52 Chapter 4 Application Development<br />

Program EX01_SHUTDOWN<br />

T#3d<br />

T#400ms<br />

CRITICAL_MODULES<br />

SYS_SHUTDOWN<br />

CI<br />

CO<br />

IO_CO<br />

OPERATIING<br />

IO_TMR<br />

TMR<br />

IO_GE_DUAL<br />

DUAL<br />

IO_GE_SINGLE<br />

SINGL<br />

IO_NO_VOTER_FLTS<br />

ZERO<br />

IO_ERROR<br />

TIMER_RUNNING<br />

MAX_TIME_DUAL<br />

TIME_LEFT<br />

MAX_TIME_SINGLE ALARM_PROGRAMMING_PERMITTED<br />

MAX_SCAN_TIME<br />

ALARM_REMOTE_ACCESS<br />

ALARM_RESPONSE_TIME<br />

ALARM_DISABLED_POINTS<br />

ERROR<br />

001<br />

Figure 10 EX01_SHUTDOWN Sample Program<br />

CO false indicates a programming error; <strong>for</strong> example, MAX_TIME_SINGLE greater than<br />

MAX_TIME_DUAL. The error number shows more detail.<br />

Table 9 Input Parameters <strong>for</strong> SYS_SHUTDOWN Function Block in EX01_SHUTDOWN<br />

Parameter Description<br />

CI Do not connect when all I/O modules are system-critical<br />

IO_CO Do not connect when all I/O modules are system-critical<br />

IO_TMR Do not connect when all I/O modules are system-critical<br />

IO_GE_DUAL Do not connect when all I/O modules are system-critical<br />

IO_GE_SINGLE Do not connect when all I/O modules are system-critical<br />

IO_NO_VOTER_FLTS Do not connect when all I/O modules are system-critical<br />

IO_ERROR Do not connect when all I/O modules are system-critical<br />

MAX_TIME_DUAL Maximum time with only two channels operating<br />

MAX_TIME_SINGLE Maximum time with only one channel operating<br />

MAX_SCAN_TIME 50% of the maximum response time<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Trident</strong> <strong>v2</strong> <strong>Systems</strong><br />

CRITICAL_MODULES_OPERATING<br />

ALARM_PROGRAMMING_PERMITTED<br />

ALARM_REMOTE_ACCESS<br />

ALARM_RESPONSE_TIME<br />

ALARM_DISABLED_POINTS