GROUNDING (EARTHING) ELECTRODE SYSTEM COMPONENT AND INSTALLATION REQUIREMENTS CHAPTER 4: EXTERNAL GROUNDING (EARTHING)<br />

4.4.2.3 PROTECTING AND SECURING GROUNDING (EARTHING) CONDUCTORS<br />

Above ground external grounding (earthing) conductors, including straps, are exposed to movement by<br />

wind <strong>and</strong> other physical <strong>for</strong>ces that can lead to damage or breakage over time. The following<br />

requirements shall apply when installing grounding conductors:<br />

• Grounding conductors shall be protected where exposed to physical damage (NFPA 70-2005,<br />

Articles 250.64, 800.100, 810.20, 820.100; <strong>and</strong> NFPA 780-2004, section 4.9.11).<br />

• Grounding conductors exposed to physical damage shall be protected <strong>for</strong> a minimum distance of<br />

1.8 m (6 ft.) above grade level (NFPA 780-2004, section 4.9.11.2). Such areas may include, but are<br />

not limited to, runways, driveways, school playgrounds, cattle yards, public walks (NFPA 780-<br />

2004, section 4.9.11).<br />

• Metallic guards <strong>and</strong>/or conduits used to protect grounding conductors shall be bonded to the<br />

grounding conductor at both ends (NFPA 70-2005, Article 250.64 <strong>and</strong> NFPA 780-2004, section<br />

4.9.11.1).<br />

• The grounding conductor or its enclosure shall be securely fastened to the surface on which it is<br />

carried (NFPA 70-2005, Articles 250.64 <strong>and</strong> 810.21; <strong>and</strong> NFPA 780-2004, section 4.10).<br />

• Grounding conductors shall be secured using appropriate hardware intended <strong>for</strong> the purpose.<br />

• When metallic fasteners are used on bare grounding conductors, fasteners of the same material<br />

shall be used, or approved bonding techniques shall be observed <strong>for</strong> the connection of dissimilar<br />

metals. See “Dissimilar Metals <strong>and</strong> Corrosion Control” on page 4-34. See NFPA 780-2004, section<br />

4.10.2 <strong>for</strong> additional in<strong>for</strong>mation.<br />

• Above ground grounding conductors shall be securely fastened at intervals not exceeding 91 cm<br />

(3 ft.) where practical. (ANSI T1.334-2002, section 8.3 <strong>and</strong> NFPA 780-2004, Section 4.10)<br />

4.4.3 EXTERNAL GROUND BUS BAR<br />

The purpose of the external ground bus bar (EGB) is to provide a convenient grounding (earthing)<br />

termination point <strong>for</strong> antenna transmission lines (coaxial cables) <strong>and</strong> other cables prior to their entry<br />

into a building or shelter (ANSI T1.313-2003). Antenna transmission lines <strong>and</strong> other <strong>communication</strong>s<br />

cables with metallic sheaths shall be grounded as close as practical to their point of entry into the<br />

building or shelter (NFPA 70-2005, articles 770.93, 800.100, 810.20, 820.93, <strong>and</strong> 820.100).<br />

Requirements <strong>for</strong> external ground bus bars, when used, are listed below:<br />

• The EGB shall be constructed <strong>and</strong> minimally sized in accordance with Table 4-3 on page 4-32,<br />

ensuring the ground bus bar is large enough to accommodate all transmission lines <strong>and</strong> other<br />

grounding connections.<br />

• The EGB shall be designed <strong>for</strong> the purpose of grounding <strong>and</strong> should be UL listed,<br />

• The EGB shall be installed at the point where the antenna transmission lines <strong>and</strong> other<br />

<strong>communication</strong>s cables enter the building or shelter.<br />

• The EGB shall be connected directly to the grounding electrode system using a downward run of<br />

35 mm2 csa (#2 AWG) or coarser, bare, solid or str<strong>and</strong>ed, tinned or un-tinned, copper conductor; it<br />

is recommended to use a larger conductor, such as 120 mm 2 (#4/0 AWG) (United States National<br />

Weather Service Manual 30-4106-2004, “Lightning Protection, Grounding, Bonding, Shielding,<br />

<strong>and</strong> Surge Protection Requirements”). See Figure 4-23. The grounding conductor shall be installed<br />

in a direct manner with no sharp bends or narrow loops. (See “Bending <strong>And</strong> Routing Grounding<br />

(Earthing) Conductors” on page 4-29.)<br />