COMPETENCE IN

ELECTRICAL SAFETY

FOR ELECTRICAL

SAFETY OFFICERS

Ready Guide to some

Frequently Asked

Questions


25,000 REASONS

AND MORE TO CELEBRATE

We are super proud to share our happiness

with you in having crossed 25,000 days in

Electrical Safety Engineering and Consulting

Services for our 500+ global customers across

42 sectors.


CONTENTS

Arc Flash

Batteries

Breakers

Cables

CEA MSES Requirements

Earthing & Flame Proof Equipments

General Questions

Lightning

LOTO

Measuring Instruments

Portable Equipments

PPE

Static Electricity

Transformers

4

12

14

15

17

24

26

30

30

30

31

31

33

33


ARC

FLASH


ARC FLASH

1

In what condition does an Arc flash happen? What are the precautionary measures to be taken

in order to avoid an arc flash?

Arc flash can happen when doing Energized Electrical works or when working around exposed

Energized conductor / circuit part.

Mitigation of Arc Flash hazards can be achieved through hierarchy of risk control methods such as

Elimination (avoiding live work), Substitution (operating from remote), Engineering control

methodologies (quick action devices), Administrative control & PPEs.

2

What are the Engineering controls for Arc flash hazards?

Engineering Controls include, but not limited to

Conducting Arc flash risk assessment, quantifying the incident energy levels and reducing it

using protection mechanism supporting with active arc detection devices

Guarding of Energized conductors to prevent Arc flash hazards.

Installing Infrared inspection ports to do Thermography

Remote racking of circuit breakers

The way to protect us from Arc flash hazards is either wearing of PPE or implementing Engineering

controls.

Both methods are practiced to reduce risk from Arc flash hazards.

Wearing of Suitable arc rated PPE is the least line of defense.

Engineering control is considered as effective method to reduce risk as it is applied to the source of

possible injury and they are less likely to be affected by human error.

3

How to calculate Incident Energy level for 33kV volt level & SC amps of 50kA?

Presently, As per IEEE standard 1584 – 2018 for Arc flash calculation available up to 15kV only.

Ralph Lee's theoretical calculation method can be used in this scenario.

Ralph Lee's method is more conservative than the practical estimation.


4

Is there any instrument to detect an arc flash?

Yes. Arc flash sensors are available.

Arc flash light sensor in combination with fast over current protection for feeder Arc flash

protection.

Arc Fault Detection Device (AFDD) are available for circuit protection"

5

6

7

Is an Arc flash required for 415V Panels?

Yes. It is required for 415V MV Panels.

Is Arc flash applicable for MCC and DBS?

Yes. Generally It is applicable for both MCC and 3 Phase Dbs.

What should be the frequency of the arc flash analysis? As per standard it should be 5 years,

however the physical property of the electrical panels never change which is measured during

the analysis. Also in NFPA 70E, there is no explanation as to why an Incident Energy analysis

needs to be done once in 5 years. Can you elaborate?

It is understood that due to any of the below reasons there may be a need to do the analysis.

There may be certain changes in a distribution system due to expansions / modifications (or)

There may be changes in the grid fault level due to increasing power demand (or)

There may be changes in the standards governing calculation of incident energy levels.

8

How to calculate Incident energy?

It needs to be calculated based on IEEE 1584 - 2018 standard.

Incident energy depends on factors such as short circuit level, time taken to isolate the circuit in

faulty conditions and working distance etc

ARC FLASH


ARC FLASH

9

Is Arc flash PPE required when panel doors are closed and restricted boundary is crossed?

Example: During meter reading from outside the panel.

For taking meter reading outside the panel, Arc flash PPE is not required as per NFPA 70 E table

130.5 ©.

Arc flash PPE is required only when live work activities like changing the components, trouble

shooting, altering the conditions or working around Exposed Energized conductor is performed

with doors and covers in open condition

10

11

Is Arc flash required for all live work and working near energized conductor?

