STANDARDS AND GUIDELINES FOR COMMUNICATION SITES GROUNDING (EARTHING) ELECTRODE SYSTEM COMPONENT AND INSTALLATION<br />

REQUIREMENTS<br />

• Within the first 152 mm (6 in.) from the ground rod, 52% of the total resistance to earth is achieved.<br />

• The area immediately around a ground rod is the most important <strong>for</strong> reducing its resistance to earth.<br />

See “Grounding (Earthing) Electrode Encasement Materials” on page 4-27 <strong>for</strong> in<strong>for</strong>mation on<br />

reducing resistance.<br />

• In high resistivity soil areas, decreasing the soil resistance in this area is useful in improving<br />

the effectiveness of the grounding electrode system.<br />

• In porous soil areas, decreasing the contact resistance with the ground rod in this area is useful<br />

in improving the effectiveness of the grounding electrode system.<br />

Unless specified elsewhere in this chapter, ground rods should be installed apart from one another by<br />

the sum of their respective lengths, so their spheres of influence do not overlap (See Figure 4-6). This is<br />

especially important when only a small number of ground rods are installed, such as around tower<br />

ground rings.<br />

NOTE: In a given area, more ground rods installed closer together (such as one length apart from one another)<br />

will achieve a lower resistance to earth than fewer rods installed further apart (such as twice the length<br />

apart from one another). For example, five 3 m (10 ft.) ground rods installed 6.1 m (20 ft.) apart in an<br />

24.4 m (80 ft.) straight line will achieve a resistance to earth of 7.8 ohms (assuming 10,000 ohm-cm<br />

soil). Nine 3 m (10 ft.) ground rods installed 3 m (10 ft.) apart in the same 24.4 m (80 ft.) straight line<br />

will achieve a resistance to earth of 5.7 ohms.<br />

4.4.1.2 GROUND RODS<br />

Typical ground rods are shown in Figure 4-7. Requirements <strong>for</strong> ground rods are listed below. See IEEE<br />

STD 142-1991, section 4.3.1 <strong>and</strong> UL 467-2004 <strong>for</strong> additional in<strong>for</strong>mation.<br />

FIGURE 4-7 TYPICAL GROUND RODS<br />

4.4.1.2.1 GROUND ROD SPECIFICATIONS<br />

• Ground rods shall be UL listed (or equivalent).<br />

• Ground rods shall be constructed of copper-clad steel, solid copper, hot-dipped galvanized steel, or<br />

stainless steel (ANSI-J-STD-607-A-2002, section C.4.3, <strong>and</strong> ANSI T1.334-2002, section 5.3.2).<br />

See NFPA 70-2005, Article 250.52 <strong>and</strong> UL 467-2004, section 9.2.1 <strong>for</strong> additional in<strong>for</strong>mation.<br />

68P81089E50-B 9/1/05 4-11