Sample <strong>Safety</strong>-Shutdown Programs 57<br />

Table 13 Output Parameters <strong>for</strong> SYS_SHUTDOWN Function Block in EX02_SHUTDOWN<br />

Parameter Description<br />

ALARM_REMOTE_ACCESS True if remote-host writes are enabled<br />

ALARM_RESPONSE_TIME True if actual scan time is greater than<br />

MAX_SCAN_TIME<br />

ALARM_DISABLED_POINTS True if one or more points are disabled<br />

ERROR_NUM Error Number:<br />

0 = No error<br />

1 = Error in maximum time<br />

2 = I/O function block error. IO_ERROR is nonzero<br />

3 = Function block error. System status or MP<br />

Status<br />

Table 14 Alarm Output Parameter Operation in EX02_SHUTDOWN<br />

Parameter Description<br />

ALARM_PROGRAMMING_PERMITTED To remind the operator to lock out programming<br />

changes after a download change, or <strong>for</strong> applications<br />

in which download changes are not allowed, connect<br />

the ALARM_PROGRAMMING_PERMITTED output<br />

to an alarm<br />

ALARM_REMOTE_ACCESS For applications in which remote changes are not<br />

allowed, connect the ALARM_REMOTE_ACCESS<br />

output to an alarm<br />

ALARM_RESPONSE_TIME Total response time depends primarily on the actual<br />

scan time. To meet the required response time of the<br />

process, set the MAX_SCAN_TIME input to less than<br />

50% of the required response time. When the actual<br />

scan time exceeds the MAX_SCAN_TIME value, the<br />

ALARM_RESPONSE_TIME output becomes true<br />

ALARM_DISABLED_POINTS A project should not contain disabled points unless<br />

there is a specific reason <strong>for</strong> disabling them, such as<br />

initial testing or maintenance. To remind an operator<br />

that some points are disabled, connect the<br />

ALARM_DISABLED_POINTS output to an alarm<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Trident</strong> <strong>v2</strong> <strong>Systems</strong>