Yes. Arc flash risk assessment & PPE is required for all live work activities and working around an

Energized conductor

Is working on test bench to test control and power circuits come under live work? Also, is Arc

flash assessment required for test bench work?

If there are no exposed energized conductors, it is not required to have Arc flash assessment.

If exposed energized conductors are present, Arc flash assessment is required.

12

Is Bus bar temperature monitoring of opening cable alleys with IR gun from a distance of 1M

considered as energized work or not?

For PCC & MCC panels (415VAC), Thermal imaging study done at a distance of 1mtr is NOT

considered as Energized work.

It can be noted that opening & closing of the door has a likelihood of Arc flash. Hence Arc flash PPE

needs to be worn during such activity.

13

Do we need to wear Arc flash rated clothes over our normal working clothes?

Yes. Arc rated PPE based on the incident energy level of the panel needs to be worn over the daily

wear while doing live work activity.


14

“Current measurement in cable alley using tong tester”. In this case, we are putting our hand

inside the cable alley. Will that be considered as “energized work”?

Yes. Work within Restricted approach boundary is considered as Energized work.

The work is considered as an activity having likelihood of Arc flash occurrence & hence Arc flash

PPE is to be worn.

15

Can we call “Energized work Permit” or “Energized work approval form”, as we have only three

types of permit (cold/ Hot and Spark Potential).

As per NFPA 70E, Energized Electrical Work Permit needs to be taken for live work activities.

16

Is troubleshooting in live 415V feeder considered as "Energized work"?

Yes. Work within Restricted approach boundary is considered as Energized work.

The work is considered as an activity having likelihood of Arc flash occurrence & hence Arc flash

PPE is to be worn.

17

Does Lockout Tag out activity come under live work?

Yes. It is considered as live work activity.

In MV panels, voltage testing will be a part of LOTO & in HV panel, removal & insertion of circuit

breaker needs to be done.

18

What is the condition to use Arc flash PPE? For example Breaker Panel ON / OFF Operation, live

line troubleshooting?

Operation of a circuit breaker (ON/OFF) does not require Arc flash PPE as long as you are confident

about the good healthiness/condition of the panel. If any maintenance has been done on the

breakers/panels then wearing of PPE is recommended for even switching of CB is recommended as

per NFPA 70E – 2021.

Live line troubleshooting requires Arc flash PPE to be worn based on the Incident energy level

ARC FLASH


ARC FLASH

19

During troubleshooting of control circuit (230V AC or 110V DC) in 11KV SWGR panel, in

isolation condition, Which kind of Cat class PPE needs to be used?

Condition 1 - If the control supply is isolated, LOTO done and if there are NO exposed energized

conductor present within the work area, Arc flash PPE is not required

Condition 2 - If the control supply is isolated, LOTO done and if there are other exposed energized

conductors present within the work area, suitable Arc flash PPE is to be worn

Condition 3 - If the control supply is Energized and if it is >120V, suitable Arc flash PPE is to be

worn

20

Is Arc flash suit required during power change over from DG to Board power or Board power to

DG?

It is not required if the power changeover arrangement system is having

Suitable interlock between both the breakers to prevent paralleling

Does not require racking in of circuit breaker

Does not require getting exposed to Energized conductors

21

Is there any minimum energy level above which Arc flash boundary is required to be

mentioned?

Arc flash boundary to be mentioned for all panels & DBs irrespective of the Energy level. However,

body protection is required where incident energy level is >1.2 cal/cm2.

22

Safe working Distance is as per which standard?

NFPA 70 & 70E

23

Is permanent boundary marking on floor required?

Generally it is recommended. Floor boundary marking is required for cautioning the operating

personnel and it is not a mandatory requirement.


24

25

In a PCC, Arc flash boundary marking needs to be done according to main EB breaker or

according to maximum Arc flash boundary of any feeder in that PCC?

Generally Arc flash boundary marking needs to be done based on the maximum arc flash boundary

distance for better safety

ARC flash sticker is required to paste at one location of main feeder or at each feeder?

Sticker not required for each feeder. It is meant for the panel. Max incident energy and PPE

requirement to be mentioned.

