24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) ELECTRODE SYSTEM COMPONENT AND INSTALLATION<br />

REQUIREMENTS<br />

• Grounding electrode conductors shall be installed in one continuous length without a splice or<br />

joint, unless spliced using irreversible compression-type connectors listed <strong>for</strong> the purpose or by<br />

exothermic welding (NFPA 70-2005, Article 250.64). See “Bonding Methods” on page 4-41 <strong>for</strong><br />

additional in<strong>for</strong>mation.<br />

• Above-ground conductors used <strong>for</strong> bonding individual metallic objects shall be 16 mm2 csa (#6<br />

AWG) or coarser, tinned or un-tinned, copper conductors (ANSI T1.334, section 5.3.3). See<br />

“Metallic Objects Requiring Bonding” on page 4-67 <strong>for</strong> additional in<strong>for</strong>mation.<br />

• Above-ground conductors used <strong>for</strong> bonding multiple metallic objects (used as a ground bus<br />

conductor) shall be 35 mm2 csa (#2 AWG) or coarser, tinned or un-tinned, copper conductors. See<br />

“Metallic Objects Requiring Bonding” on page 4-67.<br />

• Above-ground bonding conductors should be jacketed, whenever practical (ANSI T1.334-2002,<br />

section 5.1).<br />

• Solid straps or bars may be used as long as the cross-sectional area equals or exceeds that of the<br />

specified grounding conductor.<br />

WARNING<br />

The AC power system grounding conductors shall be sized appropriately <strong>for</strong> the<br />

electrical service <strong>and</strong> shall be approved by the authority having jurisdiction.<br />

4.4.2.2 BENDING AND ROUTING GROUNDING (EARTHING) CONDUCTORS<br />

Grounding (earthing) conductors shall be run in a direct manner with no sharp bends or narrow loops<br />

(ANSI T1.313-2003, section 11.3, <strong>and</strong> ANSI T1.334-2002, section 13.4). Sharp bends <strong>and</strong>/or narrow<br />

loops increase the impedance <strong>and</strong> may produce flash points (also see NFPA 780-2004, section 4.9.5).<br />

The following requirements apply when installing grounding system conductors:<br />

• Sharp bends shall be avoided (ANSI T1.334-2002, section 13.4).<br />

• Grounding conductors shall be run as short, straight, <strong>and</strong> smoothly as possible, with the fewest<br />

possible number of bends <strong>and</strong> curves (ANSI T1.313-2003, section 11.3; ANSI T1.334-2002,<br />

section 13.4; <strong>and</strong> NFPA 70-2005, Articles 800.100, 810.21, <strong>and</strong> 820.100).<br />

• A minimum bending radius of 203 mm (8 in.) shall be maintained, applicable to grounding<br />

conductors of all sizes (ANSI T1.313-2003, section 11.3; MIL-STD-188-124B; <strong>and</strong> NFPA 780-<br />

2004, section 4.9.5). A diagonal run is preferable to a bend even though it does not follow the<br />

contour or run parallel to the supporting structure. See Figure 4-22.<br />

• All bends <strong>and</strong> curves shall be made toward the ground location (grounding electrode system or<br />

ground bar).<br />

Radius<br />

The radius of any bend shall not<br />

be less than 203 mm (8 in.)<br />

90 degrees<br />

minimum<br />

The angle of any bend shall not<br />

be less than 90 degrees.<br />

FIGURE 4-22 MINIMUM BENDING RADIUS FOR GROUNDING CONDUCTORS<br />

68P81089E50-B 9/1/05 4-29

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!