4.2 - VSL
4.2 - VSL
4.2 - VSL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Figure 41: Possible tendon arrangements<br />
Under this loading case, the slab is stressed<br />
only by centric compressive stress. In regard<br />
to punching shear, it may be advantageous<br />
to position more than 50 % of the tendons<br />
over the columns.<br />
In the most commonly encountered<br />
cases, the tendon arrangement illustrated<br />
in Fig. 41 (d), with half the tendons in each<br />
direction uniformly distributed in the span<br />
and half concentrated over the columns,<br />
provides the optimum solution in respect<br />
of both design and economy.<br />
5.1.2. Spacings<br />
The spacing of the tendons in the span<br />
should not exceed 6h, to ensure<br />
transmission of point loads. Over the column,<br />
the clear spacing between tendons or strand<br />
bundles should be large enough to ensure<br />
proper compaction of the concrete and allow<br />
sufficient room for the top ordinary<br />
reinforcement. Directly above the column,<br />
the spacing of the tendons should be<br />
adapted to the distribution of the<br />
reinforcement.<br />
In the region of the anchorages, the spacing<br />
between tendons or strand bundles must be<br />
chosen in accordance with the dimensions of<br />
the anchorages. For this reason also, the<br />
strand bundles themselves are splayed out,<br />
and the monostrands individually anchored.<br />
14<br />
5.1.3. Radii of curvature<br />
For the load-relieving effect of the vertical<br />
component of the prestressing forces over<br />
the column to be fully utilized, the point of<br />
inflection of the tendons or bundles should<br />
be at a distance d s /2 from the column edge<br />
(see Fig. 30). This may require that the<br />
minimum admissible radius of curvature be<br />
used in the column region. The extreme fibre<br />
stresses in the prestressing steel must<br />
remain below the yield strength under these<br />
conditions. By considering the natural<br />
stiffness of the strands and the admissible<br />
extreme fibre stresses, this gives a minimum<br />
radius of curvature for practical use of<br />
r = 2.50 m. This value is valid for strands of<br />
nominal diameter 13 mm (0.5") and 15 mm<br />
(0.6").<br />
Table III - Required cover of prestressing<br />
steel by concrete (in mm) as a function of<br />
conditions of exposure and concrete grade<br />
1) for example, completely protected against<br />
weather, or aggressive conditions, except for<br />
brief period of exposure to normal weather<br />
conditions during construction.<br />
2) for example, sheltered from severe rain or<br />
against freezing while saturated with water,<br />
buried concrete and concrete continuously under water.<br />
3) for example, exposed to driving rain, alternate<br />
wetting and drying and to freezing while wet,<br />
subject to heavy condensation or corrosive fumes.<br />
5.1.4. Concrete cover<br />
To ensure long-term performance, the<br />
prestressing steel must have adequate<br />
concrete cover. Appropriate values are<br />
usually laid down by the relevant national<br />
standards. For those cases where such<br />
information does not exist, the requirements<br />
of the CEB/FI P model code [39] are given in<br />
Table I I I.<br />
The minimum concrete cover can also be<br />
influenced by the requirements of fire<br />
resistance. Knowledge obtained from<br />
investigations of fire resistance has led to<br />
recommendations on minimum concrete<br />
cover for the post-tensioning steel, as can be<br />
seen from Table IV. The values stated should<br />
be regarded as guidelines, which can vary<br />
according to the standards of the various<br />
countries.<br />
For grouted tendons with round ducts the<br />
cover can be calculated to the lowest or<br />
highest strand respectively.<br />
5.2. Joints<br />
The use of post-tensioned concrete and, in<br />
particular, of concrete with unbonded<br />
tendons necessitates a rethinking of some<br />
long accepted design principles. A question<br />
that very often arises in building design is the<br />
arrangement of joints in the slabs, in the<br />
walls and between slabs and walls.<br />
Unfortunately, no general answer can be<br />
given to this question since there are certain<br />
factors in favour of and certain factors<br />
against joints. Two aspects have to be<br />
considered here:<br />
Table IV - Minimum concrete cover for the post-tensioning steel (in mm) in respect of the fire<br />
resistance period required