26

What is the distance required for red boundary and yellow boundary?

Red boundary - Restricted Approach boundary

Yellow boundary - Limited Approach boundary

(Colors of the boundaries are not defined in Standard). Both are known as shock protection

Boundaries.

Both are distance from the Exposed Energized conductor and are independent of each other.

These boundary distances for panels with different voltage level are given in NFPA 70E standards.

For example, a 415VAC MV panel will have

Restricted Approach Boundary - 300mm from Exposed Energized conductor

Limited Approach Boundary - 1000mm from Exposed Energized conductor

27

What is horizontal distance? (Working distance)

It is the distance between a person's chest area and a prospective Arc source.

28

Does Arc flash boundary need to be mentioned on small lighting panels / distribution boards?

Yes. If it is a 3-phase panel / DB, Arc flash boundary is to be mentioned.

29

Define qualified person?

One who has demonstrated skills and knowledge related to the construction and operation of

Electrical equipment and installations and has received safety training to identify the hazards and

reduce the associated risk

ARC FLASH


ARC FLASH

30

What is the panel thickness and material for minimizing Arc flash effects?

Panels are called arc rated switch gear (passive protection). Its thickness depends on voltage and

short circuit capacity. Types 1, TYPE 2, sub form A, B, C are available

31

What is the standard for panel thickness for various voltage levels?

IEC 62271-200

32

Is there any format to identify and include human error to find risk assessment?

Yes. It is available in NFPA 70E.

33

What is safety measure to be taken for a Thermography study to be carried out?

If the thermography is done outside of restricted approach boundary, Arc flash precautions are not

required.

If it needs access inside the restricted approach boundary, then shock protection and Arc flash

protection PPEs are required to be worn.

34

Is there any regulation or standard reference for people that should not sit in HT panel room?

Office facilities for functions not directly related to substation control should be housed in buildings

separate from the substation control building or in areas separated by fire-rated construction

provided in accordance with the separation provisions as per IEEE 979.

There is no explicit reference to restrict people sitting for related work activities.

35

Can we also use SMC sheets for insulation?

Yes. SMC sheet can be used as barrier to prevent direct contact with the Energized conductors.


BATTERIES


BATTERIES

1

What is the standard that should be followed for battery room with lead acid SMF battery

banks?

IEEE 1187 – IEEE Recommended Practice for Installation Design and Installation of Valve-

Regulated Lead-Acid Batteries for Stationary Applications

IEEE 1188 – IEEE Recommended Practice for Maintenance, Testing, and Replacement of Valve-

Regulated Lead-Acid (VRLA) Batteries for Stationary Applications

IEEE 1189 – IEEE Guide for Selection of Valve-Regulated Lead-Acid (VRLA) Batteries for Stationary

Applications

2

3

Please mention standards for PPE to be maintained in Battery room.

NFPA 70E & respective IEEE standards for each type of batteries.

Does VRLA batteries require ventilation arrangement?

Yes. VRLA battery room requires ventilation.

4

Should Battery Banks rack having Ni-Cd cells be earthed or not?

The metallic rack of the Ni-Cd battery bank needs to be earthed.

5

Is Hydrogen generated in Ni-Cd Battery? If so, rate of generation will be very less. So, is a H2

detector required or not?

Hydrogen will be generated in Ni-Cd batteries.

If the room & ventilation system are designed to limit Hydrogen accumulation to less than 2% of

total volume of the battery area and it is sufficient to prevent the formation of local pockets of

Hydrogen external to the battery, H2 detector is not required.


6

Should the Exhaust fan installed in Battery banks room be of a flameproof type or a safe area

type?

Generally If the battery room is meeting the natural and forced ventilation requirements of IEEE

standards, the room need not be considered as Hazardous location and it does not require

flameproof equipment.

7

We have 2000kVA UPS room with 120 dry batteries, is it sufficient to maintain the room by only

cooling or Can we do some extra activities by separating the batteries. Need your suggestions

Ventilation design & arrangement needs to be designed based on IEEE standards & manufacturer

recommendations.

