4-40 68P81089E50-B 9/1/05