BREAKERS

1

What should be the acceptable range for Dynamic contact resistance for CB?

It shall be as per Manufacturer specifications

BATTERIES


CABLES


CABLES

1

Cable laying depth is as per which standard?

As per IS 1255 - Code of Practice for Installation and Maintenance of Power Cables up to and

including 33kV Rating

2

3

What should be the distance between two cable markers for LT/HT Cables?

Cable route marker should be installed once in every 200mtr and at every turning.

Is it ok if I close cable entry to the plant with some kind of civil work?

Yes. Cable entry can be closed by civil work to the full thickness of the wall using material same as

the construction of the wall.

4

Is FR coating required on FRLS cable?

No. It is not required for FRLS cables as they have inherent properties of FR.

5

What should be the Insulation value of 11KV XLPE Cable?

Minimum 5 M is required for 11kV HT cable as per CEA MSES 2010 Regulation 33


CEA MSES

REQUIREMENTS

(Measures relating to Safety

and Electric Supply)


CEA MSES REQUIREMENTS

1

2

Do we consider the connected load to designate Electrical Safety Officer, irrespective of the

sector i.e. manufacturing or research?

Yes. For Every “Electrical Installation” having more than 250kW connected load, Electrical Safety

officer needs to be designated.

Is it only applicable for construction and commissioning time or applicable for running

operation?

It is applicable for running operation to designate Electrical Safety officer in Electrical Installations

having more than 250kW connected load.

3

I have a B.Tech and industrial safety certification and have 8 years experience in HSE field. Can

I become an Electrical safety officer?

No. Electrical Safety Officer shall possess a Degree / Diploma in Electrical Engineering with five and

ten years of experience in Operation & Maintenance of Electrical Installations respectively.

4

Who does a Electrical Safety Officer report to in a factory?

Electrical Safety Officer is not a separate position in a factory. They shall continue to do their

regular O&M activities. The Electrical Safety Officer is a responsibility to ensure the compliance of

CEA Regulatory requirements within the factory.

5

Can a C license holder become a chartered Electrical Safety Officer?

Yes. But the person shall possess B.E Electrical with 5 years of O&M experience or Diploma in

Electrical Engineering with 10 years of O&M Experience. The Chartered Electrical Safety Engineer

has to be Authorized by appropriate State Government through the selection procedure.

6

Can an Electrical Safety Officer himself do the self-certification without the help of Chartered

Electrical Safety Officer & submit the form to the Electrical Inspector?

Yes. Electrical Safety Officer can do Self Certification.

For regulation 43 requirements, recommended to take the support of Chartered Electrical Safety

Engineers to assist for Self-Certification of Electrical Installations.


7

Is it compulsory for an Electrical Safety Officer to take competency certificate? As in the plant

Operation and maintenance done by electrical supervisors? Please clarify.

Electrical Safety Officers are involved in testing and inspection of Electrical Installations which

requires competency certificate.

8

I'm have done B.Tech in Electronics and I have 10 years of experience. Can I become an

Electrical Safety Officer?

No. The person should possess Degree / Diploma in Electrical Engineering as per CEA 2010

regulation 5.

9

Test certification signing should be done by C-certificate holder or by Electrical Safety Officer?

Who can be SPOC for CEIG site visit - C-certificate Holder or Electrical Safety Officer?

Generally Electrical Safety Officer is the person responsible for getting the test certification & SPOC

for CEIG site visit.

10

If there is already a C license holder in a factory. Is an Electrical Safety Officer necessary in

addition?

The same C license holder if possess relevant experience can be designated as Electrical Safety

Officer. There is no requirement of additional person.

11

12

In Maharashtra, which is the appropriate department where we can apply for Electrical Safety

Officer certification?

Electrical Safety Officer is not a certification. It is a declaration to be given by the Organization to

the Electrical Inspectorate that a person is having required qualification and experience and hence

being designated as Electrical Safety officer for the Electrical Installations.

An Electrical Inspector inspects our premises every year. Do we have to submit the forms?

Yes. The Electrical Safety Officer has to inspect the installation and keep a record thereof in Form I,

II & III as the case may be. It can be submitted to the Inspector as and required by the electrical

inspector. He may visit irrespective of the forms submitted

CEA MSES


CEA MSES

13

What is the frequency for the self-certification? Form I, II and III.

Once in 5 years (or) as directed by the Electrical Inspector for self-certification. However, the

Electrical Safety Officer shall inspect the installation once in a year and keep a record thereof in

Form I, II & III as the case may be and submit records as and when required by the electrical safety

officer

14

Form I, II, III self-assessment copy needs to be kept with us or sent to the Electrical Inspector?

Form I, II, III shall be kept as a record and produced to Electrical Inspector when asked for. For

self-certification against CEA regulation 30 and 43, it has to be submitted to the electrical inspector

15

Is competency certificate a statutory requirement?

It is a statutory requirement as per Central Electricity Authority (CEA), Measures Relating to Safety

& Electric Supply Regulations 2010 to possess competency certificate for personnel involved in

O&M of Electrical Installations.

16

Is it mandatory to have Electrical supervisor license for all Electrical engineers working in an

Organization?

Any personnel designated to operate and carry out work on Electrical Lines & apparatus shall

possess Electrical License / certificate of competency / work permit as issued by the appropriate

State Government

17

If Engineers in an organization needs a License from statutory body, Can the organization itself

authorize them? Since all the contract employees should have Licenses.

Engineers shall obtain license from Appropriate State Government only which is termed as an

Authorization in regulatory context.

18

Is Electrical wireman / supervisory license required for every one like, Engineers, Electricians,

Contract workmen in an electrical maintenance team?

Yes. Persons designated for Operation and Maintenance of Electrical Installation require Electrical

license as provided by the State Government


19

If a person has good knowledge of Electrical system & has more than 10 years of experience but

does not have ITI certificate. Can he authorize an Electrical qualified person?

No. As per CEA MSES 2010, persons with required qualification and Experience are to be

designated for operation and maintenance of Electrical Installations.

20

If a person has Mechanical Qualification and has experience in Electrical Installation, is he

eligible for C Certificate?

No. Person should be qualified in Electrical domain for obtaining Electrical License

21

Is Interlock of Isolator with circuit breaker required for LV installation (415V)?

As per CEA MSES 2010, Interlock of Isolator with circuit breaker is required for 650V and above.

However it is a good practice to have interlocking for LV also

22

Does Rajasthan Governtment accept supervisory certificate from other states to work?

Rajasthan government recognizes supervisory certificate issued by other states to get exempted

from Examination. One has to apply for obtaining Supervisor competency certificate & Permit to

work as Supervisor to the State Government of Rajasthan.

23

We are not a Power generating company. Do we have to inform Electrical Inspector when the

Transformer fails?

Yes. Suppliers as well as consumers of Electricity have to report the failure of Transformers as

below.

Failures of Transformers and Reactors of 20MVA & 20MVAR and higher capacity shall be

reported to Central Electricity Authority (CEA) within 48 hours of occurrence.

The reasons for failure, measures taken to avoid recurrence of failure shall be sent to CEA within

one month of the occurrence.

CEA MSES


CEA MSES

24

Does CPP operator for plant operation require Power plant operator certificates?

Yes. Engineers, Supervisors & Technicians of Thermal Power plant (coal based, diesel engine based

& gas turbine based) shall be provided with trainings as prescribed in Schedule I of CEA MSES

2010 Regulation

25

What is Class A supervisor license in New Delhi?

It is Class I Certificate of Competency, issued for Electrical Engineers / Diploma holders with

relevant qualification & experience. They are entitled to works as Electrical Supervisors in New

Delhi.

26

Do Engineers and Electricians from Industries need to take training from external institutes

approved by CEA for compliance with Regulation?

Engineers & Electricians working in Industries are not required to take training from External

institutes.

Engineers, Supervisors & Technicians working in Thermal power plant, Hydro power plant,

Transmission & Distribution systems are required to undergo training as specified in CEA MSES

2010 Regulations.

27

28

What is the minimum number of wiremen & how many competency certificate holders are

required in a company?

The minimum manpower required in a company is not defined in any of the standards. However it

is recommended to ensure that all the O&M electrical persons are having valid license.

As per Regulation, is single electrician on site authorized to perform job (<=LV) (except height

work)? Or does he require another license holder to accompany him?

Regulation and standards did not address on lone worker hazards and requirements

29

Fire bucket is mandatory as per which Regulation?

Providing fire bucket is mandatory as per CEA MSES 2010 Regulation 27.


30

Which code speaks about 30, 300 milli amps RCCB?

RCCB of 30mA & 100mA is required as per CEA MSES 2010 Regulation 42 & IS 732 standards.

31

Why is the standard fence height 1.8m? Is there any code for that?

Fencing of 1.8mtr height is required as per CEA MSES 2010 Regulation 49.

The reason for 1.8mtr is not given explicitly. It is understood that the average height of Indian is

1.75mtr. Hence 1.8mtr is recommended to prevent intrusion & restrict accessibility.

32

What is the depth required for the stones in the switchyard?

Gravel depth in switchyard is 150mm.

Bottom 75mm layer shall be of 20mm dia gravels

Top 75mm layer shall be of 38mm dia gravels.

33

What is the significance of putting black stones in the switchyard instead of Cement Flooring?

The use of gravels in switchyard is to increase the foot resistance to the ground.

34

Is AED required in Electrical panel room? Which standard mentions this?

CEA MSES 2010 Regulation 28 requires Artificial Respirator to be placed in generating station /

substation / switching station. It does not mandate AED. However it is a good practice to keep AED

in plant premises.

35

For new installation of factory, Is Electrical safety audit needed?

Electrical Safety Audit can be done for the new installations to ensure design safety compliance &

whether Installation works are done as per Statutory & Standard Requirements.

CEA MSES


EARTHING &

FLAME PROOF

EQUIPMENTS


EARTHING

1

If power cable is Aluminum and earth conductor is copper, is there a thumb rule of keeping

same phase wire size?

No. If both the conductors are different, the conductor size needs to be calculated based on k1/k2

ratio factor.

k1 - k factor of power conductor

k2 - k factor of protective conductor

2

If motor casing is grounded is there any chance of getting indirect electric shock?

It depends on the grounding resistance of the motor and the person making indirect contact. That

is if the grounding resistance is too low (<1ohm) and if the person making indirect contact is

properly insulated (higher ground resistance) the possibility of Electric shock is low.

3

From which standard can Earthing cable size be selected?

IS 3043

FLAME PROOF EQUIPMENTS

1

What is the standard for FLP equipment maintenance?

IS/IEC 60079-17 - Explosive atmospheres, Part 17: Electrical installations inspection and

maintenance [ETD 22: Electrical Apparatus for Explosive Atmosphere]


GENERAL

QUESTIONS


GENERAL

1

2

What is the testing frequency of RCCB?

Good Practice is

Monthly - Functional Test by pressing the Test trip button

Yearly - Performance test using an RCD tester.

What is the method & testing frequency for RCBO?

Same as that of RCCB for testing Earth leakage protection

3

If ELCB is connected, should the Earthing conductor size be same as phase wire size? RCD will

disconnect within few millisecond, then why is the thick earth wire required?

As per IS 732 standards, RCCB is considered as Additional protection. The overcurrent protective

devices are the basic protection. For the basic protective device to operate, the earth conductor

shall be of adequate size.

4

What is the main difference between ELCB AND RCCB?

ELCB are voltage sensing and operating devices which measures the voltage of the protected

equipment and ground. If it exceeds 50V, it will disconnect the circuit.

RCCBs are current operated devices which measure the leakage current to ground and isolate

the circuit.

ELCBs are no longer available in the market /installed as it has certain disadvantages when

compared to RCCBs

5

Is it safe to use neutral as a control?

No. Only Phase should be used as control.

6

Is there any color code for names on feeders like yellow background and black letters?

There is no such color code standard for feeder identification. Only requirement is it has to be

painted.


7

Is MCB required to isolate Neutral also?

If the cross-sectional area of the neutral conductor is less than that of the line conductor, it is

necessary to provide overcurrent protection for the neutral conductor.

If the cross-sectional area of the neutral conductor is equal to the line conductor, and if the current

is not expected to exceed the line conductor current, overcurrent detection is NOT required for

Neutral.

8

Can you explain more on double insulation of portable tools?

Double insulation is achieved by 2 levels of insulation in the portable power tools.

First level is the basic insulation of the conductive parts

Second level is the plastic body construction

9

Do electrical rooms need to have fire rated doors? If yes, as per which standard?

Electrical Rooms shall be provided with fire rated door as per NBC 2016 standards.

It is understood that the doors shall be fire rated when the side it is communicating has the

potential of fire spread. If the outside of Electrical room is an open area, where fire spread cannot

happen, the door shall be of non-combustible material (metallic door) and need not be fire rated.

For MV panel room, NBC 2016 recommends to have fire rated doors.

10

If there is a building inside a Petrochemical complex, does it fall under NBC?

Yes. It is applicable for Petrochemical complex also.

11

Is the power quality test a mandatory under periodical inspection?

No. it is not mandatory under periodical inspection.

12

How to become NFPA authorized safety officer? Please give a few agencies name to attain

training and examination etc.

https://www.nfpa.org/Training-and-Events/Certification/Certification/Certified-Electrical-Safety-

Compliance-Professional

GENERAL


GENERAL

13

14

External painting of MCC panel should be done when panel is isolated or when it is in ON

condition

It is recommended to do painting when the panel is in isolated condition. The paint material being

flammable can result in fire / explosion.

What is the frequency for Thermography study?

Generally Once in a year. If more no. of failures/outages is noticed, the frequency can be increased.

15

What is the specification for dielectric floor?

As per manufacturer specifications and the voltage rating of the panel. Following parameters to be

considered based on voltage level

Weather resistance Dry coating film should pass 240hrs water immersion test.

Chemical resistance 5% H2SO4 - 48hrs Immersion 5% NaOH - 48hrs Immersion

Leakage current < 0.025mA (Third party test report required)

Insulation resistance at 500V >2.5x109 M Ohm (Third party test report required)

Break down Voltage in air >33KV For Class-A

System thickness 1.1-1.3mm for Class-A

Humidity resistance >5000 Hrs

Scratch Hardness >4.5Kg

16

What equipment should be used for working on live wires?

Meters with CAT III/IV rating as per the working panel (PCC, MCC, DB etc.)

Tools which are suitable for live working (generally indicated with double triangle symbol)

Shock protection PPEs


LIGHTNING

1

We are a car manufacturing plant, consuming power from grid at 132 KV line, is ESE Lightning

protection acceptable?

Early Emission type lightning protection is not accepted by NBC 2016 codes. Also, this type of

protection is not a part of IS/IEC standards. Hence, conventional lightning protection system needs

to be designed and installed as per IS/IEC 62305 standards.

LOTO

1

After LOTO is provided, do we need to earth the equipment? The person is working in pumps

alone and not in motor.

If the LOTO is made failsafe, i.e., there is no possibility of inadvertent energization, it is not required

to earth the motor when the work is done only on pump side and not on current carrying conductor

or near the current carrying conductor.

MEASURING INSTRUMENTS

1

What is minimum frequency for calibration of testing equipment like millimeters, insulation

tester?

Periodic calibration is required to be done once in a year for millimeters and Insulation testers.

2

What should be used for voltage measurement -single function meter? Is multi meter suitable?

Any hand held meter complying with CAT rating of IEC 61010 is suitable for voltage measurement.

3

Is FLP Multimeter available?

Yes. Intrinsically safe millimeters are available for use in Hazardous areas.

GENERAL


PORTABLE EQUIPMENTS

1

2

How to ensure the condition of double insulation is good in an old drilling machine

By doing visual Inspection to identify any physical damage

By measuring the insulation resistance between the phase lead & exposed conductive part of the

drilling machine

Can we use domestic sockets for power supply of two pin double insulated power tools?

Yes. Domestic sockets can be used in areas where dust and water ingress are not possible. Where

there is a possibility of dust / water ingress, weatherproof socket outlets can be used based on IP

rating.

3

is there any recommended maximum allowable length of cable from RCCB to tools, for

protection system effectiveness?

No. It shall be based on the leakage current of the cable network. Generally, for portable equipment,

cables up to 15mtr length are recommended

PPE

1

What is the lifespan of gloves or mat?

Gloves - if there is any physical damage noticed during field testing before / after use (or) if the

gloves fail the periodical testing (proof voltage testing)

Insulating mat - Life of mat is generally 10 to 15 years. It can be used as long as there are no

visual damages

2

How to test hand gloves yearly? Which type of test & Standard?

Air inflation test and dielectric test (proof voltage withstand test) are to be done annually.

Standards - IS 4770 & IEC 60903

3

Is third party testing of gloves mandatory?

Annual testing needs to be done. Air inflation test can be done internally using market available

inflators. Dielectric tests (for proof voltage / rated voltage) are done externally with vendors having

the measuring kit / setup.

GENERAL


4

Is there Class 0 category in hand gloves?

Yes. As per IEC 60903, Class 0 rating is available.

As per IS 4770, Type 1, 2, 3 & 4 gloves are available.

5

What is the rubber mat size above 66 KV?

Above 66kV, equipment will be in a switchyard (outdoor). Personnel safety is achieved, by earth

mesh / mat design, gravels, ensuring the Touch & Step potential within tolerable limit. Hence

Insulating mat is not required.

6

Is insulating paint advisable?

Yes. Insulating floors is acceptable by CEA MSES 2010 Regulation 19.

7

RCCB selection guideline is based on which standard?

IS 12640 / IEC 61008 standard.

8

Is it permitted to use a line tester in an industry?

Generally Line testers are permitted to be used in Industry. However usage of Line tester is not

safe. Hence it is recommended to use only non-contact voltage detectors/Portable millimeters to

prevent any direct contact.

10

What is the Rescue hook, discharge rod testing frequency and against which standard has it

been tested?

Specific to Earth discharge rod and shock rescue tool, there is no standard for defining

frequency of inspections.

If considering this equipment as live working tools, periodicity of inspection can be defined as

per manufacturer recommendations (IEC 61477).

Annual Inspection – Occasionally using tools & half yearly Inspection - for regular use tools is

preferred.

For live working tools used at <1kV, visual inspection is adequate. Regular Electrical testing is

not required

GENERAL


STATIC ELECTRICITY

1

How to measure static charge in a running line having pellets/powder? Also which instrument

should be used for static charge measurement?

It can be measured using Electrostatic Voltmeter

2

When was static electricity in Hydrocarbon industry adopted?

Static Electricity Indian Standard (IS 7689) was adopted in the year 1989.

3

What is the minimum size of equipment earth wire Cu / Al meant for static electricity

suppression

There is no minimum conductor size specified in standards. The conductor shall be mechanically

strong and the earthing resistance shall be <10 Ohm for metallic equipment.

TRANSFORMERS

1

Is Transformer oil drain pit compulsory for 1000 KVA?

Drain pit is required for Transformer having oil capacity >2000ltrs.

2

We have a 1000 KVA Transformer with 1350ltrs oil capacity. Do we require an Oil Pit?

No. Oil soak pit is required for Transformers having oil capacity >2000ltrs.

However, gravels shall be spread around the Transformer.

GENERAL


Audits,

Assurance & Compliance

Assessment

& Verification

Consulting &

Advisory Services

Digital based

Electrical Engineering

Capacity Building &